*Used with Differential Enthalpy Control only.
Fig. 20 — Typical Wiring Schematic — Carrier Rooftop Unit with PremierLink™ Controls
Connect the
Enthalpy Switch/Reciever Jumper Settings — There are two jumpers. One jumper determines the mode of the enthalpy switch/receiver. The other jumper is not used. To access the jumpers, remove the 4 screws holding the cover on the enthalpy switch/receiver and then remove the cover. The fac- tory settings for the jumpers are M1 and OFF.
The mode jumper should be set to M2 for differential en- thalpy control. The factory test jumper should remain on OFF or the enthalpy switch/receiver will not calculate enthalpy.
Enthalpy Sensor Jumper Settings — There are two jumpers. One jumper determines the mode of the enthalpy sensor. The other jumper is not used. To access the jumpers, remove the 4 screws holding the cover on the enthalpy sensor and then remove the cover. The factory settings for the jumpers are M3 and OFF.
The mode jumper should be set to M3 for 4 to 20 mA output. The factory test jumper should remain on OFF or the enthalpy sensor will not calculate enthalpy.
OUTDOOR AND RETURN AIR ENTHALPY SEN- SORS — The differential enthalpy control is supplied as a
NOTE: The differential enthalpy control must be set to the “D” setting for differential enthalpy control to work properly.
The differential enthalpy control senses the outdoor and return air sensors and provides a dry contact switch input to the PremierLink Controller. Locate the controller in place of an existing economizer controller or near the actuator. The mount- ing plate may not be needed if existing bracket is used.
A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.
The
20