Carrier 30RAP010-060 specifications CCN Maintenance Tables PM-PUMP

Page 98

APPENDIX B — CCN TABLES (cont)

CCN MAINTENANCE TABLES — PM-PUMP

DESCRIPTION

VALUE

UNITS

POINT NAME

Pump Service Interval

nnnnnn

hours

SI_PUMPS

Pump 1 Service Countdown

nnnnnn

hours

P1_CDOWN

Pump 1 Maintenance Done

Yes/No

 

P1_MAINT

Pump 2 Service Countdown

nnnnnn

hours

P2_CDOWN

Pump 2 Maintenance Done

Yes/No

 

P2_MAINT

Pump 1 Maintenance Date

mm/dd/yy hh:mm

 

PMP1_PM0

Pump 1 Maintenance Date

mm/dd/yy hh:mm

 

PMP1_PM1

Pump 1 Maintenance Date

mm/dd/yy hh:mm

 

PMP1_PM2

Pump 1 Maintenance Date

mm/dd/yy hh:mm

 

PMP1_PM3

Pump 1 Maintenance Date

mm/dd/yy hh:mm

 

PMP1_PM4

Pump 2 Maintenance Date

mm/dd/yy hh:mm

 

PMP2_PM0

Pump 2 Maintenance Date

mm/dd/yy hh:mm

 

PMP2_PM1

Pump 2 Maintenance Date

mm/dd/yy hh:mm

 

PMP2_PM2

Pump 2 Maintenance Date

mm/dd/yy hh:mm

 

PMP2_PM3

Pump 2 Maintenance Date

mm/dd/yy hh:mm

 

PMP2_PM4

CCN MAINTENANCE TABLES — PM-STRN

DESCRIPTION

VALUE

UNITS

POINT NAME

Strainer Srvc Interval

nnnnnn

hours

SI_STRNR

Strainer Srvc Countdown

nnnnnn

hours

ST_CDOWN

Strainer Maint. Done

Yes/No

 

ST_MAINT

Strainer Maint. Date

mm/dd/yy hh:mm

 

STRN_PM0

Strainer Maint. Date

mm/dd/yy hh:mm

 

STRN_PM1

Strainer Maint. Date

mm/dd/yy hh:mm

 

STRN_PM2

Strainer Maint. Date

mm/dd/yy hh:mm

 

STRN_PM3

Strainer Maint. Date

mm/dd/yy hh:mm

 

STRN_PM4

CCN MAINTENANCE TABLES — PM-COIL

DESCRIPTION

VALUE

UNITS

POINT NAME

Coil Cleaning Srvc Inter

nnnnnn

hours

SI_COIL

Coil Service Countdown

nnnnnn

hours

CL_CDOWN

Coil Cleaning Maint.Done

Yes/No

 

CL_MAINT

Coil Cleaning Maint.Date

mm/dd/yy hh:mm

 

COIL_PM0

Coil Cleaning Maint.Date

mm/dd/yy hh:mm

 

COIL_PM1

Coil Cleaning Maint.Date

mm/dd/yy hh:mm

 

COIL_PM2

Coil Cleaning Maint.Date

mm/dd/yy hh:mm

 

COIL_PM3

Coil Cleaning Maint.Date

mm/dd/yy hh:mm

 

COIL_PM4

CCN MAINTENANCE TABLES — TESTMODE

DESCRIPTION

VALUE

 

UNITS

POINT NAME

Service Test Mode

On/Off

 

 

NET_CTRL

Compressor A1 Relay

On/Off

 

 

S_A1_RLY

Compressor A2 Relay

On/Off

 

 

S_A2_RLY

Compressor B1 Relay

On/Off

 

 

S_B1_RLY

Compressor B2 Relay

On/Off

 

 

S_B2_RLY

Fan 1 Relay

On/Off

 

 

S_FAN_1

Fan 2 Relay

On/Off

 

 

S_FAN_2

Cooler Pump Relay 1

On/Off

 

 

S_CLPMP1

Cooler Pump Relay 2

On/Off

 

 

S_CLPMP2

Comp A1 Unload Time

nn

sec

 

S_A1ULTM

Minimum Load Valve Relay

On/Off

 

 

S_MLV

Remote Alarm Relay

On/Off

 

 

S_ALM

EXV % Open

nn

%

 

S_EXV_A

EXV % Open

nn

%

 

S_EXV_B

98

Image 98
Contents Controls, Start-Up, Operation, Service, and Troubleshooting ContentsContents Safety ConsiderationsUnit Sizes GeneralBasic Controls Usage Unit Nominal Capacity TonsAccessory Navigator Display Module Scrolling Marquee Display Menu Structure Mode RUN Service TemperaturesSET Inputs Outputs Configuration Time Operating Alarms TestRun Status Mode and Sub-Mode Directory StrtSUB-MODE Keypad Display SUB-ITEM Comment Entry Expansion VersOuts Service Test Mode and Sub-Mode DirectorySUB-MODE Keypad Display Comment Entry Expansion Test CmpaSet Points Mode and Sub-Mode Directory Temperature Mode and Sub-Mode DirectoryPressure Mode and Sub-Mode Directory Inputs Mode and Sub-Mode Directory Outputs Mode and Sub-Mode DirectoryConfiguration Mode and Sub-Mode Directory SUB-MODE Keypad Display Comment Entry Expansion EXVOPT1 SUB-MODE Keypad Display Comment Entry Expansion UnitSUB-MODE Keypad Display Comment OPT2XXX XXX.X ΔF DST Time Clock Mode and Sub-Mode DirectoryDate Operating Mode and Sub-Mode Directory Alarms Mode and Sub-Mode DirectoryMode Item Expansion Description Operating ModesCarrier Comfort Network CCN Interface ControlsControl Module Communication Status Inputs CCN Communication Bus WiringThermistor Designations Output RelaysCCB AlmrAUX CHCA30-4962 A30-4963A30-4964 Typical Control Box for 30RAP035-060Typical Wiring Schematic, 30RAP018-030 Units Power Wiring Typical Wiring Schematic, 30RAP018-030 Units Control Wiring A30-4966Typical Wiring Schematic, 30RAP035-060 Units Power Wiring 5283Typical Wiring Schematic, 30RAP035-060 Units Control Wiring A30-5284A30-4967 A30-4968Page CEPL130351 Deadband Multiplier 30RAP Unit Size Control Capacity Steps Capacity %A30-4969 Operating Envelope for R-410A Compressor30RAP Unit Size FAN Stages Cooling Set Point SelectA30-4970 Control Occupancy Cooling SET Point Select Clsp Type State Optional Factory-Installed Hydronic PackControl Methods and Cooling Set Points CCN→PM1E = YES Configuring and Operating Dual Chiller Con Dual Chiller Configuration Master Chiller Example RsetSUB-MODE Keypad Entry Display Item Expansion Comments PartNumber Dual Chiller Configuration Slave Chiller Example Rset Slave CompleteTo 20 mA Reset Menu Configuration of 4 to 20 mA Cooling Set Point ControlMode Keypad SUB Display Configuring Outdoor Air and Space Temperature ResetConfiguring Return Temperature Reset RED LED Entry ModeOutdoor-Air Temperature Reset To 20-mA Demand Limiting PRE-START-UP Configuring Demand LimitItem Expansion Comment Entry Configuration System Check30RAP Minimum Cooler Flow Maximum Cooler Flow Size START-UP and OperationA30-4978 Operation Sequence Temperature Limits for Standard 30RAP UnitsOperating Limitations Unit Size 30RAEXV Steps ServiceElectronic Components Unit Size 30RAP EXV StepsA30-4971 Electronic Expansion Valve DetailsCooler Compressor Replacement Refer to FigUnit Torque Specification A30-4972Oil Charge Check Refrigerant Feed ComponentsLWT A30-4973A30-4974 Unit Cutout CUT-IN Factory Settings, High-Pressure Switch FixedCheck Unit Safeties Thermistor Well Temp Voltage Resistance Drop 100,260 143 86K Thermistor vs Resistance DTT DropA30-4976 A30-4975A30-499 AccsyP50 Fault History Last 8 faults P51 Software version TB1-TB2 Mode Nominal Voltage Control Input Start JumperA30-4977 TB13A-TB2Fault Codes PID Parameters Description ModeMotormaster V Program Parameters for Operating Modes Replacement Replacement Part Module MaintenanceReplacement Modules Troubleshooting Advanced Scroll Temperature Protection Label 30RAP Unit Cutout CUT-IN SizeTroubleshooting Symptoms Cause RemedyAlarm and Alert Codes T051T110 T153 T197 CSB Alert GENERATED?CCN EMMCompressor Stuck on Failure Alarms Page View Appendix a Display TablesSUB-MODE Display Item Description Comment RUNVers Appendix a Display TablesStrt Pressures Mode and Sub-Mode Directory Head SUB-MODE Display Item Description Range CommentCool FRZGEN.O SUB-MODE Display Item Description Comment HP.A HP.BEXV.A EXV.BRset Bcst DST SUB-MODE Display Item Description Comment TimeDate HOL.LHD.19 HD.30 PER.1 SUB-MODE Display Item Description Comment SCH.NSCH.L PER.2PER.8 PER.6PER.7 Hist CrntRcrn CCN Display Tables Circaan Circuit a Analog Parameters Appendix B CCN TablesCCN Display Tables Aunit General Unit Parameters Description Value Units Point Name ForcibleAppendix B CCN Tables CCN Display Tables Circban Circuit B Analog ParametersDescription Value Default Units Point Name CCN Configuration Tables Unit Unit ConfigurationCCN Configuration Tables OPTIONS1 Options 1 Configuration CCN Display Tables Options Unit ParametersCCN Configuration Tables OPTIONS2 Options 2 Configuration CCN Configuration Tables Schedovr Timed Override SetupCCN Configuration Tables Display Marquee Display Setup CCN Configuration Tables Mmconf Motormaster ConfigurationCCN Service Tables Service Description Value Units Point Name Description Value Point NameCCN Maintenance Tables Alarms Description Version ValueCCN Maintenance Tables PM-PUMP CCN Maintenance Tables Runtest CCN Maintenance Tables Dualchil Appendix C Factory Settings for Pump and Manual Starters SettingAppendix D Optional Bacnet Communications Wiring Optional BACnet Communications WiringTable B Baud Selection Table Appendix D Optional Bacnet Communications WiringTable a SW3 Protocol Switch Settings For MS/TP DS8 DS7 DS6 DS5 DS4 DS3AWG Table C MS/TP Wiring RecommendationsSpecification Recommmendation CL2PCMP Wiring Specifications Recommended Vendors and Part NumbersRmcorp LED Status Table E LED Status IndicatorsRUN LED Error LED Status Control Mode Table G Network Points List108 109 Weekly Appendix E Maintenance Summary and LOG Sheets30RAP Maintenance Interval Requirements QuarterlyAppendix E Maintenance Summary and LOG Sheets 30RAP Weekly Maintenance LogPSI 30RAP Monthly Maintenance LogUnit Section Action Entry 30RAP Seasonal Shutdown Log 113Copyright 2010 Carrier Corporation II. Preliminary Equipment Check START-UP Checklist for 30RAP Liquid ChillerRemove and use for Job File Project Information Design InformationIII. Unit Start-Up Start and Operate Machine. Complete the FollowingDual Chiller Control Only Mode RUN Status Record Software VersionsSubmode Item Expansion Display Entry Unit Configuration SettingsOPTIONS1 Options Configuration OPT1HP.A Head Pressure Cmp. Delta Configuration OPTIONS2 Options ConfigurationCCN CCN Network Configuration HP.B Head Pressure Cmp. Delta ConfigurationMM Motormaster Configuration Settings EXV.A Circuit a EXV ConfigurationEXV.B Circuit B EXV Configuration EXV.BRset Reset Configuration Settings Slct Setpoint and Ramp Load ConfigurationSetpoint SUB-MODE Keypad Display Comment Entry Expansion
Related manuals
Manual 40 pages 58.51 Kb

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.