The Vantage is shipped with the negative battery cable disconnected. Before you operate the machine, make sure the Engine Switch is in the OFF position and attach the disconnected cable securely to the negative (-) battery terminal.

Remove the insulating cap from the negative battery terminal. Replace and tighten negative battery cable terminal. NOTE: This machine is furnished with a wet charged battery; if unused for several months, the battery may require a booster charge. Be sure to use the correct polarity when charging the battery.

MUFFLER OUTLET PIPE

Remove the plastic plug covering the muffler outlet tube. Using the clamp provided secure the outlet pipe to the outlet tube with the pipe positioned such that it will direct the exhaust in the desired position.

SPARK ARRESTOR

Some federal, state or local laws may require that petrol or diesel engines be equipped with exhaust spark arrestors when they are operated in certain locations where unarrested sparks may present a fire hazard. The standard muffler included with this welder does not qualify as a spark arrestor. When required by local regulations, a suitable spark arrestor, must be installed and properly maintained.

CAUTION

An incorrect arrestor may lead to damage to the engine or adversely affect performance.

--------------------------------------------------------------------------------------

WELDING TERMINALS

The Vantage is equipped with a toggle switch for selecting "hot" welding terminals when in the "WELD TERMINALS ON" position or "cold" welding terminals when in the "REMOTELY CONTROLLED" position.

WELDING OUTPUT CABLES

With the engine off, route the electrode and work cables thru the strain relief bracket provided on the front of the base and connect to the terminals provided. These connections should be checked periodically and tightened if necessary.

Listed in Table A.1 are copper cable sizes recommended for the rated current and duty cycle. Lengths stipulated are the distance from the welder to work and back to the welder again. Cable sizes are increased for greater lengths primarily for the purpose of minimizing cable voltage drop.

Table A.1 Combined Length of Electrode and Work Cables.

 

TOTAL COMBINED LENGTH OF

 

ELECTRODE AND WORK CABLES

 

 

 

 

AMPS

Up to 150ft

150-200ft

200-250ft

@100%

 

 

 

Duty Cycle

 

 

 

500

3/0 AWG

3/0 AWG

4/0 AWG

 

 

 

 

MACHINE GROUNDING

Because this portable engine driven welder creates its own power, it is not necessary to connect its frame to an earth ground, unless the machine is connected to premises wiring (home, shop, etc.).

To prevent dangerous electric shock, other equipment powered by this engine driven welder must:

a)be grounded to the frame of the welder using a grounding type plug,

or

b) be double insulated.

When this welder is mounted on a truck or trailer, its frame must be securely connected to the metal frame of the vehicle. When this engine driven welder is connected to premises wiring such as that in a home or shop, its frame must be connected to the system earth ground. See further connection instructions in the section entitled “Standby Power Connections” as well as the article on grounding in the latest National Electrical Code and the local codes.

In general, if the machine is to be grounded, it should be connected with a #8 or larger copper wire to a solid earth ground such as a metal ground stake going into the ground for at least 10 Feet or to the metal framework of a building which has been effectively grounded. The National Electric Code lists a number of alternate means of grounding electrical equipment. A machine

grounding stud marked with the symbol is provided on the front of the welder.

Vantage 500 DEUTZ

Image 13
Contents Vantage 500 Deutz California Proposition 65 Warnings SafetyElectric Shock can kill Welding Sparks can cause fire or explosion Sûreté Pour Soudage a L’Arc Précautions DE SûretéThank You Table of Contents Vii Installation Safety Precautions InstallationLocation / Ventilation Lifting High Temperature OperationHigh Altitude Operation TowingEngine Cooling System PRE-OPERATION Engine ServiceEngine BREAK-IN Welding Terminals 5INSTALLATIONA-5Auxiliary Power Receptacles Remote ControlStandby Power Connections OutputFigure A.2 Connection of the Vantage to Premises Wiring Connection of AN LN-23P Wire Feeder to the Vantage Connection of Lincoln Electric Wire FeedersConnection of LN-7, LN-8 or LN-742 to the Vantage Connection of LN-15 to the VantageVantage 500 Deutz Connection of the LN-25 to the VantageOperation Safety InstructionsGeneral Description RUN Controls and SettingsWelding Controls Items 9 through Engine Operation Auxiliary Power ControlsStarting the Engine Stopping the EngineWelder Operation For Tungsten Electrodes OperationAuxiliary Power Operation Operation Optional Field Installed Accessories AccessoriesRoutine and Periodic Maintenance MaintenanceEngine Maintenance Fuel Filters Fuel PRE-FILTER/WATER Separator AssemblyWater Separator Element Secondary Fuel FilterCooling System Cooling Blower Belt Battery HandlingWelder / Generator Maintenance HOW to USE Troubleshooting Guide TroubleshootingPossible Areas Misadjustments Course of ActionFunction Problems 500 Connection Diagram DIAGRAMSF-2Diagram Commander / K867 / K775 / LN-7 Connection DiagramDiagrams Diagrams Commander / K867 / LN-8 Connection Diagram Diagrams Diagrams Engine Welders /LN-8 Connection Diagram Diagrams Diagrams Diagrams Diagrams Dimension Print Vantage 500 Deutz Ground Insulate yourself from workMojada Inflammable Votre corps Avec des pièces sous tensionGuards off Keep your head out of fumes Turn power off before servicingHumos. Utilice ventilación o Servicio Aspiración para gases Débranchez le courant avant Utilisez un ventilateur ou un