Prior to Sequence Program Creation

1.5.4Sequence program write

POINT

Sequence program write can be performed in any operation mode.

When rewriting the PLC function parameters and sequence program using GX Developer, check the following:

1)Check that the sequence program execution key is in the STOP position (SQ signal is off) (refer to page 7).

2)Check that the inverter is at a stop.

3)Check that the communication specification setting parameters (Pr.117 to Pr.124) are set correctly. If any of these parameters is set incorrectly, communication with GX Developer cannot be made.

REMARKS

Check and set the communication specification parameter (Pr. 117 to Pr. 124) using the parameter unit (FR-PU04/FR-PU07). (Refer to the FR-PU04/FR-PU07 instruction manual for the handling of the FR-PU04/FR-PU07.) GX Developer and the FR-PU04/FR-PU07 cannot be connected and used simultaneously.

4)Check the PLC series and sequence program capacity in the GX Developer parameters (refer to page 4).

5)Refer to the GX Developer manual and write the sequence program.

CAUTION

A sequence program cannot be written with its steps specified. If written, the sequence program does not run. (The program outside the specified range is initialized.)

Do not read the built-in PLC function parameters and sequence program without writing them to the inverter once using GX Developer. Since the inverter does not have normal data, always write the built-in PLC function parameters and sequence program once.

Since the built-in PLC function parameters and sequence program are written to the flash ROM, there are restrictions on the number of write times. (Approximately 100,000 times)

8