120 VAC LINE VOLTAGE
24 VAC
SECONDARY
24 VAC OUTPUT FROM N/C CONTACT WHEN THE OUTDOOR ENTHALPY IS LESS THAN THE INDOOR ENTHALPY
(ENABLE ECONOMIZER)
24 VAC OUTPUT FROM N/O CONTACT WHEN THE OUTDOOR ENTHALPY IS GREATER THAN THE
OUTDOOR ENTHALPY
(ENABLE ENERGY RECYCLER)
HI LOW GND 24 | ||
ENTHALPY VAC | mA | VDC |
| IN | OUT |
IN OUT
LEGEND
N/C — Normally Closed
N/O — Normally Open
33CSENTHSW
JUMPER SETTINGS FOR 33CSENTHSW
M3 | M2 | M1 |
| OFF | 100% | 50% | 0% | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
33CSENTSEN
JUMPER SETTINGS FOR 33CSENTSEN
| M3 | M2 | M1 |
| OFF | 100% | 50% | 0% | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fig. 21 — Differential Enthalpy Control Wiring
Wiring Enthalpy Sensors — To wire the enthalpy sensor, per- form the following (see Fig. 24 and 25):
NOTE: To mount outdoor air sensor remotely, remove it from back of enthalpy control and follow steps 3 and 6.
1.Use a
2.At the differential enthalpy control remove the factory- installed resistor from the SR and (+) terminals.
3.Connect the RED wire from the
4.Connect the following 4 wires from the
a.Connect the RED wire to the 24 vac terminal (TR1) on enthalpy control and to pin 1 on
b.Connect the BRN wire to the 24 vac GND terminal (TR) on enthalpy sensor and to pin 4 on
c.Connect the ORN wire to
d.Connect the RED wire to
5.At the return air enthalpy sensor, strip 3 in. of jacket from
the cable and remove 1/2 in. of insulation from each conductor.
6.Connect the RED wire to (+) spade connector on the sensor. Connect the BLK wire to (S) spade connector on the sensor. Use wire nuts or
Economizer — The PremierLink™ controller will inter- face with the 40RM economizer. Economizers will contain a Honeywell actuator (Honeywell part number M7415).
An adapter (Honeywell part number Q769B or Q769C is preferred) must be used to enable the 4 to 20 mA signal from the PremierLink controller to control the position of the econo- mizer. Refer to Honeywell Q769B and Q769C accessory in- stallation instructions for wiring details.
Disconnect power supply before making wiring connec- tions to prevent electrical shock and equipment damage.
To avoid permanent damage to the PremierLink 4 to 20 mA connection, a signal loop isolator must be installed when using the Q769B adapter.