Inverter Status Monitoring, Special Registers for Control

1.7.4Inverter operation status control

Device No.

Name

Data Access Enable Condition

D9148

Inverter operation status control

Always

 

 

Note that this function is enabled in

 

 

D9149

Inverter operation status control

the external/NET operation mode.

enable/disable

(Not enabled in the PU

 

 

 

operation mode.)

(1)Inverter operation status control (D9148)

Device for inverter operation status control. The operation of the inverter can be

controlled by turning on/off (1, 0) bits b0 to b11 of D9148. All bits are factory-set to "0".

Example: When 5 is set to D9148, bits b0 and b2 are 1 (ON), and STF and RH therefore turn on to give a high-speed forward rotation command.

B15

B12B11

B8B7

B4B3

B0

0 0 0 0 0 0 0 0 0 1 0 1

Invalid

CAUTION

0:OFF

1:ON

STF (Pr.178)

STR (Pr.179)

RH (Pr.182)

RM (Pr.181)

RL (Pr.180)

JOG (Pr.185)

RT (Pr.183)

AU (Pr.184)

CS (Pr.186)

MRS (Pr.187)

STOP (Pr.188)

RES (Pr.189)

As in the external input terminals, functions can be assigned to the bits of D9148 using Pr.178 to Pr.189. However, no function can be assigned to SQ (sequence RUN setting: 50).