Omron ZS-MDC Error Messages and Countermeasures, When Error Is Displayed on the Main Display

Page 79

Section 5

Error Messages and Countermeasures

Error Messages and Countermeasures

When [Error] Is Displayed on the Main Display

 

Display Details

Cause

Countermeasure

LCD screen

 

Overcurrent

One or all of the judgment out-

Cancel the load short-circuit.

(upper section)

 

puts are short-circuited.

(Recovery is automatic after the

 

 

 

 

load short-circuit is canceled.)

 

 

 

 

 

 

 

Calculation data error

One (or all) of the channels

Check the measurement state of

 

 

 

assigned to the operation input

the channels assigned to the oper-

 

 

 

cannot be measured.

ation input, and set all channels to

 

 

 

 

a measurable state.

 

 

 

 

 

When all digits on the main display and sub-display blink

 

Display Details

Cause

Countermeasure

 

 

LCD screen

 

SYSTEM ERROR

The controller is not connected.

Connect the Controller.

 

Section5

 

 

BANK DATA

ler in error

onds, and then hold the DOWN

 

 

 

CONNECT

 

 

 

 

 

 

SYSTEM ERROR

Bank data in the Sensor Control-

Hold the UP key down for 3 sec-

 

 

 

 

 

 

key down for 3 seconds.

 

 

 

 

SYSTEM ERROR

Internal error

APPENDIX

 

 

Turn the sensor ON again.

 

 

 

 

 

The sensor is turned ON again

 

 

 

 

 

 

and restored after the device is

 

 

 

 

 

 

initialized.

 

 

 

 

MAIN COM

 

 

 

 

 

 

 

 

 

 

 

Others

 

Display Details

Cause

Countermeasure

LCD upper sec-

 

Disp range error

The measurement result

Change the decimal point digit

tion

 

 

exceeds the number of dis-

setting.

 

 

 

played digits.

 

 

 

 

 

 

Main Display

 

– – – – – –

• The sensor is standing by

• When hold is set, start sam-

 

 

 

for measurement.

pling and apply the hold

 

 

 

• No channels are assigned

value.

 

 

 

to inputs. (Assignments

• Assign the channels.

 

 

 

are set to “NONE”.)

 

 

 

 

 

 

ZS-MDC

User’s Manual

5-3

Image 79
Contents Smart Sensor Introduction How to Switch the Display Language to EnglishSmart Sensors Multi-Controller ZS-MDC EctionRead and Understand this Document Suitability for USE Dimensions and Weights Power Supply and Wiring Installation EnvironmentOthers Installation Site Precautions for Correct UseMaintenance and Inspection Orientation when Installing the Multi-ControllerWarming Up Format Editors NoteVisual Aids Meaning of SymbolsMemo Contents Introduction Contents Features Completely Digitally Based Logic Operation Processing Multi-Controller FeaturesSupports Connection to Up to 9 Sensor Controllers Wide Range of Logic Operation FunctionsUSB Connection Same Compact Size as Sensor ControllerDedicated Software SmartMonitor Zero Measurement of Average Workpiece Height Multi-Controller ApplicationsMeasurement of Workpiece Thickness at Multiple Locations Measurement of Stepped WorkpiecesMeasurement of Workpiece Strain Measurement of Workpiece FlatnessBatch-acquisition of Multi-point Measurement Data State of gang-mounted Sensor Controllers can be monitored Gang-mounted Sensor Controllers can be set upZS-MDC11/MDC41 Basic ConfigurationPart Names and Functions Pass indicator Mode SwitchThreshold Selector Switch LOW indicatorMemo Installation & Connection Installation & ConnectionAbout the power supply About Installation and ConnectionChecking the installation environment Checking the installation siteAttaching the ferrite core Multi-ControllerAbout channel No. when controllers are gang-mounted Installing the Multi-ControllerCH0 CH1 CH2 CH3 CH9 Installation procedure Installing on the DIN trackPFP-M Removal procedure Open the connector cover on the con- trollerInstall the cover on the coupler of the controller Installation & Connection Mounting on a panel InstallationHook the hooks of the mounting fixture Install the Multi-Controller and SensorController with Panel Mount Adapters Attached onto the panel from the frontAbout the I/O cable Wiring the I/O cableLinear GND OUT3 Enable outputOUT4 Busy output Linear outputNPN type ZS-MDC11 Installation & Connection Circuit DiagramsPNP type ZS-MDC41 Memo Setup Installation and Connection Setting FlowWhen a Problem Occurs Switching Modes About SetupBasic Knowledge for Operation Displays and Key Operations FUN ModePress the Menu key to return to the top menu Press function key 2 representing onResolu RUN ModeThresh Voltage CurrentTeaching Direct Teach ModeFUN Mode List of Setting ItemsWhen TASK1 is selected SET NO-MEAS TimerAdjust COM ModeBank System When other than TASK1 is selectedTeach Mode RUN ModeSelecting Tasks Setting Assignments Setting Logic Operation Methods Switching banks by external signal input Setting I/O AssignmentsTASK3 TASK4 Changing Output AssignmentsChanging Linear Output Assignments About Digital OutputMemo Application Setting Examples Application Setting ExamplesExamples Application SettingSet the expression of TASK1 Select TASK1SENSING-CALC-CALC-MAX-MIN Application Measuring the Relative Difference between StepsSet the expression of TASK1 Following the same procedure as 2 to 3, set Up TASK3To linear-output the operation result I/O SET-I/O SET-ANALOG Measuring the Reference Difference between Steps Select TASK1 or TASK2 depending on Following the same procedure as 2 to 3, set Up TASK2Details to be output CH0 CH1 CH2 CH3 CH9 Measuring FlatnessTASK12 TASK2 TASK34 TASK4 Input a Input B Input C Measuring the Average Height Select TASK1 so that the average value can be linear-output Average to ON, and other inputs to OFFCH0 CH1 CH2 CH3 CH4 Measuring the Twist of a WorkpieceInput X Input D Input Y Input C Select TASK3 so that the twist value can be linear-output Select TASK3 so that the judgment on the twist can be outputCH0 CH1 CH2 CH3 Measuring the Warp of a WorkpieceSelect TASK1 Application Setting Examples Select TASK2 so that the warp value can be linear-output Select TASK2 so that the judgment on the warp can be output Memo Appendix Troubleshooting Others Error Messages and CountermeasuresWhen Error Is Displayed on the Main Display When all digits on the main display and sub-display blinkOr more of the rated measuring range Glossary Multi-Controller Specifications and External DimensionsPASS/LOW ZS-MDC11 ZS-MDC41Shock resistance destructive ZS-XPM1/XPM2 Panel Mount AdaptersZS-XRS2 RS-232C Cable for Connecting to a Personal ComputerZS-XCN Controller Link UnitVer1.00 to Ver1.50 Version Up InformationVer1.50 to Ver2.00 Section Index IndexUSB Memo Z209-E1-01 Revision HistoryTerms and Conditions of Sale Omron Electronics LLC