Mitsubishi Electronics 700 Series, FR-A700 How to Read the Error Code, Error Error Name Code

Models: FR-A700 700 Series

1 183
Download 183 pages 30.92 Kb
Page 177
Image 177

How to Read the Error Code

When the built-in PLC function is in the RUN status or if an alarm occurs during RUN, the self-diagnostic function displays the error and stores the error code and error step into the special registers. This chapter describes the error definitions and corrective actions.

4.1 How to Read the Error Code

When an error has occurred, the error code can be read with the peripheral device. For the operation method, refer to the operating manual of the peripheral device.

The following table indicates the error names, error codes, definitions, causes and corrective actions.

The error code and error step are stored into the following special registers. Error code................. D9008

Error step.................. D9010, D9011

Table 4.1 Error Code List

 

Error

 

 

 

Error Name

Code

Status

Definition and Cause

Corrective Action

 

(D9008)

 

 

 

“INSTRCT

 

 

The instruction code that

 

CODE ERR.”

 

 

cannot be decoded is

Read the error step using

[Checked at

10

Stop

included in the program.

GX Developer, and correct

instruction

 

 

The memory contents

that step in the program.

execution]

 

 

changed for some reason.

 

“PARAMETER

 

 

(1) Write to the CPU was

 

ERROR”

 

 

performed after the

 

[Checked at

 

 

capacity larger than the

Check the memory capacity

power-on or

 

 

memory capacity of the

 

 

of the CPU with the

STOP to RUN]

 

 

CPU was set using GX

11

Stop

memory capacity set using

 

Developer.

 

 

 

GX Developer, and re-set

 

 

 

(2) The parameter data of the

 

 

 

using GX Developer.

 

 

 

CPU memory changed

 

 

 

 

due to noise or memory

 

 

 

 

loading fault.

 

“WDT ERROR”

 

 

The scan time exceeds the

Calculate/check the user

[Checked at

22

Stop

watchdog error monitor time.

END processing

The user program scan

program scan time and

 

 

reduce the scan time.

execution]

 

 

time has increased.

 

 

 

“END NOT

 

 

(1) The END instruction has

Reset and RUN again. If

EXECUTE”

 

 

been read as another

the same error appears

[Checked at

 

 

instruction code due to

again, the cause is a CPU

END instruction

24

Stop

noise, etc.

hardware fault. Consult the

execution]l

(2) The END instruction has

Mitsubishi representative.

 

 

 

 

 

changed into another

 

 

 

 

instruction code for some

 

 

 

 

reason.

 

172

Page 177
Image 177
Mitsubishi Electronics 700 Series, FR-A700 specifications How to Read the Error Code, Error Error Name Code