Carrier 33CSPREMLK T58 Communicating Sensor Typical Wiring 33ZCT58SPT, Sampling of air

Page 11

FIELD WIRING

(American Wire Gage) twisted-pair cables (unshielded) to con- nect the separate isolated 24 vac power source to the sensor and

T58 SENSOR

VAC

24 VAC

COM

CCN-BLACK (-)

GND

WHITE (GND)

CCN+

RED (+)

 

BLACK (-)

J4-3 (24 VAC)

J6-6 SDT (COM)

CCN

COM

to connect the sensor to the control board terminals. To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. Connect the 4-20 mA terminal to terminal IAQ (RED) and connect the SIG COM terminal to terminal GND (BRN).

OUTDOOR AIR QUALITY CO2 SENSOR INSTALLA- TION (OAQ) — The Outdoor Air CO2 sensor is designed to monitor carbon dioxide (CO2) levels in the air and interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged with an outdoor cover. See Fig. 12 and 13.

The outdoor air CO2 sensor must be placed in an area that is representative of the entire conditioned space. A mounting height of 6 feet is recommended. For installation where it is not necessary to reach the control, it may be mounted higher on the wall or on the ceiling, provided the location represents a good

WHITE (GND)

J2

(COM)

 

RED (+)

 

Fig. 5 — T58 Communicating Sensor

Typical Wiring (33ZCT58SPT)

Perform the following steps if state or local code requires the use of conduit, or if your installation requires a cable length of more than 8 ft:

1.Secure the probe to the duct with two field-supplied self- drilling screws.

2.If you are extending cable length beyond 8 ft, use plenum rated, 20 AWG, twisted pair wire.

3.Connect the sensor leads to the PremierLink™ control- ler’s wiring harness terminal board at the terminals la- beled SAT (ORN) and GND (BRN).

4.Neatly bundle and secure excess wire.

INDOOR AIR QUALITY CO2 SENSOR INSTALLATION (IAQ) — The indoor air quality sensor accessory monitors carbon dioxide (CO2) levels. This information is used to moni- tor IAQ levels. Three types of sensors are provided. The wall sensor can be used to monitor the conditioned air space. Sensors use infrared technology to measure the levels of CO2 present in the air. The wall sensor is available with or without an LCD readout to display the CO2 level in ppm.

The CO2 sensors are all factory set for a range of 0 to 2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO2 sensor for electrical require- ments and terminal locations.

To accurately monitor the quality of the air in the condi- tioned air space, locate the sensor near a return air grille (if present) so it senses the concentration of CO2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact.

Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.

Wiring the Indoor Air Quality Sensor — To wire the sensors after they are mounted in the conditioned air space or outdoor location, see Fig. 7 and 8 and the instructions shipped with the sensors. For each sensor, use two 2-conductor 18 AWG

sampling of air.

Wiring the Outdoor Air CO2 Sensor — Power requirements are 18 to 36 vac RMS 50/60 Hz; 18 to 42 vdc polarity protected/ dependent; and 70 mA average, 100 mA peak at 24 vdc. All system wiring must be in compliance with all applicable local and national codes. A dedicated power supply is required for this sensor. A two-wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2. To connect the sen- sor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. Connect the 4 to 20 mA terminal OAQ (BLU) terminal J5-2. Connect the SIG COM ter- minal to terminal GND (BRN) terminal J5-3. See Fig. 12.

OUTDOOR AIR TEMPERATURE SENSOR (Fig. 14-17) — The OAT sensor must be located properly. The sensor must be installed immediately upstream from outdoor air damper where it will accurately sense the temperature of the outdoor air entering the mixing box. See Fig. 14 and 15. For applica- tions without economizer, the sensor may be located in the out- door air duct near the outdoor air intake (Fig. 15) or on the exterior of the building. The thermistor has a range of –40 to 245 F and a resistance of 10,000 ohms at 77 F.

Do not mount the sensor in direct sunlight. Inaccurate read- ings may result. Do not mount the sensor near the exhaust from air-handling units or compressors, near leakage drafts of indoor air, or near shrubbery or trees, or under direct water runoff.

If the sensor is to be mounted in the outdoor air duct, a field- supplied 2 x 4-in. by 11/2-in. deep electrical box is required. Remove the cover and enter the knockout from the rear of the box. Install the sensor through the opening so that the sensor leads are inside the electrical box. Secure the sensor to the elec- trical box using a field-supplied 1/2-in. conduit nut. Drill a 13/16-in. hole in the outdoor air duct about a foot upstream of the outdoor air damper. Apply a 1/4-in. bead of silicone type sealer around the opening and install the sensor through the hole. Secure the electrical box to the duct using 2 field- supplied, No. 10 sheet metal screws. See Fig. 17.

If the sensor is installed outdoors, a field-supplied 1/2-in. LB type conduit body, gasket, cover, and 1/2-in. EMT compression connector are required. Install the OAT sensor into the opening at the end of the LB conduit body. Install the 1/2-in. EMT connector into the rear opening. Tighten each securely to prevent water leakage into the assembly. Mount the assembly onto the 1/2-in. EMT conduit and secure by tightening the compression connector nut. After the sensor wiring is complet- ed, secure the gasket and cover in place using the screws provided with the cover. See Fig. 16.

11

Image 11
Contents Installation, Start-Up Configuration Instructions Installation PremierLink Controller Inputs and Outputs Typical PremierLink Control Wiring 38AKS013-024 Units Typical PremierLink Control Wiring 38ARD012 Units Typical PremierLink Control Wiring 38AH024-034 Units Typical PremierLink Control Wiring 38AQ007 Units PremierLink Connections Color Code Recommendations Space Temperature Sensor Typical Wiring 33ZCT55SPT Sampling of air T58 Communicating Sensor Typical Wiring 33ZCT58SPTSpace Temperature Averaging Page Page Page Page Outdoor Air Quality Sensor Cover Recommended Cables 33CSENTHSW Used with Differential Enthalpy Control only Differential Enthalpy Control Wiring See Fig Using the transformer supplied with the 40RM econoAdapter onto terminals P1 and P of actuator On the adapter connects to P terminal on the actuatorPage Mode Selection Information Actuator Drive Direction Settings24 VAC/VDC START-UP SAT 54.2 F PremierLink Navigator CarrierControl Set Point Display Units Supply Air Temperature Display UnitsDefault Value Display Range Network Access Read Only Description Value Units Status Force Name Points DisplaySet Point Display Units Indoor Air Quality ppm Display UnitsMillion implied Controller Identification Alarm Service ConfigurationThermostat Control Input Display Occupancy Configuration Holiday ConfigurationSet Point Configuration Range Default ValueDefault Value Enable Service Configuration SelectionNumber of Stages Range Default Value Time Guard Default Value Enable Stage Time Guard RangePage Space Temperature Trim Units Delta Degrees F Range 50.0 to Default Value 55.0Max Offset Adjustment Units Delta Degrees F Auxiliary Output PremierLink Control ConfigurationFor Electric Heat Range Default Value Heat Start Bias Units MON, TUE, WED Occupancy Maintenance IAQ Yes MaintenancePage Copyright 2002 Carrier Corporation