Carrier 33CSPREMLK specifications Points Display, Description Value Units Status Force Name

Page 29

Table 7 — Points Display

DESCRIPTION

VALUE

UNITS

STATUS

FORCE

NAME

Space Temperature

72.2

dF

 

 

SPT

Supply Air Temperature

67.1

dF

 

 

SAT

Outdoor Air Temperature

48.8

dF

 

 

OAT

Control Setpoint

0.0

dF

 

 

CLSP

Cooling % Total Capacity

0

%

 

 

CCAP

Heating % Total Capacity

0

%

 

 

HCAP

Economizer Active

Yes

 

 

 

ECOS

Supply Fan Relay

On

 

 

 

SF

Supply Fan Status

On

 

 

 

SFS

Economizer Position

26.2

%

 

 

ECONPOS

Current Min Damper Pos

20

%

 

 

IQMP

Filter Status

Clean

 

 

 

FLTS

Remote Occupied Mode

Off

 

 

 

RMTOCC

Heat Stage 1

Off

 

 

 

HS1

Heat Stage 2

Off

 

 

 

HS2

Heat 3/Exhaust/Rev Valve

Off

 

 

 

H3_EX_RV

Enthalpy

Low

 

 

 

ENTH

Indoor Air Quality

367.9

 

 

 

IAQI

Indoor Air Quality Setpt

1050.0

 

 

 

IAQS

Outdoor Air Quality

0.0

 

Sensor failure

 

OAQ

Fire Shutdown

Normal

 

 

 

FSD

SPT Offset

0.0

^F

 

 

STO

Compressor 1

Off

 

 

 

CMP1

Compressor 2

Off

 

 

 

CMP2

Compressor Safety

Off

 

 

 

CMPSAFE

NOTE: Bold values indicate points that can be forced through communications.

SUPPLY FAN STATUS — This point displays the Supply Fan status if controller is configured to receive input from the Supply Fan. Otherwise this point will display the output state of the Supply Fan Relay. This mode can only be used when the controller is in sensor control mode.

Supply Fan

Status: Display Units: Discrete ASCII Default Value: Off

Display Range: Off/On

Network Access: Read Only

ECONOMIZER DAMPER POSITION — This point dis- plays the current commanded damper position of the economizer 4 to 20 mA on the J-9 connector. The 4 to 20 mA signal is scaled linearly over the range of 0 to 100% of the Sup- ply Fan Relay.

Economizer

Position: Display Units: % Open Default Value: 0 Display Range: 0 to 100 Network Access: Read/Write

CURRENT MINIMUM DAMPER POSITION — This point displays the current minimum damper position if an Indoor Air Quality routine is not active. If an Indoor Air Quality sensor is installed and the differential air quality set point has been exceeded, this point will display the current calculated mini- mum position deemed necessary to maintain the air quality in the space.

Current Minimum

Damper Position: Display Units: % Open Default Value: 0 Display Range: 0 to 100 Network Access: Read Only

FILTER STATUS — The filter status point will be shown as “CLEAN” until the run time of the fan exceeds the configured Filter Timer Hours. When the user-configured Filter Timer Hours has been exceeded, the Filter Status will display “DIRTY” and a CCN alarm will be generated. Forcing the point to “CLEAN” will clear the alarm condition and will reset the timer. (Setting the configured filter timer value to zero will provide the same function.) The value of the timer is stored in EEPROM to protect it in the event of a power failure. This is done periodically every 24 hours. The filter timer function only operates if the configured filter timer value (FLTTMR) is a non-zero number.

Filter Status:

Display Units:

Discrete ASCII

 

Default Value:

Clean

 

Display Range:

Clean/Dirty

 

Network Access:

Read/Write

REMOTE OCCUPIED MODE — This point displays the status of the remote time clock input. This input is only avail- able when the controller is being used in sensor control mode. When the Remote Start point is on, and the zone controller is not controlled by a Linkage Thermostat, the controller will function in an occupied mode. When the Remote Start point is off, the controller will revert to its own occupancy schedule.

Remote

Occupied Mode: Display Units: Discrete ASCII Default Value: Off

Display Range: Off/On

Network Access: Read/Write

HEAT STAGE 1 — The Heat Stage 1 point provides the state of the Heating 1 output.

Heating Stage 1: Display Units:

Discrete ASCII

Default Value:

Off

Display Range:

Off/On

Network Access:

Read Only

29

Image 29
Contents Installation, Start-Up Configuration Instructions Installation PremierLink Controller Inputs and Outputs Typical PremierLink Control Wiring 38AKS013-024 Units Typical PremierLink Control Wiring 38ARD012 Units Typical PremierLink Control Wiring 38AH024-034 Units Typical PremierLink Control Wiring 38AQ007 Units PremierLink Connections Color Code Recommendations Space Temperature Sensor Typical Wiring 33ZCT55SPT Sampling of air T58 Communicating Sensor Typical Wiring 33ZCT58SPTSpace Temperature Averaging Page Page Page Page Outdoor Air Quality Sensor Cover Recommended Cables 33CSENTHSW Used with Differential Enthalpy Control only Differential Enthalpy Control Wiring Adapter onto terminals P1 and P of actuator Using the transformer supplied with the 40RM econoOn the adapter connects to P terminal on the actuator See FigPage Mode Selection Information Actuator Drive Direction Settings24 VAC/VDC START-UP SAT 54.2 F PremierLink Navigator CarrierControl Set Point Display Units Supply Air Temperature Display UnitsDefault Value Display Range Network Access Read Only Description Value Units Status Force Name Points DisplaySet Point Display Units Indoor Air Quality ppm Display UnitsMillion implied Controller Identification Alarm Service ConfigurationThermostat Control Input Display Occupancy Configuration Holiday ConfigurationSet Point Configuration Range Default ValueNumber of Stages Range Default Value Time Guard Service Configuration SelectionDefault Value Enable Stage Time Guard Range Default Value EnablePage Space Temperature Trim Units Delta Degrees F Range 50.0 to Default Value 55.0Max Offset Adjustment Units Delta Degrees F Auxiliary Output PremierLink Control ConfigurationFor Electric Heat Range Default Value Heat Start Bias Units MON, TUE, WED Occupancy Maintenance IAQ Yes MaintenancePage Copyright 2002 Carrier Corporation