System Configuration

1.3 System Configuration

The following shows the system configuration for use of the PLC function.

<System configuration example>

GX Developer:

 

FR-A700

Programming tool

 

 

 

 

 

PU connector

 

RS-232C/

 

 

RS-485

 

 

converter

Motor

 

 

3-phase AC power supply

Communication specifications

Set the following setting in communication parameters of the inverter.

Inverter Parameter

GX Developer Setting

 

Inverter initial setting

Pr.118 PU communication speed

96 (9600bps)

192 (19200bps)

Pr.119 PU communication stop bit length

0 (data length: 8 bits, stop

1

(data length: 8 bits, stop

 

bit: 1 bit)

bit: 2 bit)

Pr.120 PU communication parity check

1 (with odd parity check)

2

(with even parity check)

Pr.122 PU communication check time

9999 (without

9999 (without

interval

communication check)

communication check)

REMARKS

•For futher details, refer to the Inverter instruction manual (applied).

POINT

Support GX Developer ver.8.0 or more

GX Developer Setting

PLC series

ACPU

PLC type

A0J2H

[Project data list]→[Parameter]→[PLC parameter]→[A parameter]

→«Memory capacity» tab→"Program capacity"→"Sequence"→"main"

1k step

REMARKS

•Refer to the Inverter instruction manual (applied) for wiring.

•Refer to the GX Developer manuals for the specifications related to GX Developer and the personal computer that uses GX Developer.

GX Developer Version xx Operating manual

GX Developer Version xx Operating manual (startup)

•The programming tool that can be used is GX Developer only. (The A6GPP, A7PHP, etc. cannot be used.)