|
|
| BLACK | 4 |
|
|
|
| |
|
|
|
| 3 |
|
|
|
| 5 |
|
|
| BLUE | 2 |
|
|
|
| |
| 500 OHM |
|
| 8 |
| RESISTOR |
|
| |
| VIOLET |
|
| 6 |
NOTE 1 |
|
|
| |
PINK |
|
|
| |
|
|
| 7 | |
RUN |
|
|
| |
|
|
|
| |
NOTE 2 |
|
| RED | 1 |
|
|
| ||
WIRES FOR |
|
|
| |
|
|
|
| |
50HJ540573 | OAT SENSOR | YELLOW |
| 10 |
|
|
| ||
ACTUATOR |
|
| 11 | |
ASSEMBLY |
|
|
| |
|
|
|
| 9 |
DIRECT DRIVE |
| WHITE | 12 | |
ACTUATOR |
|
|
| |
|
|
|
|
TRANSFORMER GROUND
24 VAC
ECONOMISER2 PLUG
NOTES:
1.Switch on actuator must be in run position for economizer to operate.
2.50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with
Fig. 30B — PremierLink™ Control Wiring to Belimo-Style Actuator EconoMi$er2 Harness
START-UP
The unit must be electrically grounded in accordance with local codes and NEC ANSI/NFPA 70 (American National Standards Institute/National Fire Protection Association).
Use the Carrier network communication software to start up and configure the PremierLink™ controller.
Changes can be made using the ComfortWORKS® soft- ware, ComfortVIEW™ software, or Network Service Tool. The Network Service Tool is a portable interface device that allows the user to change system
NOTE: All
For specific operating instructions, refer to the literature provided with user interface software.
Perform System Check-Out
1.Check correctness and tightness of all power and communication connections.
2.At the unit, check fan and system controls for proper operation.
3.At the unit, check electrical system and connections of any optional electric heat.
NOTE: If optional electric heat is installed, Heat Type must be changed to “1” (electric heat) from default of “0” (gas heat).
4.Check to be sure the area around the unit is clear of construction dirt and debris.
5.Check that final filters are installed in the unit. Dust and debris can adversely affect system operation.
6.Verify that the PremierLink controls are properly connected to the CCN bus.
26
Initial Operation and Test — Perform the following
procedure:
1.Apply 24 vac power to the control.
2.Connect the Service Tool to the phone jack service port of the controller.
3.Using the Service Tool, upload the controller from address 0, 31 at 9600 baud rate. The address may be set at this time. Make sure that Service Tool is connected to only one unit when changing the address.
MEMORY RESET — DIP switch 4 causes a
To cause a reset of the
Install Navigator™ Display Module — The Navi- gator is a portable display module that conforms to NEMA 4 specifications for outdoor use in temperatures ranging from
The Navigator keypad contains eleven menu LEDs and one Alarm Status LED, all of which are red. The Navigator is capa- ble of displaying four