Carrier 33CSPREMLK specifications Space Temperature Sensor Typical Wiring 33ZCT55SPT

Page 10

Table 3 — Thermistor Resistance vs Temperature

Values for Space Temperature Sensor, Supply Air Temperature Sensor, and

Outdoor Air Temperature Sensor

TEMP

TEMP

RESISTANCE

(C)

(F)

(Ohms)

–40

–40

335,651

–35

–31

242,195

–30

–22

176,683

–25

–13

130,243

–20

–4

96,974

–15

5

72,895

–10

14

55,298

–5

23

42,315

0

32

32,651

5

41

25,395

10

50

19,903

15

59

15,714

20

68

12,494

25

77

10,000

30

86

8,056

35

95

6,530

40

104

5,325

45

113

4,367

50

122

3,601

55

131

2,985

60

140

2,487

65

149

2,082

70

158

1,752

1

2

3

4

5

6

RED(+)

 

 

 

 

 

 

 

 

 

 

 

 

 

WHT(GND)

CCN COM

 

 

 

 

 

 

BLK(-)

 

 

 

 

 

 

 

 

 

 

SEN

 

 

 

 

 

SW1

 

 

 

 

 

 

 

 

 

 

 

BRN (GND)

SENSOR WIRING

 

 

 

 

 

BLU (SPT)

 

Fig. 3 — Space Temperature Sensor

Typical Wiring (33ZCT55SPT)

1

2

3

4

5

6

RED(+)

 

 

 

 

 

 

 

 

 

 

 

 

 

WHT(GND)

CCN COM

 

 

 

 

 

 

BLK(-)

 

 

 

 

 

 

 

 

 

 

SEN

 

SET

 

 

 

SW1

 

 

 

 

BLK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(T56)

 

 

 

 

 

 

BRN (GND)

SENSOR WIRING

 

 

 

 

 

BLU (SPT)

 

 

 

 

 

 

 

 

JUMPER

 

 

 

 

 

 

 

TERMINALS

 

 

 

 

 

 

 

AS SHOWN

Cool Warm

Fig. 4 — Space Temperature Sensor

Typical Wiring (33ZCT56SPT)

SUPPLY AIR TEMPERATURE (SAT) SENSOR INSTAL- LATION — The 33ZCSENSAT supply air temperature sensor is required for controller operation. The sensor consists of a thermistor encased within a stainless steel probe. The SAT sensor probe is 6-in. nominal length with 114 in. of unshielded, 2-conductor 18 AWG twisted-pair cables. The sensor tempera- ture range is –40 to 245 F with a nominal resistance of 10,000 ohms at 77 F. The sensor measures accuracy of ±0.36 F. The SAT sensor is supplied with a gasket and 2 self-drilling mounting screws.

NOTE: The sensor must be mounted in the discharge of the unit, downstream of the cooling coil and heat exchanger. Be sure the probe tip does not come in contact with any of the unit surfaces. See Fig. 11 for mounting location.

Do not run sensor or relay wires in the same conduit or race- way with Class 1 AC service wiring. Do not abrade, cut, or nick the outer jacket of the cable. Do not pull or draw cable with a force that may harm the physical or electrical properties. Avoid splices in any control wiring.

Perform the following steps to connect the SAT sensor to the PremierLink™ controller:

1.Locate the opening in the control box. Pass the sensor probe through the hole.

2.Drill or punch a 1/2-in. hole in the supply air duct.

3.Use two field-supplied, self-drilling screws to secure the sensor probe to the duct.

4.Connect the sensor leads to the PremierLink controller’s wiring harness J6-3,4 board at the terminals labeled SAT (ORN) and GND (BRN).

10

Image 10
Contents Installation, Start-Up Configuration Instructions Installation PremierLink Controller Inputs and Outputs Typical PremierLink Control Wiring 38AKS013-024 Units Typical PremierLink Control Wiring 38ARD012 Units Typical PremierLink Control Wiring 38AH024-034 Units Typical PremierLink Control Wiring 38AQ007 Units PremierLink Connections Color Code Recommendations Space Temperature Sensor Typical Wiring 33ZCT55SPT T58 Communicating Sensor Typical Wiring 33ZCT58SPT Sampling of airSpace Temperature Averaging Page Page Page Page Outdoor Air Quality Sensor Cover Recommended Cables 33CSENTHSW Used with Differential Enthalpy Control only Differential Enthalpy Control Wiring On the adapter connects to P terminal on the actuator Using the transformer supplied with the 40RM econoAdapter onto terminals P1 and P of actuator See FigPage Actuator Drive Direction Settings Mode Selection Information24 VAC/VDC START-UP PremierLink Navigator Carrier SAT 54.2 FDefault Value Display Range Network Access Read Only Supply Air Temperature Display UnitsControl Set Point Display Units Points Display Description Value Units Status Force NameMillion implied Indoor Air Quality ppm Display UnitsSet Point Display Units Thermostat Control Input Display Alarm Service ConfigurationController Identification Holiday Configuration Occupancy ConfigurationRange Default Value Set Point ConfigurationDefault Value Enable Stage Time Guard Range Service Configuration SelectionNumber of Stages Range Default Value Time Guard Default Value EnablePage Max Offset Adjustment Units Delta Degrees F Range 50.0 to Default Value 55.0Space Temperature Trim Units Delta Degrees F For Electric Heat PremierLink Control ConfigurationAuxiliary Output Range Default Value Heat Start Bias Units MON, TUE, WED Occupancy Maintenance IAQ Maintenance YesPage Copyright 2002 Carrier Corporation