Mitsubishi Electronics 700 Series, FR-A700 specifications RAM, Eeprom

Models: FR-A700 700 Series

1 183
Download 183 pages 30.92 Kb
Page 57
Image 57

CC-Link I/O Specifications

2.3.2I/O signal when CC-Link Ver.2 double setting is selected (Pr. 544 = 112)

The device points usable in CC-Link communication are 32 input (RX) points (12 points are available for PLC function), 32 output (RY) points (12 points are available for PLC function), 4 remote register (RWr) points and 4 remote register (RWw) points.

(1) Remote I/O

PLC

Remote

 

function

output

Signal

device

device

No.

No.

 

X30

RYn0

Forward rotation command

X31

RYn1

Reverse rotation command

X32

RYn2

High-speed operation

command

 

 

(terminal RH function) *1

X33

RYn3

Middle-speed operation

command

 

 

(terminal RM function) *1

X34

RYn4

Low-speed operation

command

 

 

(terminal RL function) *1

X35

RYn5

Jog operation command

(terminal JOG function) *1

 

 

X36

RYn6

Second function selection

(terminal RT function) *1

 

 

X37

RYn7

Current input selection

(terminal AU function) *1

 

 

X38

RYn8

Selection of automatic restart after

instantaneous power failure

 

 

(terminal CS function) *1

X39

RYn9

Output stop

 

 

 

X3A

RYnA

Start self-holding selection

(terminal STOP function) *1

 

 

X3B

RYnB

Reset

(terminal RES function) *1

 

 

RYnC

Monitor command

RYnD

Frequency setting command

(RAM)

 

 

RYnE

Frequency setting command

(RAM, EEPROM)

 

 

RYnF

Instruction code execution

request

 

 

RY(n+1)0

Reserved

to

 

RY(n+1)7

 

 

 

Not used

RY(n+1)8

(initial data process

 

 

completion flag)

 

 

Not used

RY(n+1)9

(initial data process request

 

 

flag)

RY(n+1)A

Error reset request flag

RY(n+1)B

Reserved

to

 

RY(n+1)F

 

 

 

 

PLC

Remote

 

function

input

Signal

device

device

No.

No.

 

X30

RXn0

Forward running

X31

RXn1

Reverse running

X32

RXn2

Running

(terminal RUN function) *2

 

 

 

 

 

X33

RXn3

Up to frequency

(terminal SU function) *2

 

 

 

 

 

X34

RXn4

Overload alarm

(terminal OL function) *2

 

 

 

 

 

X35

RXn5

Instantaneous power failure

(terminal IPF function) *2

 

 

X36

RXn6

Frequency detection

(terminal FU function) *2

 

 

X37

RXn7

Error

(terminal ABC1 function) *2

 

 

X38

RXn8 (terminal ABC2 function) *2

 

 

 

X39

RXn9

Pr. 313 assignment function

(DO0)

 

 

X3A

RXnA

Pr. 314 assignment function

(DO1)

 

 

X3B

RXnB

Pr. 315 assignment function

(DO2)

 

 

RXnC Monitoring

RXnD

Frequency setting completion

(RAM)

 

 

RXnE

Frequency setting completion

(RAM, EEPROM)

 

 

RXnF

Instruction code execution

completion

 

 

RX(n+1)0

Reserved

to

 

RX(n+1)7

 

 

 

Not used

RX(n+1)8

(initial data process request

 

 

flag)

 

 

Not used

RX(n+1)9

(initial data process

 

 

completion flag)

RX(n+1)A

Error status flag

 

RX(n+1)B

Remote station Ready

RX(n+1)C

Reserved

 

to

 

RX(n+1)F

 

52

Page 57
Image 57