Sequence Instructions

OUT(T)

(1)When the operation result up to the OUT instruction is ON, the coil of the timer turns on and the timer times up to the setting, and when the timer times out (timing value setting), the contact operates as indicated below.

N/O contact

Energize

N/C contact

Not energize

 

 

(2)When the operation result up to the OUT instruction turns from ON to OFF, the timer operates as indicated below.

 

Timer

Present

Before Time-out

After Time-out

Timer Type

Value of

N/O

N/C

N/O

N/C

Coil

 

Timer

contact

contact

contact

contact

 

 

100ms timer

OFF

0

Not

Energize

Not

Energize

10ms timer

energize

energize

 

 

 

 

 

 

 

 

 

 

 

100ms

OFF

Maintained

Not

Energize

Energize

Not

retentive timer

energize

energize

 

 

 

 

(3)After a time-out, the contact state of the retentive timer remains unchanged until the RST instruction is executed.

(4)A negative number (-32768 to -1) cannot be specified for the setting.

(5)If the setting is 0, it is timed as infinity. Hence, the timer does not time out.

(6)Refer to page 81 for the timing method of the timer.

OUT(C)

(1)When the operation result up to the OUT instruction turns from OFF to ON, the present value (count value) is incremented by 1, and when the counter stops counting (present value = setting), the contact operates as indicated below.

N/O contact

Energize

N/C contact

Not energize

 

 

(2)The counter does not count if the operation result remains ON. (Count inputs need not be converted into pulses.)

(3)After the counter has stopped counting, the count value and contact state remain unchanged until the RST instruction is executed.

(4)A negative number (-32768 to -1) cannot be specified for the setting. If the setting is 0, processing is the same as when the setting is 1.

(5)Refer to page 83 for the counting method of the counter.

Execution Conditions

Executed every scan independently of the operation result up to the OUT instruction.

124

Page 129
Image 129
Mitsubishi Electronics 700 Series, FR-A700 specifications Outt, Outc, Contact