CC-Link I/O Specifications

2.3.4I/O signal when CC-Link Ver.2 octuple setting is selected (Pr. 544 = 118)

The device points usable in CC-Link communication are 32 input (RX) points (12 points are available for PLC function), 32 output (RY) points (12 points are available for PLC function), 16 remote register (RWr) points and 16 remote register (RWw) points.

(1) Remote I/O

Same as when Pr. 544 = 112 ( Refer to page 52)

(2) Remote resister

PLCfunction

Address

 

Description

 

PLC function

Address

Description

 

Upper 8

Lower 8

 

device No.

 

 

Bits

Bits

 

device No.

 

 

 

 

 

 

 

 

 

 

 

RWwn

 

Monitor

Monitor

 

RWrn

First monitor value

 

code 2

code 1

 

 

 

 

 

 

 

 

 

RWwn+1

 

Set frequency

 

RWrn+1

Second monitor

 

(0.01Hz increments)

 

value

 

 

 

 

 

 

 

 

 

Link

Instruction

 

 

 

Reply

Reply

RWwn+2

 

parameter

 

RWrn+2

 

expansion

code

 

code2

code1

 

 

 

 

 

 

 

 

 

setting

 

 

 

 

 

 

RWwn+3

 

Write

data

 

RWrn+3

Read

data

RWwn+4

 

Monitor code 3

 

RWrn+4

Third monitor value

RWwn+5

 

Monitor code 4

 

RWrn+5

Fourth monitor value

RWwn+6

 

Monitor code 5

 

RWrn+6

Fifth monitor value

RWwn+7

 

Monitor code 6

 

RWrn+7

Sixth monitor value

 

RWwn+8

 

Alarm

 

 

 

RWrn+8

Alarm

Alarm

 

definition

H00

 

definition

definition

 

 

 

No.

 

 

 

 

No.

data

RWwn+9

 

PID set point

 

RWrn+9

Alarm definition

 

(0.01% increments) *1

 

(output frequency)

 

 

 

 

 

 

RWwn+A

 

PID measured value

 

RWrn+A

Alarm definition

 

(0.01% increments) *1

 

(output current)

 

 

 

 

 

 

RWwn+B

 

PID deviation

 

RWrn+B

Alarm definition

 

(0.01% increments) *1

 

(output voltage)

 

 

 

 

 

 

RWwn+C

 

toruqe command / limit

 

RWrn+C

Alarm definition

 

(0.01% increments)

 

(energization time)

 

 

 

 

 

 

RWwn+D

 

 

 

 

RWrn+D

 

 

RWwn+E

 

H00 (Free)

 

RWrn+E

H00 (Free)

RWwn+F

 

 

 

 

RWrn+F

 

 

*1 When Pr. 128 = "50, 51, 60, 61", they are valid.

2

CC-Link COMMUNICATION

55

Page 60
Image 60