PremierLink Connections
40RMQ Connections | 38AQ007 |
| Control |
| Connections |
CUT FOR DUAL | TRANSFORMER | EQUIPTMENT |
CUT TO ISOLATE | CONTROLLER | POWER |
RED
RED
RELAYS
RED
RED
J1 J8
PWR
PWR
RED
HS3/EXH/RVS
ORN CR
HS2
PNK
HS1
WHT
CMP2
BLU
CMP1
YEL
FAN
GRN
BRN
|
|
| R |
R |
|
|
|
Y1 | 40RM, 40RMQ, 40RMS |
| |
Y2 |
| HEAT ACCESSORY |
|
|
|
| |
W1 |
| W1 |
|
W2 |
| W2 | CR |
G | WHT C1 IFC C2 | C | O |
C | WHT |
| |
|
| ||
X |
|
|
|
|
|
| W |
|
|
| Y |
|
|
| BL |
LEGEND
CR — Control Relay
IAQ —
IFC —
NOTES:
1.Configure AC to “1” for heat pump units.
2.Configure AUXOUT to “3’ for reversing valve.
3.Configure PremierLink control for
4.If IAQ is high priority, wire HS2 to W1. If not, wire HS1 to W1.
Fig. 2G — Typical PremierLink™ Control Wiring — 38AQ007 Units
PremierLink Connections | 40RM Connections |
38AQS008
Terminal
Board (TB)
RED
RED
PWR
RED
HS3/EXH/RVS
ORN CR
HS2
PNK
HS1
WHT
R
Y1
Y2
W1
W2
G
C
40RM, 40RMQ, 40RMS
HEAT ACCESSORY
W1
W2
WHT C1 IFC C2 | C |
WHT
R
Y1
Y2
CUT |
RELAYS
RED
RED
CMP2
CMP1
BLU
YEL
X
LLSV
W1
CR
W2
G
CUT TO ISOLATE CONTROLLER POWER |
PWR J1 J8
FAN
GRN
BRN
C
X
LEGEND
CR — Control Relay
IFC —
IAQ —
LLSV — Liquid LIne Solenoid Valve
NOTES:
1.Configure AC to “1” for heat pump units.
2.Configure AUXOUT to “3” for reversing valve.
3.Configure PremierLink control for
4.When using controller for DCV, if IAQ priority is set to HIGH, the controller will use a stage of heat for temperature tempering. If priority is set to LOW, no tempering will occur. If IAQ is high priority, wire HS2 to W1. If not, wire HS1 to W1.
Fig. 2H — Typical PremierLink Control Wiring — 38AQS008 and 38ARQ008,012 Units
7