Carrier 33CSPREMLK specifications PremierLink Connections

Page 8

PremierLink Connections

CAPORREMOVE THIS END OF

 

 

 

 

PWR

RED

 

 

 

 

 

JUMPER

 

 

 

HS3/EXH/RVS

ORN

 

 

 

 

 

RED

 

HS2

 

 

 

 

 

 

 

PNK

 

CUT FOR DUAL

TRANSFORMER

 

 

 

 

 

EQUIPTMENT

RED

 

 

 

 

 

HS1

WHT

 

 

 

 

 

RELAYS

 

CMP2

BLU

 

 

 

 

 

 

 

 

 

 

 

RED

 

CMP1

 

 

 

 

 

 

 

YEL

 

 

 

 

 

 

 

CUT TO

ISOLATE

CONTROLLER

POWER

RED

 

 

 

J8

FAN

GRN

 

 

 

 

 

PWR

 

 

BRN

J1

 

 

 

 

 

 

LEGEND

 

 

IAQ — Indoor-Air Quality

IFC — Indoor-Fan Contactor

 

40RMQ Connections

 

 

 

 

 

R

 

 

 

 

Y1

40RM, 40RMQ, 40RMS

Y2

 

HEAT ACCESSORY

W1

 

 

W1

 

W2

 

 

W2

 

G

WHT C1 IFC C2

 

C

 

 

 

 

 

 

CWHT

X

38AQS012-016

Terminal

Board (TB2)

R

B

W1

Y1

Y2

G

C

NOTES:

1.Configure AC to “1” for heat pump or “0” for air conditioner.

2.When using controller for DCV, if IAQ priority is set to HIGH, the controller will use a stage of heat for temperature tempering. If priority is set to LOW, no tempering will occur.

3.For air conditioners, use HS1 for IAQ tempering.

4.For heat pumps, use HS2 for IAQ tempering.

Fig. 2I — Typical PremierLink™ Control Wiring — 38AQS012-016 Units

Table 1 — PremierLink Controller Inputs and Outputs

INPUTS

POWER

TERMINAL(S)

SPACE TEMPERATURE (SPT)

AI (10K Thermistor)

J6-7, J6-6

SET POINT ADJUSTMENT (STO)

AI (10K Thermistor)

J6-5, J6-6

SUPPLY AIR TEMPERATURE (SAT)

AI (10K Thermistor)

J6-3, J6-4

OUTDOOR AIR TEMPERATURE (OAT)

AI (10K Thermistor)

J6-1, J6-2

IAQ SENSOR (IAQI)

(4-20 mA)

J5-5, J5-6

OUTDOOR AQ SENSOR (OAQ)

(4-20 mA)

J5-2, J5-3

REMOTE TIME CLOCK (RMTOCC)

DI (24 VAC)

J4-11, J4-12

COMPRESSOR LOCKOUT (CMPSAFE)

DI (24 VAC)

J4-9, J4-10

FIRE SHUTDOWN (FSD)

DI (24 VAC)

J4-7, J4-8

SUPPLY FAN STATUS (SFS)

DI (24 VAC)

J4-5, J4-6

NOT USED

 

 

ENTHALPY STATUS (ENTH)

DI (24 VAC)

J4-1, J4-2

 

OUTPUTS

POWER

TERMINAL(S)

ECONOMIZER (ECONPOS)

4-20 mA

J9-1, J9-2

FAN (SF)

DO Relay (24 VAC, 1A)

J8-18

COOL STAGE 1 (CMP1)

DO Relay (24 VAC, 1A)

J8-15

COOL STAGE 2 (CMP2)

DO Relay (24 VAC, 1A)

J8-12

HEAT STAGE 1 (HS1)

DO Relay (24 VAC, 1A)

J8-9

HEAT STAGE 2 (HS2)

DO Relay (24 VAC, 1A)

J8-6

HEAT 3/EXHAUST/REVERSING VALVE (HS3/EXH/RVS)

DO Relay (24 VAC, 1A)

J8-3

 

LEGEND

 

 

AI

Analog Input

 

 

DI

Digital Input

 

 

DO — Digital Output

 

 

8

Image 8
Contents Installation, Start-Up Configuration Instructions Installation PremierLink Controller Inputs and Outputs Typical PremierLink Control Wiring 38AKS013-024 Units Typical PremierLink Control Wiring 38ARD012 Units Typical PremierLink Control Wiring 38AH024-034 Units Typical PremierLink Control Wiring 38AQ007 Units PremierLink Connections Color Code Recommendations Space Temperature Sensor Typical Wiring 33ZCT55SPT T58 Communicating Sensor Typical Wiring 33ZCT58SPT Sampling of airSpace Temperature Averaging Page Page Page Page Outdoor Air Quality Sensor Cover Recommended Cables 33CSENTHSW Used with Differential Enthalpy Control only Differential Enthalpy Control Wiring Using the transformer supplied with the 40RM econo Adapter onto terminals P1 and P of actuatorOn the adapter connects to P terminal on the actuator See FigPage Actuator Drive Direction Settings Mode Selection Information24 VAC/VDC START-UP PremierLink Navigator Carrier SAT 54.2 FControl Set Point Display Units Supply Air Temperature Display UnitsDefault Value Display Range Network Access Read Only Points Display Description Value Units Status Force NameSet Point Display Units Indoor Air Quality ppm Display UnitsMillion implied Controller Identification Alarm Service ConfigurationThermostat Control Input Display Holiday Configuration Occupancy ConfigurationRange Default Value Set Point ConfigurationService Configuration Selection Number of Stages Range Default Value Time GuardDefault Value Enable Stage Time Guard Range Default Value EnablePage Space Temperature Trim Units Delta Degrees F Range 50.0 to Default Value 55.0Max Offset Adjustment Units Delta Degrees F Auxiliary Output PremierLink Control ConfigurationFor Electric Heat Range Default Value Heat Start Bias Units MON, TUE, WED Occupancy Maintenance IAQ Maintenance YesPage Copyright 2002 Carrier Corporation