Prior to Sequence Program Creation

1.5 Prior to Sequence Program Creation

1.5.1Precautions for sequence program creation

POINT

Online change of the sequence program and access to other stations are not allowed.

In addition, program read/write from other stations and all PLC memory clear cannot be performed.

Back up the ladder configured with the protective function of GX Developer.

If any of the instructions (refer to page 103) and devices (refer to page 3) that cannot be used with the built-in PLC function exists in a sequence program, an instruction code error occurs at the execution of that instruction.

Error code

D9008=10

Operation error step

D9010

 

D9011

REMARKS

Refer to page 22 for the error codes.

1.5.2Usable main GX Developer functions

zParameter or sequence program read/write

zLadder monitor

zDevice monitor

zDevice test

zAll device memory clear

zRemote RUN/STOP

CAUTION

Device test ([Online] - [Debug] - [Device test]) of GX Developer can be performed, but if devices corresponding to control terminal (e.g. STF, STR) signals are tested, the devices turn on in the sequence but the inverter does not perform the corresponding operation.

6

Page 11
Image 11
Mitsubishi Electronics 700 Series, FR-A700 Prior to Sequence Program Creation, Precautions for sequence program creation