HH57AC077
ENTHALPY
CONTROL
BRACKET
HH57AC078 ENTHALPY |
|
SENSOR (USED WITH |
|
ENTHALPY CONTROL | C7400A1004 |
FOR DIFFERENTIAL | |
ENTHALPY OPERATION) | + |
MOUNTING PLATE
Fig. 22 — Differential Enthalpy Control,
Sensor and Mounting Plate (33AMKITENT006)
Fig. 23 — Location of Differential Enthalpy Controller and Return Air Enthalpy Sensor (40RM Unit Shown)
Q769B — Because the Honeywell adapter is designed for a negative 4 to 20 mA input instead of a positive signal, the Q769B adapter requires a separate transformer and a current loop isolator to perform properly. Connecting the adapter directly to the PremierLink controller could cause the 4 to 20 mA output on the controller to be permanently dam- aged. This condition is followed by a constant 36 vdc output from the PremierLink™ economizer output
The Q769B adapter is supplied with female
To connect the Q769B adapter to the actuator, follow these steps and refer to Fig. 26:
1.Remove power from unit.
2.Remove the logic module from the actuator and discard.
3.Mount the adapter on the actuator by gently pushing the adapter onto the P1 and P terminals on actuator.
NOTE: Be sure the plus (+) terminal on the adapter con- nects to P1 on the actuator and the minus
4.Using
5.Using the transformer supplied with the 40RM econo- mizer, connect 24 vac to actuator terminals TR and TR1.
6.Connect the plus (+) terminal from the loop isolator to
7.Restore power to unit.
Q769C — The Q769C adapter incorporates a female quick- connect terminal that attaches to P1 and P male
IMPORTANT: It is recommended that the Q769C adapter be used with a
To connect the Q769C adapter to the actuator, follow the steps below and refer to Fig. 27:
1. | Remove power from unit. |
2. | Remove the logic module from the actuator and discard. |
3. | Mount the adapter onto the actuator by gently pushing the |
A B C TR
D SO |
SR |
2 |
TR1
+
+
3
BRN
RED
BLK
RED
S (RETURN AIR
+ENTHALPY
SENSOR)
| adapter onto terminals P1 and P of actuator. |
4. | NOTE: Be sure the plus (+) terminal on the adapter |
| connects to P1 on the actuator and the minus |
| on the adapter connects to P terminal on the actuator. |
| See Fig. 27. |
5. | Using the transformer supplied with the 40RM econo- |
LED
1
GRAY
GRAY
WIRE HARNESS IN UNIT
mizer, connect 24 vac to actuator terminals TR and TR1. |
6. Connect |
and minus |
NOTES:
1.Remove
2.Switches shown in high outdoor air enthalpy state. Terminals 2 and 3 close on low outdoor air enthalpy relative to indoor air enthalpy.
3.Remove sensor mounted on back of control and locate in out- side airstream.
Fig. 24 — Outside and Return Air Sensor Wiring Connections for Differential Enthalpy Control
7. | Connect | the plus (+) terminal from the adapter to |
| terminal | on the PremierLink Controller. Connect the |
| minus | |
| the PremierLink Controller. | |
8. | Restore power to unit. |
22