User Area Read/Write Method

1.9 User Area Read/Write Method

Inverter parameters Pr.506 to Pr.515 can be used as user parameters.

Since this parameter area and the devices used with the PLC function, D110 to D119, are accessible to each other, the values set in Pr.506 to Pr.515 can be used in a sequence program. The result of operation performed in the sequence program can also be monitored using Pr.506 to Pr.515.

 

 

 

 

 

 

 

 

Device

Inverter

 

 

Initial

Setting

Minimum Setting

 

Parameter

Name

 

Data Access

No.

No.

 

 

Value

Range

Unit

 

 

 

 

 

 

 

 

D110 to

506 to 515

User

 

0

0 to

1

Always

D119

parameters

 

65535

enabled

 

Inverter parameters

 

PLC function devices

 

 

Pr.506 to Pr.515

 

 

D110 to D119

 

POINT

Example of using the user parameter area

When the timing is to be changed for machine adjustment using D110 that stores the timer setting, setting Pr. 506 without modifying the program enters the set data into D110, enabling adjustment.

1.9.1User parameter read/write method

User parameter (Pr.506 to Pr.515) and device (D110 to D119) data can be read/written freely. Data transfer between Pr.506 to Pr.515 and D110 to D119 is executed automatically.

1)User parameter write processing

When values are written to Pr.506 to Pr.515 using the FR-PU04 or computer link communication, they are written to the parameter storing RAM area and EEPROM area, and further to D110 to D119 simultaneously.

2)User parameter read processing

When values are written to D110 to D119 from the PLC function side, they are written to the parameter storing RAM area (Pr.506 to Pr.515) and read using the FR- PU04/FR-PU07 or communication(RS-485 or communication option). (Since data are not written to the EEPROM, making power-on reset returns the data to the original values.)

3)Processing performed at inverter reset or power restoration

When the inverter is reset, the Pr.506 to Pr.515 values stored in the EEPROM are transferred to the RAM area and D110 to D119.

 

1)

 

1)

FR-PU04 or RS-485

 

Pr.506 to Pr.515

D110 to D119

communication

 

(RAM)

 

2)

 

2)

 

3)

 

3)

1)

 

Pr.506 to Pr.515

1)

 

 

 

 

(EEPROM)

 

 

 

 

38