| INSTALLATION | |||||
TECHNICAL SPECIFICATIONS – IDEALARC® |
|
| |||||
|
|
|
|
|
|
| |
|
| INPUT - THREE PHASE ONLY |
|
| |||
CODES | Standard |
|
| Input Current at Rated Output |
| ||
| Voltage |
| 100% Duty Cycle |
| 60% Duty Cycle | 50% Duty Cycle |
|
|
|
|
|
|
|
|
|
11613, 11707 | 230/460/575/60 |
| 108/54/43 |
| 122/61/49 | 134/67/54 |
|
11598, 11725 | 415/50/60 |
| 62 |
| 68 | 73 |
|
|
|
|
|
|
|
|
|
RATED OUTPUT
Duty Cycle
100% Duty Cycle
60% Duty Cycle
50% Duty Cycle
Output Range
Amps
600
680
750
OUTPUT
Maximum Open Circuit Voltage
5V for 60 HZ models
5V for 50/60 HZ models
Volts at Rated Amperes
44
44
44
Auxiliary Power
See the OPERATION section
for Auxiliary Power
information by model
RECOMMENDED INPUT WIRE AND FUSE SIzES
INPUT | HERTz | INPUT AMPERE | TYPE 75°C | TYPE 75°C | TYPE 75°C | |
COPPER WIRE | GROUND WIRE | (SUPER LAG) | ||||
VOLTAGE / |
| RATING ON | ||||
| IN CONDUIT | IN CONDUIT | OR bREAKER | |||
FREQUENCY |
| NAMEPLATE | ||||
| SIzE (AMPS)1 | |||||
|
|
| ||||
|
|
| 30°C (86°F) Ambient |
|
| |
230 | 60 | 108 | 2 (34) | 6 (14) | 175 Amp | |
460 | 60 | 54 | 6 (14) | 8 (8.4) | 90 Amp | |
575 | 60 | 43 | 8 (8.4) | 8 (8.4) | 70 Amp | |
415 | 50/60 | 61 | 6 (14) | 8 (8.4) | 100 Amp | |
|
|
|
|
|
|
PHYSICAL DIMENSIONS
HEIGHT | WIDTH | DEPTH | WEIGHT |
30.75 in | 22.25 in | 39.0 in | 525 lbs. |
781 mm | 567 mm | 988 mm | 238 kg. |
|
|
|
|
1Also called “inverse time” or “thermal/magnetic” circuit breakers; circuit breakers which have a delay in tripping action that decreases as the magnitude of the current increases.
IDEALARC®