Carrier 33CSPREMLK Service Configuration Selection, Default Value Enable Stage Time Guard Range

Page 34

Table 14 — Service Configuration Selection

DESCRIPTION

VALUE

UNITS

NAME

Cooling PID

 

 

 

Proportional Gain

6.0

 

KP

Integral Gain

3.0

 

KI

Derivative Gain

5.0

 

KD

Starting Value

70.0

dF

STARTVAL

Staged Cooling

 

 

 

Total Number of Stages

2

 

STAGES

Stage 1 Time Guard

Enable

 

TG1

Stage 2 Time Guard

Enable

 

TG2

Stage 3 Time Guard

Disable

 

TG3

Heating PID

 

 

 

Proportional Gain

6.0

 

KP

Integral Gain

3.0

 

KI

Derivative Gain

5.0

 

KD

Starting Value

75.0

dF

STARTVAL

Staged Heating

 

 

 

Total Number of Stages

2

 

STAGES

Stage 1 Time Guard

Enable

 

TG1

Stage 2 Time Guard

Enable

 

TG2

Stage 3 Time Guard

Enable

 

TG3

IAQ PID

 

 

 

Proportional Gain

0.1

 

KP

Integral Gain

0.0

 

KI

Derivative Gain

0.0

 

KD

Starting Value

0.0

%

STARTVAL

Economizer PID

 

 

 

Proportional Gain

-4.0

 

KP

Integral Gain

-2.0

 

KI

Derivative Gain

-3.0

 

KD

Starting Value

70.0

dF

STARTVAL

Submaster Gain Limit

-5.5

 

ESG

Submaster Center Value

60

%

CTRVAL

Damper Movement Band

0

%

ECONBAND

OAT Temp Band

25

^F

TEMPBAND

Minimum Damper Position

20

%

MDP

Low Temp MDP Override

100

%

LOWMDP

DX Cooling Lockout

On

 

DXCTLO

DX Cooling Lockout Temp

45.0

dF

DXLOCK

SAT CMP1 Lockout Temp

55.0

dF

SATL01

SAT CMP2 Lockout Temp

50.0

dF

SATL02

Time Guard Override

Off

 

TGO

Continuous Power Exhaust

Disable

 

MODPE

Supply Fan Status Enable

Disable

 

SFSENABL

Max Offset Adjustment

2.0

^F

LIMT

Space Temp Trim

0.0

^F

RATTRIM

Supply Air Temp Trim

0.0

^F

SATTRIM

STAGED COOLING — The staging function is used for DX cooling (1 or 2 stages). The staging function uses the cooling submaster reference from the PID and compares the value to the supply air temperature to calculate the required number of output stages to energize.

Time Guard delays are provided to allow for up to 2 stages of compression. Also, a DX Lockout will prevent operation of the DX cooling if the outdoor air temperature is below this value.

The cooling algorithm controls the valve or stages of DX cooling to prevent the space temperature from exceeding the current cooling set point (which includes any calculated offset value from a T56 sensor slide bar during occupied periods).

Also, the cooling is controlled so that the supply air tempera- ture does not fall below 50 F when cooling is active.

If number of stages is set to 1, then the SAT CMP2 LOCK- OUT TEMP will be used as the low supply air set point.

Number of Stages: Range:

1 to 3

Default Value:

2

The Time Guards must be set to Enable for output to a compressor, and set to Disable for output to a valve or compressor unloader.

Stage 1

Time Guard: Range: Disable/Enable Default Value: Enable

Stage 2

Time Guard: Range: Disable/Enable Default Value: Enable

Stage 3

Time Guard: Range: Disable/Enable Default Value: Disable

HEATING PID — The PremierLink™ controller determines if a heating demand exists in the space. The controller reads the space temperature sensor and compares the temperature to the current low set point (including any calculated offset value from a T56 or T57 sensor) during occupied periods. If it is below the set point, and heating is configured and available, it then calculates the required supply air temperature to satisfy the given conditions. The calculated value (heating submaster reference) is compared to the actual supply-air temperature and the output is then adjusted to satisfy conditions by using a Proportional/Integral/Derivative (PID) loop.

The Heating PID includes the following set points: Propor- tional Gain, Integral Gain, Derivative Gain, and Starting Value.

Proportional Gain:

Range:

–100.0 to 100.0

 

Default Value:

6.0

Integral Gain:

Range:

–5.0 to 5.0

 

Default Value:

3.0

Derivative Gain:

Range:

–20.0 to 20.0

 

Default Value:

5.0

Starting Value:

Units:

Degrees F

 

Range:

40.0 to 120.0

 

Default Value:

75.0

STAGED HEATING — The Staged Heating function is used for two-position valves or for electric heat (1 or 2 stages). The staging function uses the heating submaster reference value from the PID and compares it to the supply air temperature to calculate the required number of output stages to energize.

Number of Stages:

Range:

1 to 3

 

Default Value:

2

Stage 1

 

 

Time Guard:

Range:

Disable/Enable

 

Default Value:

Enable

Stage 2

 

 

Time Guard:

Range:

Disable/Enable

 

Default Value:

Enable

Stage 3

 

 

Time Guard:

Range:

Disable/Enable

 

Default Value:

Enable

IAQ PID — The proportional gain affects the response of PID calculations for staged control. The gain is also used for two- position control to establish the hysteresis between on and off. A larger gain speeds response time or reduces the hysteresis, while a smaller gain requires a larger error to generate the same response to changes in Indoor Air Quality. Enter the desired proportional gain for the Indoor Air Quality control algorithm.

34

Image 34
Contents Installation, Start-Up Configuration Instructions Installation PremierLink Controller Inputs and Outputs Typical PremierLink Control Wiring 38AKS013-024 Units Typical PremierLink Control Wiring 38ARD012 Units Typical PremierLink Control Wiring 38AH024-034 Units Typical PremierLink Control Wiring 38AQ007 Units PremierLink Connections Color Code Recommendations Space Temperature Sensor Typical Wiring 33ZCT55SPT T58 Communicating Sensor Typical Wiring 33ZCT58SPT Sampling of airSpace Temperature Averaging Page Page Page Page Outdoor Air Quality Sensor Cover Recommended Cables 33CSENTHSW Used with Differential Enthalpy Control only Differential Enthalpy Control Wiring On the adapter connects to P terminal on the actuator Using the transformer supplied with the 40RM econoAdapter onto terminals P1 and P of actuator See FigPage Actuator Drive Direction Settings Mode Selection Information24 VAC/VDC START-UP PremierLink Navigator Carrier SAT 54.2 FDefault Value Display Range Network Access Read Only Supply Air Temperature Display UnitsControl Set Point Display Units Points Display Description Value Units Status Force NameMillion implied Indoor Air Quality ppm Display UnitsSet Point Display Units Thermostat Control Input Display Alarm Service ConfigurationController Identification Holiday Configuration Occupancy ConfigurationRange Default Value Set Point ConfigurationDefault Value Enable Stage Time Guard Range Service Configuration SelectionNumber of Stages Range Default Value Time Guard Default Value EnablePage Max Offset Adjustment Units Delta Degrees F Range 50.0 to Default Value 55.0Space Temperature Trim Units Delta Degrees F For Electric Heat PremierLink Control ConfigurationAuxiliary Output Range Default Value Heat Start Bias Units MON, TUE, WED Occupancy Maintenance IAQ Maintenance YesPage Copyright 2002 Carrier Corporation