1.2 PLC Function Specifications

The following table indicates the program capacity and devices of the PLC function.

 

 

 

 

A700 Sequence Section

Control method

 

Repeated operation (by stored program)

I/O control method

 

Refresh

Programming language

Relay symbolic language (ladder mode)

Logic symbolic language (list mode)

 

 

 

 

Number of instruction

PLC instructions

23

Basic instructions

32

Application instructions

18

 

 

 

 

 

 

 

 

 

Processing speed

 

PLC instruction 1.9s to 12s/step(*2)

 

 

 

 

128 (X: 64 points, Y: 64 points)

Number of I/O points

 

19 points installed, X: 12 points, Y: 7 points (*1)

 

FR-A7AX, X: 16 points

 

 

 

 

FR-A7AY, Y: 6 points

 

 

 

 

FR-A7AR, Y: 3 points

Number of analog I/O points

5 points installed, Input: 3 points, Output: 2 points

FR-A7AY output: 2 points

 

 

 

 

Watchdog timer

 

10 to 2000(ms)

Memory capacity

 

6k bytes used by sequence and parameters.

Program capacity

 

1k step

 

Internal relay (M)

64(M0 to M63)

 

Latch relay (L)

 

None (Can be set with parameters but will not latch)

 

Step relay (S)

 

None (Can be set with parameters but will operate as M)

 

Link relay (B)

 

None

 

 

 

Points

16

 

Timer (T)

 

100ms timer: Set time 0.1 to 3276.7s (T0 to T15)

 

Specifications

10ms timer: Set time 0.01 to 327.67s

 

 

 

 

 

 

 

100ms retentive timer: Set time 0.1 to 3276.7s

Devices

Counter (C)

 

Points

16

 

Specifications

Normal counter: Setting range 1 to 32767 (C0 to C15)

 

 

Interrupt program counter: None

 

 

 

Data device (D)

 

120(D0 to D119)

Link register (W)

None

 

 

Annunciator (F)

 

None

 

File register (R)

 

None

 

Accumulator (A)

None

 

Index register (Z, V)

None

 

Pointer (P)

 

None

 

Interrupt pointer (I)

None

 

Special relay (M)

256 (M9000 to 9255) with function limit

 

Special register (D)

256 (D9000 to 9255) with function limit

*1 These signals use the same terminals as used by the input and output signals given in the common specifications of the inverter.

One point is always necessary for a sequence start (RUN/STOP).

*2 As inverter control is also performed actually, the scan time is approximately 40ms at 500 steps.

1

PLC FUNCTION

3

Page 8
Image 8