Inverter Status Monitoring, Special Registers for Control

(5)Parameter clear (D9147)

Writing H9696 or H9966 to D9147 clears all parameters. Writing H5A5A or H55AA to D9147 clears the parameters other than the communication parameters (Refer to the Inverter instruction manual (applied)).

Device No.

Setting

Description

Details

 

H9696

 

Terminal functions are not

 

All parameter clear

cleared.

 

 

 

H9966

Terminal functions are

 

 

D9147

 

cleared.

 

 

H5A5A

Parameters other than

Terminal functions are not

 

 

cleared.

 

 

communication parameters

 

 

Terminal functions are

 

H55AA

are cleared.

 

cleared.

 

 

 

At completion of clear, the write completion signal (X27) turns on, and at the same time, 0 is set to D9150. If any value outside the setting range is written or write is performed during inverter operation, HFFFF is set to D9150 as soon as the write completion signal (X27) turns on, resulting in abnormal completion. If abnormal completion occurs, the parameters are not cleared.

REMARKS

Check the terminal function parameters and communication-related parameters in the parameter list (Refer to the Inverter instruction manual (applied)).

POINT

Setting is enabled in the PU operation mode and NET operation mode. Refer to the inverter instruction manual (applied).

<All parameter clear program example>

The following program clears all parameters.

All parameter clear request

Normal write

Abnormal write

Turns on all parameter clear request pulse.

Check whether all parameter clear signal turned on to judge whether write was performed normally or not.

Stores H9696 (all parameter clear code) to D9146 and turns on alarm definition batch clear command.

(Until completion signal turns on)

‹Related device‹

Device D9150: Parameter access error code (refer to page 33)