Fig. 26 — PremierLink™ Control Wiring to
Q769B Adapter and Actuator
TR |
| 24 VAC |
|
|
| |
24 VAC |
|
|
|
|
|
|
TR1 |
|
|
|
|
|
|
|
|
| TRANSFORMER |
|
| |
|
|
| (SEPARATE, |
|
| |
T |
|
|
|
| ||
|
|
|
|
|
| |
SENSOR |
|
|
|
|
|
|
T1 |
|
|
|
| PREMIERLINK | |
|
| Q769C |
| |||
|
|
| CONTROL | |||
|
| ADAPTER |
|
| J9 | |
P1 | + | - | + | 500 OHM |
|
|
|
|
| ||||
MIN. |
|
|
| 2 | 1 | |
POS | - |
|
| RESISTOR | ||
|
|
|
| |||
P |
|
|
|
|
|
|
M7415 |
|
|
|
|
|
|
ACTUATOR |
|
|
|
|
|
|
Fig. 27 — PremierLink Control Wiring to
Q769C Adapter and Actuator
Economizer with Johnson 4 to 20 mA Actua- tor — The PremierLink Controller can be connected to an economizer that uses a Johnson 4 to 20 mA actuator.
DRIVE DIRECTION — The actuator drive direction is dependent upon the position of Switch 3 and the spring return direction. See Table 5. The actuator is factory set for Direct Acting (DA) operation with Switch 3 in the DA position. An increasing control signal drives the actuator away from the spring return position in DA mode. The actuator should be installed in the DA mode so damper will close automatically on power shut down.
If Reverse Acting (RA) operation is desired, move Switch 3 to the RA position. An increasing control signal drives the actuator toward the spring return position in RA mode.
SWITCH SELECTION — The type of input control signal is determined by the position of Switch 5. With Switch 5 in the VDC position (factory setting), the signal is DC voltage. With Switch 5 min the mA position, the input signal changes to current input. See Fig. 28 and Table 6. The switch should be set to mA for use with PremierLink controller.
NOTE: To change the factory setting, use a
Table 5 — Actuator Drive Direction Settings
POSITION OF |
|
|
SWITCH 3 AND THE | DRIVE DIRECTION | DRIVE DIRECTION |
DIRECTION OF | WITH A MINIMUM | WITH A MAXIMUM |
SPRING RETURN | INPUT SIGNAL | INPUT SIGNAL |
DRIVE |
|
|
DA/CCW | CCW | CW |
RA/CCW | CW | CCW |
DA/CW | CW | CCW |
RA/CW | CCW | CW |
LEGEND |
|
|
CCW — Counterclockwise
CW — Clockwise
DA — Direct Action
RA — Reverse Action
Table 6 — Mode Selection Information
MODE | SWITCH FUNCTIONS | FACTORY | |
SWITCHES | SETTINGS | ||
| |||
5 | VDC or mA | VDC | |
4 | 0 to 10 VDC (0 to 20 mA or | 0 to 10 | |
2 to 10 VDC (4 to 20 mA) | |||
|
| ||
3 | Direct Acting (DA) or | DA | |
Reverse Acting (RA) | |||
|
| ||
2 | FIXED or AUTO | FIXED | |
1 | — or 6 to 9 VDC | — |
NOTE: The 6 to 9 VDC setting of Switch 1 overrides switch 4.
WIRING (See Fig.
For the Belimo Actuator, connect the white wire on the ac- tuator to
NOTE: To retrofit PremierLink Controller to older 4 to 20 mA actuator, connect the red wire on the actuator wire harness to the purple wire on the PremierLink
IMPORTANT: Make sure the common side is grounded for both the PremierLink power and the actuator power. This is especially important if separate transformers are used.
MOVE TO LEFT
FOR
WITH PREMIERLINK
CONTROLLER
VDC | 5 | mA |
4 | ||
DA | 3 | RA |
FIXED | 2 | AUTO |
—1
Fig. 28 — Position of Actuator Mode Switches