Analog I/O function

1.10 Analog I/O function

1.10.1 Analog input

Analog input value of termianl 1, 2, 4 can be read from D9245 to D9247.

Device

Terminal Name

Setting

Data Access Enable

No.

 

Unit

Condition

D9245

Terminal 1 input

0.1%

Always

D9246

Terminal 2 input

0.1%

D9247

Terminal 4 input

0.1%

 

Actual read processing is performed at the END processing of the sequence.

REMARKS

Full-scale value of analog input is determined by the setting of Pr. 73 Analog input selection, Pr. 267 Terminal 4 input selection. Refer to the inverter instruction manual (applied).

1.10.2 Analog output

Analog output from each terminal can be performed by setting value on D9251 to D9254.

Output from PLC function can be performed by setting "7" in output signal selection parameters of each terminal (terminal FM: Pr. 54, terminal AM: Pr. 158, terminal AMO, AM1: Pr. 306, Pr. 310).

Device

Terminal Name

Setting

Data Access Enable

No.

 

Unit

Condition

D9251

Terminal FM

0.1%

 

D9252

Terminal AM

0.1%

 

D9253

Terminal AM0

0.1%

Always

(FR-A7AY)

D9254

Terminal AM1

0.1%

 

(FR-A7AY)

 

Actual read processing is performed at the END processing of the sequence.

1

REMARKS

High speed pulse train output (Pr. 291) from terminal FM can be performed. (Refer to the

inverter instruction manual (applied).)

PLC FUNCTION

39

Page 44