Carrier 33CSPREMLK specifications Differential Enthalpy Control Wiring

Page 21

120 VAC LINE VOLTAGE

24 VAC

SECONDARY

24 VAC OUTPUT FROM N/C CONTACT WHEN THE OUTDOOR ENTHALPY IS LESS THAN THE INDOOR ENTHALPY

(ENABLE ECONOMIZER)

24 VAC OUTPUT FROM N/O CONTACT WHEN THE OUTDOOR ENTHALPY IS GREATER THAN THE

OUTDOOR ENTHALPY

(ENABLE ENERGY RECYCLER)

HI LOW GND 24

4-20 24-36

ENTHALPY VAC

mA

VDC

 

IN

OUT

24-36 4-20 VDC mA

IN OUT

LEGEND

N/C — Normally Closed

N/O — Normally Open

33CSENTHSW

JUMPER SETTINGS FOR 33CSENTHSW

M3

M2

M1

 

OFF

100%

50%

0%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33CSENTSEN

JUMPER SETTINGS FOR 33CSENTSEN

 

M3

M2

M1

 

OFF

100%

50%

0%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 21 — Differential Enthalpy Control Wiring

Wiring Enthalpy Sensors — To wire the enthalpy sensor, per- form the following (see Fig. 24 and 25):

NOTE: To mount outdoor air sensor remotely, remove it from back of enthalpy control and follow steps 3 and 6.

1.Use a 2-conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the differential enthalpy control. Use a 4-conductor, 18 or 20 AWG cable to connect the enthalpy control to the PremierLink con- troller and power transformer.

2.At the differential enthalpy control remove the factory- installed resistor from the SR and (+) terminals.

3.Connect the RED wire from the 2-conductor cable which originates from the return air enthalpy sensor to the SR (+) terminal. Connect the BLK wire to the SR (–) terminal.

4.Connect the following 4 wires from the 4-wire conduc- tive cable to the differential enthalpy controller:

a.Connect the RED wire to the 24 vac terminal (TR1) on enthalpy control and to pin 1 on 12-pin harness.

b.Connect the BRN wire to the 24 vac GND terminal (TR) on enthalpy sensor and to pin 4 on 12-pin harness.

c.Connect the ORN wire to J4-2 on PremierLink controller and to terminal 3 on enthalpy sensor.

d.Connect the RED wire to J4-1 on PremierLink controller and to terminal 2 on enthalpy sensor.

5.At the return air enthalpy sensor, strip 3 in. of jacket from

the cable and remove 1/2 in. of insulation from each conductor.

6.Connect the RED wire to (+) spade connector on the sensor. Connect the BLK wire to (S) spade connector on the sensor. Use wire nuts or closed-end crimp-type con- nectors to fasten the connections securely. See Fig. 22.

Economizer — The PremierLink™ controller will inter- face with the 40RM economizer. Economizers will contain a Honeywell actuator (Honeywell part number M7415).

An adapter (Honeywell part number Q769B or Q769C is preferred) must be used to enable the 4 to 20 mA signal from the PremierLink controller to control the position of the econo- mizer. Refer to Honeywell Q769B and Q769C accessory in- stallation instructions for wiring details.

Disconnect power supply before making wiring connec- tions to prevent electrical shock and equipment damage.

To avoid permanent damage to the PremierLink 4 to 20 mA connection, a signal loop isolator must be installed when using the Q769B adapter.

21

Image 21
Contents Installation, Start-Up Configuration Instructions Installation PremierLink Controller Inputs and Outputs Typical PremierLink Control Wiring 38AKS013-024 Units Typical PremierLink Control Wiring 38ARD012 Units Typical PremierLink Control Wiring 38AH024-034 Units Typical PremierLink Control Wiring 38AQ007 Units PremierLink Connections Color Code Recommendations Space Temperature Sensor Typical Wiring 33ZCT55SPT Sampling of air T58 Communicating Sensor Typical Wiring 33ZCT58SPTSpace Temperature Averaging Page Page Page Page Outdoor Air Quality Sensor Cover Recommended Cables 33CSENTHSW Used with Differential Enthalpy Control only Differential Enthalpy Control Wiring Adapter onto terminals P1 and P of actuator Using the transformer supplied with the 40RM econoOn the adapter connects to P terminal on the actuator See FigPage Mode Selection Information Actuator Drive Direction Settings24 VAC/VDC START-UP SAT 54.2 F PremierLink Navigator CarrierSupply Air Temperature Display Units Default Value Display Range Network Access Read OnlyControl Set Point Display Units Description Value Units Status Force Name Points DisplayIndoor Air Quality ppm Display Units Million impliedSet Point Display Units Alarm Service Configuration Thermostat Control Input DisplayController Identification Occupancy Configuration Holiday ConfigurationSet Point Configuration Range Default ValueNumber of Stages Range Default Value Time Guard Service Configuration SelectionDefault Value Enable Stage Time Guard Range Default Value EnablePage Range 50.0 to Default Value 55.0 Max Offset Adjustment Units Delta Degrees FSpace Temperature Trim Units Delta Degrees F PremierLink Control Configuration For Electric HeatAuxiliary Output Range Default Value Heat Start Bias Units MON, TUE, WED Occupancy Maintenance IAQ Yes MaintenancePage Copyright 2002 Carrier Corporation