CC-Link I/O Specifications

2.3 CC-Link I/O Specifications

2.3.1I/O signal when CC-Link Ver.1 one station is occupied (Pr. 544 = 100)

The device points usable in CC-Link communication are 32 input (RX) points (16 points are available for PLC function), 32 output (RY) points (16 points are available for PLC function), 4 remote register (RWr) points and 4 remote register (RWw) points.

(1) Remote I/O

PLC

Remote

 

function

output

Signal

device

device

No.

No.

 

X30

RYn0

Forward rotation command

X31

RYn1

Reverse rotation command

X32

RYn2

High-speed operation

command

 

 

(terminal RH function) *1

X33

RYn3

Middle-speed operation

command

 

 

(terminal RM function) *1

X34

RYn4

Low-speed operation

command

 

 

(terminal RL function) *1

X35

RYn5

Jog operation command

(terminal JOG function) *1

 

 

X36

RYn6

Second function selection

(terminal RT function) *1

 

 

X37

RYn7

Current input selection

(terminal AU function) *1

 

 

X38

RYn8

Selection of automatic restart after

instantaneous power failure

 

 

(terminal CS function) *1

X39

RYn9

Output stop

 

 

 

X3A

RYnA

Start self-holding selection

(terminal STOP function) *1

 

 

X3B

RYnB

Reset

(terminal RES function) *1

 

 

X3C

RYnC

 

X3D

RYnD

General-purpose remote input

 

 

available in PLC function

X3E

RYnE

X3F

RYnF

 

RY(n+1)0

Reserved

to

 

RY(n+1)7

 

 

 

Not used

RY(n+1)8

(initial data process

 

 

completion flag)

 

 

Not used

RY(n+1)9

(initial data process request

 

 

flag)

RY(n+1)A

Error reset request flag

PLC

Remote

 

function

input

Signal

device

device

No.

No.

 

X30

RXn0

Forward running

X31

RXn1

Reverse running

X32

RXn2

Running

(terminal RUN function) *2

 

 

 

 

 

X33

RXn3

Up to frequency

(terminal SU function) *2

 

 

 

 

 

X34

RXn4

Overload alarm

(terminal OL function) *2

 

 

 

 

 

X35

RXn5

Instantaneous power failure

(terminal IPF function) *2

 

 

X36

RXn6

Frequency detection

(terminal FU function) *2

 

 

X37

RXn7

Error

(terminal ABC1 function) *2

 

 

X38

RXn8

(terminal ABC2 function) *2

 

 

 

X39

RXn9

Pr. 313 assignment function

(DO0)

 

 

X3A

RXnA

Pr. 314 assignment function

(DO1)

 

 

X3B

RXnB

Pr. 315 assignment function

(DO2)

 

 

X3C

RXnC

 

X3D

RXnD

General-purpose remote input

 

 

available in PLC function

X3E

RXnE

X3F

RXnF

 

RX(n+1)0

Reserved

to

 

RX(n+1)7

 

Not used

RX(n+1)8 (initial data process request flag)

Not used

RX(n+1)9 (initial data process completion flag)

RX(n+1)A Error status flag

50

Page 55
Image 55
Mitsubishi Electronics 700 Series, FR-A700 specifications CC-Link I/O Specifications, Remote I/O