3)In user sequence, ON of read completion is confirmed and data are read from data registers D9242(D9243) and processed.

1)Read command is turned on in user sequence.

Y28(Y2A) Parameter read command

X28(X2A) Parameter read completion

Inverter parameter

D9242(D9243) Parameter read data

User sequence processing

4)After completion of read, read command is turned off.

2)Inverter CPU stores inverter parameter data into data registers D9242(D9243), and turns on read completion.

5)Inverter CPU confirms that read command is off and turns off read completion.