Carrier 33CSPREMLK specifications Iaq

Page 41
Display Units: Degrees F (Degrees C)
Display Range: 40.0 to 150.0
Default Value: 40
Network Access: Read Only
Display Units: Hours
Default Value: 0
Network Access: Read Only
Display Units: Hours
Default Value: 0
Network Access: Read Only

IAQ PRE-OCCUPANCY PURGE — Indicates that the pre- occupancy purge mode is currently active.

IAQ

 

 

Pre-occupancy

 

 

Purge:

Display Range:

No/Yes

 

Default Value:

No

 

Network Access:

Read Only

UNOCCUPIED FREE COOLING — Indicates that unoccu- pied free cooling is in effect.

Unoccupied Free

 

 

Cooling:

Display Range:

No/Yes

 

Default Value:

No

 

Network Access:

Read Only

FIRE SHUTDOWN — Indicates in a sensor mode that the Fire shutdown input has been sensed. This will cause the supply fan and heating and cooling to be turned off also.

Fire Shutdown: Display Range:

No/Yes

Default Value:

No

Network Access:

Read/Write

LINKAGE CONTROL — Indicates

if the controller is

receiving linkage communication.

 

Linkage Control: Display Range:

No/Yes

Default Value:

No

Network Access:

Read/Write

FIELD/STARTUP TEST — This point is used to enable field test of the controller. When forced to Yes, the controller will perform a test of all outputs and reset to “NO” at end of test. The test may be aborted at any time by forcing value to NO.

Field/Startup

 

 

Test:

Display Range:

No/Yes

 

Default Value:

No

 

Network Access:

Read/Write

HEAT SUBMASTER REFERENCE — When in sensor mode, the Heat Submaster Reference point displays the supply air temperature calculated by the heating PID loop. This value is compared to the actual supply air temperature to determine the number of required stages. When in the thermostat mode, the value displayed is zero.

Heat Submaster Reference:

COOL SUBMASTER REFERENCE — The Cool Submas- ter Reference point displays the supply air temperature calcu- lated by the cooling PID loop when in sensor mode. This value is compared to the actual supply air temperature to determine the number of required stages. When in the thermostat mode, the value displayed is zero.

Cool Submaster

 

 

Reference:

Display Units:

Degrees F (Degrees C)

 

Display Range:

40.0 to 150.0

 

Default Value:

150

 

Network Access:

Read Only

ECONOMIZER SUBMASTER REFERENCE — This point displays the supply air temperature determined by the Economizer PID calculation.

Economizer

 

 

Submaster

 

 

Reference:

Display Units:

Degrees F (Degrees C)

 

Display Range:

48 to 120

 

Default Value:

120

 

Network Access:

Read Only

ECONOMIZER SUBMASTER GAIN — Displays the cur- rent Submaster gain multiplier in use to calculate the econo- mizer damper position. At temperatures below 45 F this number will decrease to slow the rate of movement of the economizer damper.

Economizer

Submaster Gain: Display Range: –20 to 20 Default Value: –5.5 Network Access: Read Only

COMPRESSOR STARTS — Displays the total number of compressor starts.

Compressor

 

 

Starts:

Default Value:

0

 

Network Access:

Read Only

COMPRESSOR 1 RUN TIME — Displays the number of run hours of compressor no. 1.

NOTE: The clock must be set for run times to accumulate. Compressor 1

Run Time:

COMPRESSOR 2 RUN TIME — Displays the number of run hours of compressor 2.

NOTE: The clock must be set for run times to accumulate. Compressor 2

Run Time:

SUPPLY FAN RUN TIME — Displays the number of run hours of the supply fan.

NOTE: The clock must be set for run times to accumulate.

This is not the same timer used for the filter status. A sepa- rate timer is used to keep track of the run hours since the last filter change.

Supply Fan

 

 

Run Time:

Display Units:

Hours

 

Default Value:

0

 

Network Access:

Read Only

LINKAGE THERMOSTAT — The following Linkage Ther- mostat points display the standard values received from a Linkage Thermostat (if one is being used to provide space temperature, set point and occupancy information).

Linkage

Status: Display Range: 0 to 3 Default Value: 2 Network Access: None

The Supervisory Element displays the address of the device sending the linkage supervisory table to the PremierLink™ controller.

Supervisory

 

 

Element:

Default Value:

0

 

Network Access:

Read Only

The Supervisory Bus displays the bus number of the device sending the linkage supervisory table to the PremierLink controller.

Supervisory Bus: Default Value:

0

Network Access:

Read Only

The Supervisory Block displays the block or table number of the linkage table occurrence in the supervisory device. Some linkage supervisory devices may contain more than one linkage table for different air sources.

Supervisory

 

 

Block:

Default Value:

0

 

Network Access:

Read Only

41

Image 41
Contents Installation, Start-Up Configuration Instructions Installation PremierLink Controller Inputs and Outputs Typical PremierLink Control Wiring 38AKS013-024 Units Typical PremierLink Control Wiring 38ARD012 Units Typical PremierLink Control Wiring 38AH024-034 Units Typical PremierLink Control Wiring 38AQ007 Units PremierLink Connections Color Code Recommendations Space Temperature Sensor Typical Wiring 33ZCT55SPT Sampling of air T58 Communicating Sensor Typical Wiring 33ZCT58SPTSpace Temperature Averaging Page Page Page Page Outdoor Air Quality Sensor Cover Recommended Cables 33CSENTHSW Used with Differential Enthalpy Control only Differential Enthalpy Control Wiring Adapter onto terminals P1 and P of actuator Using the transformer supplied with the 40RM econoOn the adapter connects to P terminal on the actuator See FigPage Mode Selection Information Actuator Drive Direction Settings24 VAC/VDC START-UP SAT 54.2 F PremierLink Navigator CarrierControl Set Point Display Units Supply Air Temperature Display UnitsDefault Value Display Range Network Access Read Only Description Value Units Status Force Name Points DisplaySet Point Display Units Indoor Air Quality ppm Display UnitsMillion implied Controller Identification Alarm Service ConfigurationThermostat Control Input Display Occupancy Configuration Holiday ConfigurationSet Point Configuration Range Default ValueNumber of Stages Range Default Value Time Guard Service Configuration SelectionDefault Value Enable Stage Time Guard Range Default Value EnablePage Space Temperature Trim Units Delta Degrees F Range 50.0 to Default Value 55.0Max Offset Adjustment Units Delta Degrees F Auxiliary Output PremierLink Control ConfigurationFor Electric Heat Range Default Value Heat Start Bias Units MON, TUE, WED Occupancy Maintenance IAQ Yes MaintenancePage Copyright 2002 Carrier Corporation