Carrier 33CSPREMLK specifications Mon, Tue, Wed

Page 39

Low Reference specifies Low Point of the Outdoor IAQ Sensor Range in ppm.

Low Reference: Units:

PPM (parts per million)

Range:

0 to 5000

Default Value:

0

High Reference specifies High Point of the Outdoor IAQ Sensor Range in ppm.

High Reference: Units:

PPM (parts per million)

Range:

0 to 5000

Default Value:

2000

OUTDOOR AIR QUALITY LOCKOUT POINT — When set to non-zero value, the IAQ algorithm will compare Outdoor IAQ reading against this decision and disable IAQ control whenever the value of OAQ exceeds this configured value.

Outdoor Air

 

 

Quality Lockout

 

 

Point:

Range:

0 to 5000

 

Default Value:

0

SERVICE PASSWORD — The Service Password function defines the password needed to access the controller via the Navigator interface.

Service Password: Range:

0000 to 9999

Default Value:

1111

PASSWORD ENABLE — The Password Enable function is used to require a password to be entered when attempting to access the controller via the Navigator™ display module interface.

Password

Enable: Range: Enable/Disable Default Value: Disable

METRIC DISPLAY — The Metric Display function is used to toggle the display for the Navigator between US and Metric units.

Metric Display: Range:

On/Off

Default Value:

Off

Occupancy Maintenance Screen — The Occupan- cy Maintenance screen is used to check the occupied schedule. Information concerning the current occupied period is dis- played. See Table 16.

MODE — The Mode point displays the current occupied mode for the controller. If the controller is following its own local schedule this is the result of the local schedule status. If the controller is configured to follow a global schedule, this point displays the mode last received from a global schedule broadcast.

Mode:

Display Range:

0 to 1

 

Default Value:

0

 

Network Access:

None

CURRENT OCCUPIED PERIOD — If the controller is con- figured to determine occupancy locally, the Current Occupied Period point is used to display the current period determining occupancy.

Current Occupied

Period: Display Range: 1 to 8 Default Value: 0 Network Access: None

OVERRIDE IN PROGRESS — The Override in Progress point is used to display if an occupancy override is in progress. The point will display “Yes” if an override is in progress, or “No” if there is no override.

Override In

Progress: Display Range: Yes/No Default Value: No Network Access: None

OVERRIDE DURATION — The Override Duration point displays the number of minutes remaining for an occupancy override which is in effect. If the override duration value down- loaded is in hours, the value will be converted to minutes. If the occupancy schedule is occupied when override is initiated, the current occupancy period will be extended by the number of hours/minutes requested.

If the current occupancy period is unoccupied when the oc- cupancy override is initiated, the mode will change to occupied for the duration of the number of hours/minutes downloaded. If the occupancy override is due to end after the start of the next occupancy period, the mode will transition from occupancy override to occupied without becoming unoccupied, and the occupancy override timer will be reset.

Override

Duration: Display Units: Minutes Display Range: 0 to 240 Default Value: 0 Network Access: None

OCCUPIED START TIME — The Occupied Start Time point shows the time that the current occupied mode began. If the current mode is unoccupied or the controller is following a global schedule, the value displayed by this point will remain at default.

Occupied

 

 

Start Time:

Display Range:

00:00 to 24:00

 

Default Value:

00:00

 

Network Access:

None

UNOCCUPIED START TIME — The Unoccupied Start Time point shows the time that the current occupied mode will end. This will also be the beginning of the next unoccupied mode. If the current mode is unoccupied or the controller is following a global schedule, the value displayed by this point will remain at default.

Unoccupied

 

 

Start Time:

Display Range:

00:00 to 24:00

 

Default Value:

00:00

 

Network Access:

None

NEXT OCCUPIED DAY — The Next Occupied Day point displays the day of week when the next occupied period will begin. This point is used with the Next Occupied Time so the user will know when the next occupied period will occur. If the controller is following a global schedule this point will remain at default.

Next Occupied

 

 

Day:

Display Range:

MON, TUE, WED,

 

 

THU, FRI, SAT, SUN

 

Default Value:

No display (Blank)

 

Network Access:

None

NEXT OCCUPIED TIME — The Next Occupied Time point displays the time day when the next occupied period will begin. This point is used with the Next Occupied Day so the user will know when the next occupied period will occur. If the PremierLink™ controller is following a global schedule this point will remain at default.

Next Occupied

Time: Display Range: 00:00 to 24:00 Default Value: 00:00 Network Access: None

39

Image 39
Contents Installation, Start-Up Configuration Instructions Installation PremierLink Controller Inputs and Outputs Typical PremierLink Control Wiring 38AKS013-024 Units Typical PremierLink Control Wiring 38ARD012 Units Typical PremierLink Control Wiring 38AH024-034 Units Typical PremierLink Control Wiring 38AQ007 Units PremierLink Connections Color Code Recommendations Space Temperature Sensor Typical Wiring 33ZCT55SPT Sampling of air T58 Communicating Sensor Typical Wiring 33ZCT58SPTSpace Temperature Averaging Page Page Page Page Outdoor Air Quality Sensor Cover Recommended Cables 33CSENTHSW Used with Differential Enthalpy Control only Differential Enthalpy Control Wiring See Fig Using the transformer supplied with the 40RM econoAdapter onto terminals P1 and P of actuator On the adapter connects to P terminal on the actuatorPage Mode Selection Information Actuator Drive Direction Settings24 VAC/VDC START-UP SAT 54.2 F PremierLink Navigator CarrierSupply Air Temperature Display Units Default Value Display Range Network Access Read OnlyControl Set Point Display Units Description Value Units Status Force Name Points DisplayIndoor Air Quality ppm Display Units Million impliedSet Point Display Units Alarm Service Configuration Thermostat Control Input DisplayController Identification Occupancy Configuration Holiday ConfigurationSet Point Configuration Range Default ValueDefault Value Enable Service Configuration SelectionNumber of Stages Range Default Value Time Guard Default Value Enable Stage Time Guard RangePage Range 50.0 to Default Value 55.0 Max Offset Adjustment Units Delta Degrees FSpace Temperature Trim Units Delta Degrees F PremierLink Control Configuration For Electric HeatAuxiliary Output Range Default Value Heat Start Bias Units MON, TUE, WED Occupancy Maintenance IAQ Yes MaintenancePage Copyright 2002 Carrier Corporation