Carrier 33CSPREMLK specifications Actuator Drive Direction Settings, Mode Selection Information

Page 24

TR

 

24 VAC

 

 

24 VAC

 

 

 

 

TR1

 

 

 

 

 

 

TRANSFORMER

 

 

T

 

 

 

 

SENSOR

 

 

 

 

T1

 

 

PREMIERLINK

 

 

Q769B

 

 

CONTROL

 

 

ADAPTER

 

 

 

J9

 

 

 

 

P1

+

- +

 

 

 

 

 

MIN.

 

 

2

1

POS

-

 

 

 

 

P

 

LOOP

 

 

 

ISOLATOR

 

M7415

 

+

-

 

 

 

 

 

ACTUATOR

 

 

 

 

 

 

-

+

 

Fig. 26 — PremierLink™ Control Wiring to

Q769B Adapter and Actuator

TR

 

24 VAC

 

 

 

24 VAC

 

 

 

 

 

 

TR1

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

(SEPARATE,

 

 

T

 

 

FIELD-SUPPLIED)

 

 

 

 

 

 

 

 

SENSOR

 

 

 

 

 

 

T1

 

 

 

 

PREMIERLINK

 

 

Q769C

 

 

 

 

CONTROL

 

 

ADAPTER

 

 

J9

P1

+

-

+

500 OHM

 

 

 

 

 

MIN.

 

 

 

2

1

POS

-

 

 

RESISTOR

 

 

 

 

P

 

 

 

 

 

 

M7415

 

 

 

 

 

 

ACTUATOR

 

 

 

 

 

 

Fig. 27 — PremierLink Control Wiring to

Q769C Adapter and Actuator

Economizer with Johnson 4 to 20 mA Actua- tor — The PremierLink Controller can be connected to an economizer that uses a Johnson 4 to 20 mA actuator.

DRIVE DIRECTION — The actuator drive direction is dependent upon the position of Switch 3 and the spring return direction. See Table 5. The actuator is factory set for Direct Acting (DA) operation with Switch 3 in the DA position. An increasing control signal drives the actuator away from the spring return position in DA mode. The actuator should be installed in the DA mode so damper will close automatically on power shut down.

If Reverse Acting (RA) operation is desired, move Switch 3 to the RA position. An increasing control signal drives the actuator toward the spring return position in RA mode.

SWITCH SELECTION — The type of input control signal is determined by the position of Switch 5. With Switch 5 in the VDC position (factory setting), the signal is DC voltage. With Switch 5 min the mA position, the input signal changes to current input. See Fig. 28 and Table 6. The switch should be set to mA for use with PremierLink controller.

NOTE: To change the factory setting, use a 1/8-in. (3-mm) flat-blade screwdriver to position the mode switch to the alter- nate setting.

Table 5 — Actuator Drive Direction Settings

POSITION OF

 

 

SWITCH 3 AND THE

DRIVE DIRECTION

DRIVE DIRECTION

DIRECTION OF

WITH A MINIMUM

WITH A MAXIMUM

SPRING RETURN

INPUT SIGNAL

INPUT SIGNAL

DRIVE

 

 

DA/CCW

CCW

CW

RA/CCW

CW

CCW

DA/CW

CW

CCW

RA/CW

CCW

CW

LEGEND

 

 

CCW — Counterclockwise

CW — Clockwise

DA — Direct Action

RA — Reverse Action

Table 6 — Mode Selection Information

MODE

SWITCH FUNCTIONS

FACTORY

SWITCHES

SETTINGS

 

5

VDC or mA

VDC

4

0 to 10 VDC (0 to 20 mA or

0 to 10

2 to 10 VDC (4 to 20 mA)

 

 

3

Direct Acting (DA) or

DA

Reverse Acting (RA)

 

 

2

FIXED or AUTO

FIXED

1

— or 6 to 9 VDC

NOTE: The 6 to 9 VDC setting of Switch 1 overrides switch 4.

WIRING (See Fig. 29-30B) — The wires for power and signal transmission from PremierLink to economizer are field- supplied. To connect the Economizer Johnson Actuator to PremierLink controller, connect the pink wire on actuator to purple wire on PremierLink J9-1. See Fig. 30A.

For the Belimo Actuator, connect the white wire on the ac- tuator to J9-1 on the PremierLink controller. See Fig. 30B.

NOTE: To retrofit PremierLink Controller to older 4 to 20 mA actuator, connect the red wire on the actuator wire harness to the purple wire on the PremierLink J9-1. Connect the yellow and white wires from the actuator wire harness to the 24-volt AC transformer on equipment. See Fig. 29.

IMPORTANT: Make sure the common side is grounded for both the PremierLink power and the actuator power. This is especially important if separate transformers are used.

MOVE TO LEFT

FOR 4-20mA CONTROL

WITH PREMIERLINK

CONTROLLER

VDC

5

mA

0-10

4

2-10

DA

3

RA

FIXED

2

AUTO

1 6-9

Fig. 28 — Position of Actuator Mode Switches

(Factory Default)

24

Image 24
Contents Installation, Start-Up Configuration Instructions Installation PremierLink Controller Inputs and Outputs Typical PremierLink Control Wiring 38AKS013-024 Units Typical PremierLink Control Wiring 38ARD012 Units Typical PremierLink Control Wiring 38AH024-034 Units Typical PremierLink Control Wiring 38AQ007 Units PremierLink Connections Color Code Recommendations Space Temperature Sensor Typical Wiring 33ZCT55SPT T58 Communicating Sensor Typical Wiring 33ZCT58SPT Sampling of airSpace Temperature Averaging Page Page Page Page Outdoor Air Quality Sensor Cover Recommended Cables 33CSENTHSW Used with Differential Enthalpy Control only Differential Enthalpy Control Wiring Using the transformer supplied with the 40RM econo Adapter onto terminals P1 and P of actuatorOn the adapter connects to P terminal on the actuator See FigPage Actuator Drive Direction Settings Mode Selection Information24 VAC/VDC START-UP PremierLink Navigator Carrier SAT 54.2 FSupply Air Temperature Display Units Default Value Display Range Network Access Read OnlyControl Set Point Display Units Points Display Description Value Units Status Force NameIndoor Air Quality ppm Display Units Million impliedSet Point Display Units Alarm Service Configuration Thermostat Control Input DisplayController Identification Holiday Configuration Occupancy ConfigurationRange Default Value Set Point ConfigurationService Configuration Selection Number of Stages Range Default Value Time GuardDefault Value Enable Stage Time Guard Range Default Value EnablePage Range 50.0 to Default Value 55.0 Max Offset Adjustment Units Delta Degrees FSpace Temperature Trim Units Delta Degrees F PremierLink Control Configuration For Electric HeatAuxiliary Output Range Default Value Heat Start Bias Units MON, TUE, WED Occupancy Maintenance IAQ Maintenance YesPage Copyright 2002 Carrier Corporation