Sequence Instructions

3.25.7Output Instructions : Leading edge, trailing edge differential outputs ... PLS, PLF

 

 

 

Usable Devices

 

 

 

 

Error

 

Bit devices

 

Word (16-bit) devices

Constants

Level

Digit

Flag

X

Y

M

T

C

D

K

H

N

Designation

(M9010,

 

M9011)

 

 

 

 

 

 

 

 

 

 

D

{

{

 

 

 

 

 

 

 

 

PLS command

Set data

 

D

Device number whose data will be converted into pulses

PLF command

Functions

PLS

(1)Turns the specified device on when the PLS command turns from OFF to ON, and turns it off except when the PLS command turns from OFF to ON.

When there is one PLS instruction for the device specified at D during one scan, the specified device turns on for one scan.

Do not execute the PLS instruction for the same device more than once during one scan.

1

scan

 

 

1

scan

 

 

 

 

 

 

 

 

 

 

 

 

 

(2)If the status is switched to STOP and switched to RUN again after execution of the PLS instruction, the PLS instruction is not executed.

SEQUENCE PROGRAMMING

3

129

Page 134
Image 134