INSTALLATION |
2.Take necessary steps to assure load is limited to the capacity of the Vantage by installing a 50 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 50 amps. Loading above the rated output will reduce output voltage below the allowable
3.Install a 50 amp 120/240 VAC plug (NEMA Type
4.Plug this cable into the 50 Amp 120/240 Volt receptacle on the Vantage case front.
Figure A.2 Connection of the Vantage to Premises Wiring
240Volt
60 Hz.
Service
240 VOLT
POWER
120 VOLT
COMPANY
120 VOLT
METER
GROUNDED CONDUCTOR
NEUTRAL
BUS
N
DOUBLE POLE DOUBLE THROW |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| LOAD | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
SWITCH RATING TO BE THE SAME |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
AS OR GREATER THAN PREMISES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
SERVICE OVERCURRENT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
PROTECTION. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| PREMISES | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| DISCONNECT AND | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SERVICE | ||
|
|
|
|
|
|
|
| GROUND | ||||||||||||
|
|
|
| 50AMP | OVERCURRENT | |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| PROTECTION | ||||||
|
|
|
| 240 VOLT |
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
| DOUBLE |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
50 AMP, 120/240 |
|
| POLE |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
| CIRCUIT |
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
VOLT PLUG | 240 VOLT |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
BREAKER |
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
NEMA TYPE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GND
|
| N |
|
50 AMP, 120/240 VOLT |
| NOTE: No. 6 COPPER CONDUCTOR CABLE SEE | |
RECEPTACLE |
| ||
|
| NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE | |
|
|
| SIZE RECOMMENDATIONS. |
Vantage 500 DEUTZ