Carrier 30RAP010-060 specifications OPT1, SUB-MODE Keypad Display Comment Entry Expansion Unit

Page 12

Table 10 — Configuration Mode and Sub-Mode Directory

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

COMMENT

ENTRY

EXPANSION

 

 

 

 

UNIT

 

 

ENTER

 

 

 

 

UNIT CONFIGURATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIZE

XX

UNIT SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SZA.1

XX

COMPRESSOR A1 SIZE

Unit Dependent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SZA.2

XX

COMPRESSOR A2 SIZE

Unit Dependent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SZA.3

XX

COMPRESSOR A3 SIZE

Unit Dependent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SZA.4

XX

COMPRESSOR A4 SIZE

Unit Dependent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SZB.1

XX

COMPRESSOR B1 SIZE

Unit Dependent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SZB.2

XX

COMPRESSOR B2 SIZE

Unit Dependent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SZB.3

XX

COMPRESSOR B3 SIZE

Unit Dependent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SZB.4

XX

COMPRESSOR B4 SIZE

Unit Dependent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SH.SP

XX.X ΔF

SUPERHEAT SETPOINT

Default: 9 °F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN.S

 

NUMBER OF FANS

1 = One Fan

 

 

 

 

 

 

 

 

 

2 = Two Fans

 

 

 

 

 

 

 

 

 

3 = Three Fans

 

 

 

 

 

 

 

 

 

4 = Four Fans

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXV

YES/NO

EXV MODULE INSTALLED?

Default: Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Default: No

 

 

 

 

 

 

A1.TY

YES/NO

COMPRESSOR A1 DIGITAL?

Yes = A1 Compressor is Digital

 

 

 

 

 

 

 

 

 

Scroll

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Default: 7

 

 

 

 

 

 

MAX.T

0 to 12

MAXIMUM A1 UNLOAD TIME

Max 12 010,015

 

 

 

 

 

 

 

 

 

Max 10 018-060

 

 

 

 

 

 

 

 

 

 

OPT1

 

 

 

 

 

 

 

UNIT OPTIONS 1 HARDWARE

 

 

 

 

 

 

 

 

 

 

Default: Water

 

 

 

ENTER

 

 

FLUD

X

COOLER FLUID

1 = Water

 

 

 

 

2 = Medium Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brine

 

 

 

 

 

 

MLV.S

YES/NO

MINIMUM LOAD VALVE SELECT

Default: No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D.G.EN

ENBL/DSBL

DISCHARGE GAS TEMP ENABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CSB.E

ENBL/DSBL

CSB BOARDS ENABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPC

ON/OFF

COOLER PUMP CONTROL

Default: Off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PM1E

YES/NO

COOLER PUMP 1 ENABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PM2E

YES/NO

COOLER PUMP 2 ENABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PM.P.S

YES/NO

COOLER PMP PERIODIC STRT

Default: No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PM.SL

X

COOLER PUMP SELECT

Default: Automatic

 

 

 

 

 

 

 

 

 

0 = Automatic

 

 

 

 

 

 

 

 

 

1 = Pump 1 Starts first

 

 

 

 

 

 

 

 

 

2 = Pump 2 Starts first

 

 

 

 

 

 

PM.DY

XX MIN

COOLER PUMP SHUTDOWN DLY

0 to 10 minutes, Default: 1

 

 

 

 

 

 

min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PM.DT

XXXX HRS

PUMP CHANGEOVER HOURS

Default: 500 hours

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ROT.P

YES/NO

ROTATE COOLER PUMPS NOW

User Entry

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EMM

YES/NO

EMM MODULE INSTALLED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CND.T

0,1

COND HX

0 = RTPF

 

 

 

 

 

 

1 = MCHX Default MCHX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOPS

XX

EXV MOP SET POINT

Range: 40 - 80 Default: 50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

APPR

XX

CONFIG APPROACH SETPOINT

Range: 5 - 40 Default: 9.0

 

 

 

 

 

 

 

 

 

 

12

Image 12
Contents Controls, Start-Up, Operation, Service, and Troubleshooting ContentsContents Safety ConsiderationsGeneral Basic Controls UsageUnit Sizes Unit Nominal Capacity TonsAccessory Navigator Display Module Mode RUN Service Temperatures SET Inputs Outputs Configuration Time Operating AlarmsScrolling Marquee Display Menu Structure TestRun Status Mode and Sub-Mode Directory StrtSUB-MODE Keypad Display SUB-ITEM Comment Entry Expansion VersService Test Mode and Sub-Mode Directory SUB-MODE Keypad Display Comment Entry Expansion TestOuts CmpaTemperature Mode and Sub-Mode Directory Pressure Mode and Sub-Mode DirectorySet Points Mode and Sub-Mode Directory Inputs Mode and Sub-Mode Directory Outputs Mode and Sub-Mode DirectoryConfiguration Mode and Sub-Mode Directory SUB-MODE Keypad Display Comment Entry Expansion EXVOPT1 SUB-MODE Keypad Display Comment Entry Expansion UnitSUB-MODE Keypad Display Comment OPT2XXX XXX.X ΔF Time Clock Mode and Sub-Mode Directory DateDST Operating Mode and Sub-Mode Directory Alarms Mode and Sub-Mode DirectoryMode Item Expansion Description Operating ModesControls Control Module CommunicationCarrier Comfort Network CCN Interface CCN Communication Bus Wiring Thermistor DesignationsStatus Inputs Output RelaysAlmr AUXCCB CHCA30-4962 A30-4963A30-4964 Typical Control Box for 30RAP035-060Typical Wiring Schematic, 30RAP018-030 Units Power Wiring Typical Wiring Schematic, 30RAP018-030 Units Control Wiring A30-4966Typical Wiring Schematic, 30RAP035-060 Units Power Wiring 5283Typical Wiring Schematic, 30RAP035-060 Units Control Wiring A30-5284A30-4967 A30-4968Page CEPL130351 Deadband Multiplier 30RAP Unit Size Control Capacity Steps Capacity %A30-4969 Operating Envelope for R-410A CompressorCooling Set Point Select A30-497030RAP Unit Size FAN Stages Optional Factory-Installed Hydronic Pack Control Methods and Cooling Set PointsControl Occupancy Cooling SET Point Select Clsp Type State CCN→PM1E = YES Configuring and Operating Dual Chiller Con Dual Chiller Configuration Master Chiller Example RsetPart NumberSUB-MODE Keypad Entry Display Item Expansion Comments Dual Chiller Configuration Slave Chiller Example Rset Slave CompleteTo 20 mA Reset Menu Configuration of 4 to 20 mA Cooling Set Point ControlConfiguring Outdoor Air and Space Temperature Reset Configuring Return Temperature ResetMode Keypad SUB Display RED LED Entry ModeOutdoor-Air Temperature Reset To 20-mA Demand Limiting Configuring Demand Limit Item Expansion Comment Entry ConfigurationPRE-START-UP System CheckSTART-UP and Operation A30-497830RAP Minimum Cooler Flow Maximum Cooler Flow Size Temperature Limits for Standard 30RAP Units Operating LimitationsOperation Sequence Unit Size 30RAService Electronic ComponentsEXV Steps Unit Size 30RAP EXV StepsA30-4971 Electronic Expansion Valve DetailsCompressor Replacement Refer to Fig Unit Torque SpecificationCooler A30-4972Oil Charge Check Refrigerant Feed ComponentsA30-4973 A30-4974LWT Factory Settings, High-Pressure Switch Fixed Check Unit SafetiesUnit Cutout CUT-IN Thermistor Well Temp Voltage Resistance Drop 100,260 143 86K Thermistor vs Resistance DTT DropA30-4975 A30-499A30-4976 AccsyP50 Fault History Last 8 faults P51 Software version Mode Nominal Voltage Control Input Start Jumper A30-4977TB1-TB2 TB13A-TB2Fault Codes Parameters Description Mode Motormaster V Program Parameters for Operating ModesPID Maintenance Replacement ModulesReplacement Replacement Part Module Troubleshooting Advanced Scroll Temperature Protection Label 30RAP Unit Cutout CUT-IN SizeTroubleshooting Symptoms Cause RemedyAlarm and Alert Codes T051T110 T153 T197 Alert GENERATED? CCNCSB EMMCompressor Stuck on Failure Alarms Page Appendix a Display Tables SUB-MODE Display Item Description CommentView RUNAppendix a Display Tables StrtVers Pressures Mode and Sub-Mode Directory SUB-MODE Display Item Description Range Comment CoolHead FRZGEN.O SUB-MODE Display Item Description Comment HP.A HP.BEXV.A EXV.BRset Bcst SUB-MODE Display Item Description Comment Time DateDST HOL.LHD.19 HD.30 SUB-MODE Display Item Description Comment SCH.N SCH.LPER.1 PER.2PER.6 PER.7PER.8 Crnt RcrnHist Appendix B CCN Tables CCN Display Tables Aunit General Unit ParametersCCN Display Tables Circaan Circuit a Analog Parameters Description Value Units Point Name ForcibleAppendix B CCN Tables CCN Display Tables Circban Circuit B Analog ParametersCCN Configuration Tables Unit Unit Configuration CCN Configuration Tables OPTIONS1 Options 1 ConfigurationDescription Value Default Units Point Name CCN Display Tables Options Unit ParametersCCN Configuration Tables OPTIONS2 Options 2 Configuration CCN Configuration Tables Schedovr Timed Override SetupCCN Configuration Tables Display Marquee Display Setup CCN Configuration Tables Mmconf Motormaster ConfigurationCCN Service Tables Service Description Value Units Point Name Description Value Point NameCCN Maintenance Tables Alarms Description Version ValueCCN Maintenance Tables PM-PUMP CCN Maintenance Tables Runtest CCN Maintenance Tables Dualchil Appendix C Factory Settings for Pump and Manual Starters SettingAppendix D Optional Bacnet Communications Wiring Optional BACnet Communications WiringAppendix D Optional Bacnet Communications Wiring Table a SW3 Protocol Switch Settings For MS/TPTable B Baud Selection Table DS8 DS7 DS6 DS5 DS4 DS3Table C MS/TP Wiring Recommendations Specification RecommmendationAWG CL2PWiring Specifications Recommended Vendors and Part Numbers RmcorpCMP Table E LED Status Indicators RUN LED Error LED StatusLED Status Control Mode Table G Network Points List108 109 Appendix E Maintenance Summary and LOG Sheets 30RAP Maintenance Interval RequirementsWeekly QuarterlyAppendix E Maintenance Summary and LOG Sheets 30RAP Weekly Maintenance Log30RAP Monthly Maintenance Log Unit Section Action EntryPSI 30RAP Seasonal Shutdown Log 113Copyright 2010 Carrier Corporation START-UP Checklist for 30RAP Liquid Chiller Remove and use for Job File Project InformationII. Preliminary Equipment Check Design InformationIII. Unit Start-Up Start and Operate Machine. Complete the FollowingDual Chiller Control Only Mode RUN Status Record Software VersionsUnit Configuration Settings OPTIONS1 Options ConfigurationSubmode Item Expansion Display Entry OPT1OPTIONS2 Options Configuration CCN CCN Network ConfigurationHP.A Head Pressure Cmp. Delta Configuration HP.B Head Pressure Cmp. Delta ConfigurationEXV.A Circuit a EXV Configuration EXV.B Circuit B EXV ConfigurationMM Motormaster Configuration Settings EXV.BRset Reset Configuration Settings Slct Setpoint and Ramp Load ConfigurationSetpoint SUB-MODE Keypad Display Comment Entry Expansion
Related manuals
Manual 40 pages 58.51 Kb

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.