Carrier 33CSPREMLK specifications Maintenance, Yes

Page 42

The Average Occupied Heat Set Point displays the Occupied Heat set point from the Linkage Thermostat.

Average Occupied

 

Heat Set Point: Display Units:

Degrees F (Degrees C)

Display Range:

0.0 to 99.9

Default Value:

0.0

Network Access:

None

The Average Occupied Cool Set Point displays the Occu- pied Cool set point from the Linkage Thermostat.

Average Occupied

 

Cool Set Point: Display Units:

Degrees F (Degrees C)

Display Range:

0.0 to 99.9

Default Value:

0.0

Network Access:

None

The Average Unoccupied Heat Set Point displays the Unoc- cupied heat set point from the Linkage Thermostat.

Average Unoccupied

Heat Set Point: Display Units: Degrees F (Degrees C) Display Range: 0.0 to 99.9

Default Value: 0.0

Network Access: None

The Average Unoccupied Cool Set Point displays the Unoc- cupied cool set point from the Linkage Thermostat.

Average Unoccupied

Cool Set Point: Display Units: Degrees F (Degrees C) Display Range: 0.0 to 99.9

Default Value: 0.0

Network Access: None

The Average Zone Temperature displays the space tempera- ture from the Linkage Thermostat.

Average Zone

 

 

Temperature:

Display Units:

Degrees F (Degrees C)

 

Display Range:

0.0 to 99.9

 

Default Value:

0.0

 

Network Access:

None

The Average Occupied Zone Temperature displays the space temperature from the Linkage Thermostat during occu- pied periods.

Average Occupied

Zone Temperature: Display Units: Degrees F (Degrees C) Display Range: 0.0 to 99.9

Default Value: 0.0

Network Access: None

The Occupancy Status point displays a 1 if occupancy is re- ported by the Linkage Thermostat. The Occupancy Status point displays a 0 if occupancy is not reported by the Linkage Thermostat.

Occupancy

Status:Display Range: 0, 1 Default Value: 0 Network Access: None

Table 17 — Maintenance

DESCRIPTION

VALUE

UNITS

STATUS

FORCE

NAME

Thermostat Control

No

 

 

 

TSTAT

Occupied

Yes

 

 

 

OCCUP

Timed Override in Effect

No

 

 

 

TIMOV

Start Bias Time

0

min

 

 

STRTBIAS

Heat

No

 

 

 

HEAT

Cool

No

 

 

 

COOL

IAQ Control

No

 

 

 

IAQCL

Demand Limit

No

 

 

 

DEMLT

Temp Compensated Start

No

 

 

 

TCSTR

IAQ Pre-Occupancy Purge

No

 

 

 

IQPRG

Unoccupied Free Cool

No

 

 

 

NTFCL

Fire Shutdown

No

 

 

 

FIRES

Linkage Control

No

 

 

 

DAVCL

Field/Startup Test

No

 

 

 

FIELD

Heat Submaster Ref

40.0

dF

 

 

SHSR

Cool Submaster Ref

150.0

dF

 

 

CCSR

Economizer Submaster Ref

120.0

dF

 

 

ECONSR

Economizer Submastr Gain

0.00

 

 

 

ECONGN

Compressor Starts

0.00

 

 

 

CMPST

Compressor 1 Runtime

0.00

HOURS

 

 

CM1RT

Compressor 2 Runtime

0.00

HOURS

 

 

CM2RT

Supply Fan Runtime

17.00

HOURS

 

 

FANRT

Linkage Thermostat

 

 

 

 

 

Linkage Status

2

 

 

 

LINKSTAT

Supervisory Element

0

 

 

 

SUPE-ADR

Supervisory Bus

0

 

 

 

SUPE-BUS

Supervisory Block

0

 

 

 

BLOCKNUM

Average Occ Heat Setpt

0.0

dF

 

 

OCLOSTPT

Average Occ Cool Setpt

0.0

dF

 

 

OCHISTPT

Average Unoc Heat Setpt

0.0

dF

 

 

UNLOSTPT

Average Unoc Cool Setpt

0.0

dF

 

 

UNHISTPT

Average Zone Temp

0.0

dF

 

 

AZT

Average Occ Zone Temp

0.0

dF

 

 

AOZT

Occupancy Status(1=occ)

1

 

 

 

OCCSTAT

NOTE: Bold values indicate points that can be forced through communications.

42

Image 42
Contents Installation, Start-Up Configuration Instructions Installation PremierLink Controller Inputs and Outputs Typical PremierLink Control Wiring 38AKS013-024 Units Typical PremierLink Control Wiring 38ARD012 Units Typical PremierLink Control Wiring 38AH024-034 Units Typical PremierLink Control Wiring 38AQ007 Units PremierLink Connections Color Code Recommendations Space Temperature Sensor Typical Wiring 33ZCT55SPT T58 Communicating Sensor Typical Wiring 33ZCT58SPT Sampling of airSpace Temperature Averaging Page Page Page Page Outdoor Air Quality Sensor Cover Recommended Cables 33CSENTHSW Used with Differential Enthalpy Control only Differential Enthalpy Control Wiring On the adapter connects to P terminal on the actuator Using the transformer supplied with the 40RM econoAdapter onto terminals P1 and P of actuator See FigPage Actuator Drive Direction Settings Mode Selection Information24 VAC/VDC START-UP PremierLink Navigator Carrier SAT 54.2 FSupply Air Temperature Display Units Default Value Display Range Network Access Read OnlyControl Set Point Display Units Points Display Description Value Units Status Force NameIndoor Air Quality ppm Display Units Million impliedSet Point Display Units Alarm Service Configuration Thermostat Control Input DisplayController Identification Holiday Configuration Occupancy ConfigurationRange Default Value Set Point ConfigurationDefault Value Enable Stage Time Guard Range Service Configuration SelectionNumber of Stages Range Default Value Time Guard Default Value EnablePage Range 50.0 to Default Value 55.0 Max Offset Adjustment Units Delta Degrees FSpace Temperature Trim Units Delta Degrees F PremierLink Control Configuration For Electric HeatAuxiliary Output Range Default Value Heat Start Bias Units MON, TUE, WED Occupancy Maintenance IAQ Maintenance YesPage Copyright 2002 Carrier Corporation