Carrier 33CSPREMLK specifications Range Default Value, Set Point Configuration

Page 33

UNOCCUPIED HIGH — The Unoccupied High set point de- scribes the high temperature limit of the space during Unoccu- pied mode.

Unoccupied High: Units:

Degrees F (Degrees C)

Range:

45.0 to 99.9

Default Value:

90.0

HIGH OAT LIMIT FOR IAQ PRE-OCCUPANCY PURGE — The High OAT unit for IAQ Pre-Occupancy Purge function determines the Economizer Damper position used for IAQ Pre-Occupancy Purge.

High OAT

 

 

Limit:

Units:

Degrees F (Degrees C)

 

Range:

55.0 to 75.0

 

Default Value:

65.0

UNOCCUPIED OAT LOCKOUT TEMPERATURE — The Unoccupied OAT Lockout Temperature describes the low- est Outdoor Air Temperature allowed for Unoccupied Free Cooling operation. This function is also used by IAQ Pre- Occupancy Purge control to determine the minimum damper position for IAQ Purge.

Unoccupied

 

 

OAT Lockout:

Units:

Degrees F (Degrees C)

 

Range:

40.0 to 70.0

 

Default Value:

50.0

UNOCCUPIED HEATING DEADBAND — The Unoccu- pied Heating Deadband describes the space temperature value which has to be achieved while unoccupied Heating before the unoccupied Heating mode will turn off.

Unoccupied

 

 

Heating

 

 

Deadband:

Units:

Degrees F (Degrees C)

 

Range:

0.0 to 10.0

 

Default Value:

1.0

UNOCCUPIED COOLING DEADBAND — The Unoccu- pied Cooling Deadband describes the space temperature value which has to be achieved while unoccupied Cooling before the unoccupied Cooling mode will turn off.

Unoccupied

 

 

Cooling

 

 

Deadband:

Units:

Delta Degrees F

 

 

(Delta Degrees C)

 

Range:

0.0 to 10.0

 

Default Value:

1.0

LOW TEMPERATURE MINIMUM POSITION — The Low Temperature Minimum Position describes the low temperature limit for Low Outdoor Air Temperature conditions.

IAQ Pre-Occupancy Purge Algorithm will use this value whenever Outdoor Air Temperature is below Unoccupied OAT Lockout Temperature.

Low Temperature Minimum

Position: Units: Percent

Range: 0 to 100

Default Value: 10.0

HIGH TEMPERATURE MINIMUM POSITION — The High Temperature Minimum Position specifies the value for Purge Minimum Damper Position for High Outdoor Air temperature conditions.

IAQ Pre-Occupancy Purge Algorithm shall use this value whenever Outdoor Air Temperature is above or at Unoccupied OAT Lockout Temperature, and also OAT is above Occupied Cool Set Point or Enthalpy is High. Whenever OAT>=NTLO and OAT<=OCSP and Enthalpy is Low, the Purge algorithm will set Purge Minimum Damper Position to 100%.

High Temperature Minimum

Position: Units: Percent

Range: 0 to 100

Default Value: 35.0

POWER EXHAUST SET POINT — The Power Exhaust Set Point describes the minimum damper position that the Econo- mizer Damper must be before the power exhaust fan will be energized.

Power Exhaust

 

 

Set Point:

Units:

Percent

 

Range:

0 to 100

 

Default Value:

50.0

Table 13 — Set Point Configuration

DESCRIPTION

VALUE

UNITS

NAME

Setpoints

 

 

 

Occupied Low Setpoint

70.0

dF

OHSP

Occupied High Setpoint

74.0

dF

OCSP

Unoccupied Low Setpoint

69.0

dF

UHSP

Unoccupied High Setpoint

75.0

dF

UCSP

Hi OAT Limit for

65.0

dF

OATL

IAQ Pre-Occ Purge

 

 

 

 

 

Unocc. OAT Lockout TEMP

50.0

dF

NTLO

Unocc. Heating Deadband

1.0

^F

UHDB

Unocc. Cooling Deadband

1.0

^F

UCDB

Low Temp. Min. Position

10

%

LTMP

Hi Temp. Min. Position

35

%

HTMP

Power Exhaust Setpoint

50

%

PES

Service Configuration Selection Screen — The Service Configuration Selection screen is used to configure the service set points of the PremierLink™ controller. See Table 14.

COOLING PID — The PremierLink controller reads the space temperature sensor and compares the temperature to he current high set point. If it exceeds the set point, and cooling is configured and available, the controller then calculates the re- quired supply air temperature to satisfy the given conditions.

The Cooling PID (Proportional/Integral/Derivative) in- cludes the following set points: Proportional Gain, Integral Gain, Derivative Gain, and Starting Value.

Proportional Gain:

Range:

0.0 to 40.0

 

Default Value:

6.0

Integral Gain:

Range:

0.0 to 10.0

 

Default Value:

3.0

Derivative Gain:

Range:

0.0 to 20.0

 

Default Value:

5.0

Starting Value:

Units:

Degrees F

 

Range:

40.0 to 90.0

 

Default Value:

70.0

33

Image 33
Contents Installation, Start-Up Configuration Instructions Installation PremierLink Controller Inputs and Outputs Typical PremierLink Control Wiring 38AKS013-024 Units Typical PremierLink Control Wiring 38ARD012 Units Typical PremierLink Control Wiring 38AH024-034 Units Typical PremierLink Control Wiring 38AQ007 Units PremierLink Connections Color Code Recommendations Space Temperature Sensor Typical Wiring 33ZCT55SPT Sampling of air T58 Communicating Sensor Typical Wiring 33ZCT58SPTSpace Temperature Averaging Page Page Page Page Outdoor Air Quality Sensor Cover Recommended Cables 33CSENTHSW Used with Differential Enthalpy Control only Differential Enthalpy Control Wiring Adapter onto terminals P1 and P of actuator Using the transformer supplied with the 40RM econoOn the adapter connects to P terminal on the actuator See FigPage Mode Selection Information Actuator Drive Direction Settings24 VAC/VDC START-UP SAT 54.2 F PremierLink Navigator CarrierSupply Air Temperature Display Units Default Value Display Range Network Access Read OnlyControl Set Point Display Units Description Value Units Status Force Name Points DisplayIndoor Air Quality ppm Display Units Million impliedSet Point Display Units Alarm Service Configuration Thermostat Control Input DisplayController Identification Occupancy Configuration Holiday ConfigurationSet Point Configuration Range Default ValueNumber of Stages Range Default Value Time Guard Service Configuration SelectionDefault Value Enable Stage Time Guard Range Default Value EnablePage Range 50.0 to Default Value 55.0 Max Offset Adjustment Units Delta Degrees FSpace Temperature Trim Units Delta Degrees F PremierLink Control Configuration For Electric HeatAuxiliary Output Range Default Value Heat Start Bias Units MON, TUE, WED Occupancy Maintenance IAQ Yes MaintenancePage Copyright 2002 Carrier Corporation