Setting of Output (Y) Status at Switching from

STOP Status to RUN Status

3.18Setting of Output (Y) Status at Switching from STOP Status to RUN Status

When the RUN status is switched to the STOP status, the outputs (Y) in the RUN status are stored into the built-in PLC function.

Using the built-in PLC function parameter, you can set whether the outputs (Y) will be output again or will be output after execution of operation when the STOP status is switched to the RUN status.

"Output (Y) status at STOP is output"

The sequence program operation is performed after the output (Y) status at the time of entering the STOP status is output.

"Outputs (Y) are cleared (output one scan later)"

The outputs (Y) are all cleared, and after execution of the sequence program operation, the outputs are provided.

STOP status to RUN status

 

Is output (Y) status at

NO

 

STOP to be output?

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

Output (Y) status at the time of

 

Output (Y) status is cleared.

 

 

 

 

entering the STOP status is output.

 

 

 

 

 

 

 

 

 

 

 

 

Sequence program operation is executed.

Fig 3.24 Processing Performed when STOP Status Is Switched to RUN Status

96

Page 101
Image 101