Table 2 — Color Code Recommendations

SIGNAL TYPE

CCN BUS WIRE

CCN PLUG PIN

COLOR

NUMBER

 

+

Red

1

Ground

White

2

Black

3

Install Sensors (See Fig. 3-10)The PremierLink™ controller can be used with either the T58 Communicating sen- sor or any combination of CO2 and space temperature sensors. Refer to the instructions supplied with each sensor for electrical requirements.

NOTE: All sensors are field-installed accessories.

SPACE TEMPERATURE (SPT) SENSOR INSTALLA- TION — There are three types of SPT sensors available from Carrier: The 33ZCT55SPT space temperature sensor with timed override button, the 33ZCT56SPT space temperature sensor with timed override button and set point adjustment, and the 33ZCT58SPT T58 communicating room sensor with timed override button, set point adjustment, and manual fan control.

The space temperature sensors are used to measure the building interior temperature. The T58 communicating room sensors measure and maintain room temperature by communi- cating with the controller. Sensors should be located on an interior building wall. The sensor wall plate accommodates the NEMA (National Electrical Manufacturers Association) standard 2 x 4 junction box. The sensor can be mounted direct- ly on the wall surface if acceptable by local codes.

Do not mount the sensor in drafty locations such as near air conditioning or heating ducts, over heat sources such as base- board heaters, radiators, or directly above wall-mounted light- ing dimmers. Do not mount the sensor near a window which may be opened, near a wall corner, or a door. Sensors mounted in these areas will have inaccurate and erratic sensor readings.

The sensor should be mounted approximately 5 ft from the floor, in an area representing the average temperature in the space. Allow at least 4 ft between the sensor and any corner and mount the sensor at least 2 ft from an open doorway. The SPT sensor wires are to be connected to terminals in the unit main control board.

Install the sensor as follows:

1.Locate the two Allen type screws at the bottom of the sensor.

2.Turn the two screws clockwise to release the cover from the sensor wall mounting plate.

3.Lift the cover from the bottom and then release it from the top fasteners.

4.Feed the wires from the electrical box through the open- ing in the center of the sensor mounting plate.

5.Using two no. 6-32 x 1 mounting screws (provided with the sensor), secure the sensor to the electrical box.

NOTE: Sensor may also be mounted directly on the wall using 2 plastic anchors and 2 sheet metal screws (field-supplied).

6.Use 20 gage wire to connect the sensor to the controller. The wire is suitable for distances of up to 500 ft. Use a three-conductor shielded cable for the sensor and set point adjustment connections. The standard CCN communication cable may be used. If the set point adjust- ment (slidebar) is not required, then an unshielded, 18 or 20 gage, two-conductor, twisted pair cable may be used.

The CCN network service jack requires a separate, shielded CCN communication cable. Always use sepa- rate cables for CCN communication and sensor wir- ing. (Refer to Fig. 5 for wire terminations.)

7.Replace the cover by inserting the cover at the top of the mounting plate first, then swing the cover down over the lower portion. Rotate the two Allen head screws counter- clockwise until the cover is secured to the mounting plate and locked in position.

NOTE: See Table 3 for thermistor resistance vs temperature values.

Wiring the Space Temperature Sensor — To wire the sensor, perform the following (see Fig. 3-5):

1.Identify which cable is for the sensor wiring.

2.Strip back the jacket from the cables for at least 3 inches.

Strip 1/4-in. of insulation from each conductor. Cut the shield and drain wire from the sensor end of the cable.

3.Connect the sensor cable as follows:

a.Connect one wire from the cable to (BLU) wire on J6-7 analog connector on the controller. Connect the other end of the wire to the left terminal on the SEN terminal block of the sensor.

b.Connect another wire from the cable to (BRN) J6-6 analog connector on the controller. Connect the other end of the wire to the remaining open ter- minal on the SEN terminal block.

c.On 33ZCT56SPT thermostats, connect the remain- ing wire to the (BLK) STO on J6-5 connector on the controller. Connect the other end of the wire to the SET terminal on the sensor.

d.In the control box, install a no. 10 ring type crimp lug on the shield drain wire. Install this lug under the mounting screw of the PremierLink controller.

e.On 33ZCT56SPT thermostats install a jumper between the two center terminals (right SEN and left SET). See Fig. 4.

f.Refer to Fig. 5 for 33ZCT58SPT thermostat wir- ing. Once the T58 sensor is powered up, all of the graphic icons on the LCD (liquid crystal display) display will be energized for a few seconds. The graphical icons will then turn off and the T58 sen- sor will energize the three-digit numeric display. The value “58” will be displayed for two seconds. After 2 seconds, the LCD will display the default space temperature value.

NOTE: See Fig. 6 for space temperature sensor averaging.

9

Image 9
Contents Installation, Start-Up Configuration Instructions Installation PremierLink Controller Inputs and Outputs Typical PremierLink Control Wiring 38AKS013-024 Units Typical PremierLink Control Wiring 38ARD012 Units Typical PremierLink Control Wiring 38AH024-034 Units Typical PremierLink Control Wiring 38AQ007 Units PremierLink Connections Color Code Recommendations Space Temperature Sensor Typical Wiring 33ZCT55SPT Sampling of air T58 Communicating Sensor Typical Wiring 33ZCT58SPTSpace Temperature Averaging Page Page Page Page Outdoor Air Quality Sensor Cover Recommended Cables 33CSENTHSW Used with Differential Enthalpy Control only Differential Enthalpy Control Wiring Adapter onto terminals P1 and P of actuator Using the transformer supplied with the 40RM econoOn the adapter connects to P terminal on the actuator See FigPage Mode Selection Information Actuator Drive Direction Settings24 VAC/VDC START-UP SAT 54.2 F PremierLink Navigator CarrierSupply Air Temperature Display Units Default Value Display Range Network Access Read OnlyControl Set Point Display Units Description Value Units Status Force Name Points DisplayIndoor Air Quality ppm Display Units Million impliedSet Point Display Units Alarm Service Configuration Thermostat Control Input DisplayController Identification Occupancy Configuration Holiday ConfigurationSet Point Configuration Range Default ValueNumber of Stages Range Default Value Time Guard Service Configuration SelectionDefault Value Enable Stage Time Guard Range Default Value EnablePage Range 50.0 to Default Value 55.0 Max Offset Adjustment Units Delta Degrees FSpace Temperature Trim Units Delta Degrees F PremierLink Control Configuration For Electric HeatAuxiliary Output Range Default Value Heat Start Bias Units MON, TUE, WED Occupancy Maintenance IAQ Yes MaintenancePage Copyright 2002 Carrier Corporation