Description of devices

3.9.4Timers T

The timers of the PLC function are count up timers.

The count up timer starts timing the present value when its coil turns on, and the contact of that timer turns on when the present value reaches the setting (time-out).

3.9.5100ms, 10ms and 100ms retentive timers

(1)100ms and 10ms timers

The timer starts timing the present value when its coil turns on, and the present value is reset to 0 and the contact turns off when the coil turns off.

Ladder example

 

 

 

 

 

When input X5 turns on, T2 coil turns on

 

 

 

and timer times 5s. (T2 is 100ms timer.)

Timing chart

 

 

 

 

ON

ON

X5

OFF

OFF

OFF

 

 

ON

ON

T2 coil

OFF

OFF

OFF

Timer present

 

 

Setting

 

 

 

value

 

 

5s

 

 

 

ON

T2 contact

OFF

 

OFF

Fig 3.15 Timing Chart

REMARKS

100ms, 10ms and 100ms retentive timers can be changed using the built-in PLC function parameter. (The default is a 100ms timer.)

Since the FR-C500 has 8 timers (T0 to T7), it can use only any one type of 100ms, 10ms and 100ms retentive timers.