Inverter Status Monitoring, Special Registers for Control

1.7.5Inverter parameter access error (D9150)

Device No.

Name

Data Access Enable

Condition

 

 

D9150

Inverter parameter access error

Always

 

 

 

If any value outside the setting range is written during parameter write, set frequency write, parameter clear, etc. from the sequence program of the inverter, or if write is performed when write is disabled, a write alarm occurs and the corresponding alarm code is stored into D9150.

<Parameter>

The parameter No. + H8000 is stored into D9150.

Example: If an error occurs during write of Pr.0 Torque boost, H8000 (H0 + H8000) is stored into D9150.

If an error occurs during write of Pr.10 DC injection brake operation frequency, H800A is stored into D9150.

<Operation mode, set frequency, alarm definition batch clear, all parameter clear>

HFFFF is stored into D9150. (Normal 0)

POINT

If write is completed normally after error occurrence, D9150 is not cleared (D9150 data is held at error occurrence). When using D9150 to stop operation, etc., the user must clear it.

1.7.6Inverter status (D9151)

Device No.

Name

Data Access Enable

Condition

 

 

D9151

Inverter status

Always

 

 

 

The running status and operating status of the inverter are stored. The corresponding bits are set according to the inverter status.

B15B8B7 B4B3 B0

0:OFF

1:ON

Inverter running(RUN) Forward running Reverse running

Up to frequency(SU) Overload alarm(OL) Instantaneous power failure /undervoltage(IPF)

Output frequency detection(FU) Alarm output(ALM) Minor fault output(LF)

1

PLC FUNCTION

33

Page 38