Carrier 30RAP010-060 specifications START-UP and Operation, A30-4978

Page 45

2.Use the scrolling marquee display to adjust the Cooling Set Point.

3.Fill chilled fluid circuit with clean water (with recom- mended inhibitor added) or other non-corrosive fluid to be cooled. Bleed all air out of the high points of the sys- tem. If chilled water is to be maintained at a temperature below 40 F (4.4 C) or outdoor temperatures are expected to be below 32 F (0° C), a brine of sufficient concentra- tion must be used to prevent freeze-up at anticipated suction temperatures. See Table 28.

4.Check tightness of all electrical connections.

5.Oil should be visible in the compressor sightglass(es). See Fig. 23. An acceptable oil level in the compressors is from 1/8 to 3/8 of sight glass. Adjust the oil level as re- quired. See Oil Charge section on page 50 for Carrier ap- proved oils.

6.Electrical power source must agree with unit nameplate.

7.All condenser fan and factory installed hydronic package pump motors are three phase. Check for proper rotation of condenser fans first BEFORE attempting to start pumps or compressors. To reverse rotation, interchange any two of the main incoming power leads.

8.Be sure system is fully charged with refrigerant (see Check Refrigerant Charge section on this page).

9.If unit is a brine unit, check to ensure proper brine con- centration is used to prevent freezing.

10.Verify proper operation of cooler and hydronic package heaters (if installed). Heaters operate at the same voltage as the main incoming power supply and are single phase. Heater current is approximately 0.4 amps for 460 and 575 v units. Heater current is approximately 0.8 amps for 230 v units.

a30-4978

OIL SIGHTGLASS

START-UP AND OPERATION

NOTE: Refer to Start-Up Checklist on pages CL-1 to CL-10.

Actual Start-UpActual start-up should be done only under supervision of a qualified refrigeration mechanic.

1.Be sure all service valves are open.

2.Using the scrolling marquee display, set leaving-fluid set point (Set PointsCOOLCSP.1). No cooling range adjustment is necessary.

3.Start chilled fluid pump (if not configured for cooler pump control).

4.Turn ENABLE/OFF/REMOTE CONTACT switch to ENABLE position.

5.Allow unit to operate and confirm that everything is func- tioning properly. Check to see that leaving fluid tempera- ture agrees with leaving set point (Set PointsCOOL

CSP.1) or (Set PointsCOOLCSP.2), or if reset is used, with the control point (Run StatusVIEW

CTPT).

6.Check the cooler leaving chilled water temperature to see that it remains well above 32 F (0° C), or the brine freez- ing point if the unit is a medium temperature brine unit.

7.Recheck compressor oil level (see Oil Charge section).

Check Refrigerant Charge — All 30RAP units are shipped with a complete operating charge of R-410A and should be under sufficient pressure to conduct a leak test after installation. If there is no system pressure, admit nitrogen until a pressure is observed and then proceed to test for leaks. After leaks are repaired, the system must be dehydrated.

All refrigerant charging should be done through the ¼-in. Schraeder connection on the liquid line. Do NOT add refriger- ant charge through the low-pressure side of the system. If com- plete charging is required, weigh in the appropriate charge for the circuit as shown on the unit nameplate. If partial charging is required, operate circuit at full load and use an accurate tem- perature sensor on the liquid line as it enters the EXV. Use the Temperatures mode on the scrolling marquee display to show the circuit saturated condensing temperature (Tempera-

turesCIR.ASCT.A) or (TemperaturesCIR.B SCT.B). Charging is most accurate at saturated discharge temperatures of 120 to 125 F (49 to 52 C). Block condenser air- flow as required to reach this temperature range. Add refriger- ant until the system subcooling (SCT.A or SCT.B minus liquid line temperature entering EXV) is approximately 15 to 17 F (–9.4 to –8.3 C). Refrigerant VAPOR only may be added to a circuit through the 1/4-in. suction Schraeder connection on the suction line.

Fig. 23 — Sight Glass Location

Table 28 — Minimum Cooler Flow Rates and Minimum Loop Volume

30RAP

MINIMUM COOLER FLOW

MAXIMUM COOLER FLOW

MINIMUM COOLER FLOW

MAXIMUM COOLER FLOW

SIZE

RATE (gpm)

RATE (gpm)

RATE (l/s)

RATE (l/s)

010

13

50

0.8

3.2

015

17

66

1.1

4.2

018

20

78

1.3

4.9

020

23

91

1.5

5.7

025

28

112

1.8

7.1

030

33

133

2.1

8.4

035

41

164

2.6

10.3

040

47

186

3.0

11.7

045

53

209

3.3

13.2

050

57

228

3.6

14.4

055

63

251

4.0

15.8

060

68

270

4.3

17.0

45

Image 45
Contents Contents Controls, Start-Up, Operation, Service, and TroubleshootingSafety Considerations ContentsBasic Controls Usage GeneralUnit Sizes Unit Nominal Capacity TonsAccessory Navigator Display Module SET Inputs Outputs Configuration Time Operating Alarms Mode RUN Service TemperaturesScrolling Marquee Display Menu Structure TestStrt Run Status Mode and Sub-Mode DirectoryVers SUB-MODE Keypad Display SUB-ITEM Comment Entry ExpansionSUB-MODE Keypad Display Comment Entry Expansion Test Service Test Mode and Sub-Mode DirectoryOuts CmpaTemperature Mode and Sub-Mode Directory Pressure Mode and Sub-Mode DirectorySet Points Mode and Sub-Mode Directory Outputs Mode and Sub-Mode Directory Inputs Mode and Sub-Mode DirectorySUB-MODE Keypad Display Comment Entry Expansion EXV Configuration Mode and Sub-Mode DirectorySUB-MODE Keypad Display Comment Entry Expansion Unit OPT1OPT2 SUB-MODE Keypad Display CommentXXX XXX.X ΔF Time Clock Mode and Sub-Mode Directory DateDST Alarms Mode and Sub-Mode Directory Operating Mode and Sub-Mode DirectoryOperating Modes Mode Item Expansion DescriptionControls Control Module CommunicationCarrier Comfort Network CCN Interface Thermistor Designations CCN Communication Bus WiringStatus Inputs Output RelaysAUX AlmrCCB CHCA30-4963 A30-4962Typical Control Box for 30RAP035-060 A30-4964Typical Wiring Schematic, 30RAP018-030 Units Power Wiring A30-4966 Typical Wiring Schematic, 30RAP018-030 Units Control Wiring5283 Typical Wiring Schematic, 30RAP035-060 Units Power WiringA30-5284 Typical Wiring Schematic, 30RAP035-060 Units Control WiringA30-4968 A30-4967Page CEPL130351 30RAP Unit Size Control Capacity Steps Capacity % Deadband MultiplierOperating Envelope for R-410A Compressor A30-4969Cooling Set Point Select A30-497030RAP Unit Size FAN Stages Control Methods and Cooling Set Points Optional Factory-Installed Hydronic PackControl Occupancy Cooling SET Point Select Clsp Type State CCN→PM1E = YES Configuring and Operating Dual Chiller Con Rset Dual Chiller Configuration Master Chiller ExamplePart NumberSUB-MODE Keypad Entry Display Item Expansion Comments Rset Slave Complete Dual Chiller Configuration Slave Chiller ExampleMenu Configuration of 4 to 20 mA Cooling Set Point Control To 20 mA ResetConfiguring Return Temperature Reset Configuring Outdoor Air and Space Temperature ResetMode Keypad SUB Display RED LED Entry ModeOutdoor-Air Temperature Reset To 20-mA Demand Limiting Item Expansion Comment Entry Configuration Configuring Demand LimitPRE-START-UP System CheckSTART-UP and Operation A30-497830RAP Minimum Cooler Flow Maximum Cooler Flow Size Operating Limitations Temperature Limits for Standard 30RAP UnitsOperation Sequence Unit Size 30RAElectronic Components ServiceEXV Steps Unit Size 30RAP EXV StepsElectronic Expansion Valve Details A30-4971Unit Torque Specification Compressor Replacement Refer to FigCooler A30-4972Check Refrigerant Feed Components Oil ChargeA30-4973 A30-4974LWT Factory Settings, High-Pressure Switch Fixed Check Unit SafetiesUnit Cutout CUT-IN Thermistor Well Temp Voltage Resistance Drop 100,260 143 Drop 86K Thermistor vs Resistance DTTA30-499 A30-4975A30-4976 AccsyP50 Fault History Last 8 faults P51 Software version A30-4977 Mode Nominal Voltage Control Input Start JumperTB1-TB2 TB13A-TB2Fault Codes Parameters Description Mode Motormaster V Program Parameters for Operating ModesPID Maintenance Replacement ModulesReplacement Replacement Part Module Troubleshooting 30RAP Unit Cutout CUT-IN Size Advanced Scroll Temperature Protection LabelSymptoms Cause Remedy TroubleshootingT051 Alarm and Alert CodesT110 T153 T197 CCN Alert GENERATED?CSB EMMCompressor Stuck on Failure Alarms Page SUB-MODE Display Item Description Comment Appendix a Display TablesView RUNAppendix a Display Tables StrtVers Pressures Mode and Sub-Mode Directory Cool SUB-MODE Display Item Description Range CommentHead FRZGEN.O SUB-MODE Display Item Description Comment HP.B HP.AEXV.B EXV.ARset Bcst Date SUB-MODE Display Item Description Comment TimeDST HOL.LHD.19 HD.30 SCH.L SUB-MODE Display Item Description Comment SCH.NPER.1 PER.2PER.6 PER.7PER.8 Crnt RcrnHist CCN Display Tables Aunit General Unit Parameters Appendix B CCN TablesCCN Display Tables Circaan Circuit a Analog Parameters Description Value Units Point Name ForcibleCCN Display Tables Circban Circuit B Analog Parameters Appendix B CCN TablesCCN Configuration Tables OPTIONS1 Options 1 Configuration CCN Configuration Tables Unit Unit ConfigurationDescription Value Default Units Point Name CCN Display Tables Options Unit ParametersCCN Configuration Tables Schedovr Timed Override Setup CCN Configuration Tables OPTIONS2 Options 2 ConfigurationCCN Configuration Tables Mmconf Motormaster Configuration CCN Configuration Tables Display Marquee Display SetupCCN Service Tables Service Description Value Point Name Description Value Units Point NameDescription Version Value CCN Maintenance Tables AlarmsCCN Maintenance Tables PM-PUMP CCN Maintenance Tables Runtest CCN Maintenance Tables Dualchil Setting Appendix C Factory Settings for Pump and Manual StartersOptional BACnet Communications Wiring Appendix D Optional Bacnet Communications WiringTable a SW3 Protocol Switch Settings For MS/TP Appendix D Optional Bacnet Communications WiringTable B Baud Selection Table DS8 DS7 DS6 DS5 DS4 DS3Specification Recommmendation Table C MS/TP Wiring RecommendationsAWG CL2PWiring Specifications Recommended Vendors and Part Numbers RmcorpCMP Table E LED Status Indicators RUN LED Error LED StatusLED Status Table G Network Points List Control Mode108 109 30RAP Maintenance Interval Requirements Appendix E Maintenance Summary and LOG SheetsWeekly Quarterly30RAP Weekly Maintenance Log Appendix E Maintenance Summary and LOG Sheets30RAP Monthly Maintenance Log Unit Section Action EntryPSI 113 30RAP Seasonal Shutdown LogCopyright 2010 Carrier Corporation Remove and use for Job File Project Information START-UP Checklist for 30RAP Liquid ChillerII. Preliminary Equipment Check Design InformationStart and Operate Machine. Complete the Following III. Unit Start-UpDual Chiller Control Only Record Software Versions Mode RUN StatusOPTIONS1 Options Configuration Unit Configuration SettingsSubmode Item Expansion Display Entry OPT1CCN CCN Network Configuration OPTIONS2 Options ConfigurationHP.A Head Pressure Cmp. Delta Configuration HP.B Head Pressure Cmp. Delta ConfigurationEXV.B Circuit B EXV Configuration EXV.A Circuit a EXV ConfigurationMM Motormaster Configuration Settings EXV.BSlct Setpoint and Ramp Load Configuration Rset Reset Configuration SettingsSetpoint Entry Expansion SUB-MODE Keypad Display Comment
Related manuals
Manual 40 pages 58.51 Kb

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.