APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)

Table G — Network Points List (cont)

POINT DESCRIPTION

POINT NAME

READ/

UNITS

DEFAULT

RANGE

BACNET

BACNET

 

 

WRITE

 

VALUE

 

OBJECT ID

OBJECT NAME

Cooling Setpoint 2

CSP2

R/W

°F

44.0

-20 - 70

AV:54

csp2_1

CSM Controlling Chiller

MODE_1

R

 

 

 

BV:30

mode_1_1

Demand Level 1

 

R

%

 

 

AV:75

dmv_lvl_1_perct_1

Demand Level 2

 

R

%

 

 

AV:76

dmv_lvl_2_perct_1

Demand Level 3

 

R

%

 

 

AV:77

dmv_lvl_3_perct_1

Demand Limit Switch 1

DMD_SW1

R

 

 

 

BV:25

dmd_sw1_1

Demand Limit Switch 2

DMD_SW2

R

 

 

 

BV:26

dmd_sw2_1

Demand/Sound Limited

MODE_15

R

 

 

 

BV:41

mode_15_1

Discharge Gas Temp

DISGAS

R

°F

 

 

AV:15

disgas_1

Discharge Pressure

DP_A

R

psig

 

 

AV:13

dp_a_1

Discharge Pressure

DP_B

R

psig

 

 

AV:23

dp_b_1

Dual Setpoint

MODE_13

R

 

 

 

BV:39

mode_13_1

Dual Setpoint Switch

DUAL_IN

R

 

 

 

BV:29

dual_in_1

Element Comm Status

 

R

 

 

 

BV:2999

element_stat_1

Element Communications

 

R

 

 

 

BV:58

comm_lost_alm_1

Alarm

 

 

 

 

 

 

 

 

 

 

 

Emergency Stop

EMSTOP

R/W

 

Enabled

Enabled/Emstop

BV:6

emstop_1

Entering Fluid Temp

EWT

R

°F

 

 

AV:6

ewt_1

EXV % Open

EXV_A

R

%

 

 

AV:18

exv_a_1

EXV % Open

EXV_B

R

%

 

 

AV:27

exv_b_1

Fan 1 Relay

FAN_1

R

 

 

 

BV:22

fan_1_1

Fan 2 Relay

FAN_2

R

 

 

 

BV:23

fan_2_1

Head Setpoint

HSP

R

°F

 

 

AV:29

hsp_1

Heat Request

HEAT_REQ

R

 

 

 

BV:28

heat_req_1

High SCT Circuit A

MODE_21

R

 

 

 

BV:47

mode_21_1

High SCT Circuit B

MODE_22

R

 

 

 

BV:48

mode_22_1

High Temperature Cooling

MODE_18

R

 

 

 

BV:44

mode_18_1

Ice Done

ICE_DONE

R

 

 

 

BV:27

ice_done_1

Ice Setpoint

CSP3

R/W

°F

32.0

-20 - 32

AV:55

csp3_1

Lead/Lag Circuit Select

 

 

 

 

1 = Automatic

 

 

LEAD_TYP

R/W

 

1

2 = Circuit A Leads

AV:43

lead_typ_1

 

 

 

 

 

3 = Circuit B Leads

 

 

Lead/Lag Circuit Select

LEAD_TYP

R

 

 

 

MSV:6

lead_typ_msv_1

Lead/Lag Leaving Fluid

DUAL_LWT

R

°F

 

 

AV:32

dual_lwt_1

Leadpump

LEADPUMP

R

 

 

 

MSV:9

leadpump_msv_1

Leaving Fluid Temp - Prime

LWT

R

°F

 

 

AV:7

lwt_1

Variable

 

 

 

 

 

 

 

 

 

Loading Sequence Select

SEQ_TYPE

R

 

 

 

AV:74

seq_type_1

Local Schedule

 

R

 

 

 

BV:1

schedule_1

Low Cooler Suction Temp A

MODE_7

R

 

 

 

BV:35

mode_7_1

Low Cooler Suction Temp B

MODE_8

R

 

 

 

BV:36

mode_8_1

Low Sound Active

LSACTIVE

R

 

 

 

BV:2

lsactive_1

Low Sound Mode

MODE_25

R

 

 

 

BV:51

mode_25_1

Low Temperature Cooling

MODE_17

R

 

 

 

BV:43

mode_17_1

Machine Operating Hours

HR_MACH

R

hr

 

 

AV:57

hr_mach_1

Machine Starts

CY_MACH

R

 

 

 

AV:58

cy_mach_1

Making ICE

MODE_19

R

 

 

 

BV:45

mode_19_1

Master/Slave Control

MODE_3

R

 

 

 

BV:32

mode_3_1

Minimum Comp. On Time

MODE_23

R

 

 

 

BV:49

mode_23_1

Minimum Load Valve Relay

MLV_RLY

R

 

 

 

BV:15

mlv_rly_1

Minimum OFF Time Active

MODE_10

R

 

 

 

BV:38

mode_10_1

Minutes Off Time

DELAY

R/W

min

0

0 - 15

AV:42

delay_1

Occupied

OCC

R

 

 

 

BV:3

occ_1

Outside Air Temperature

OAT

R

°F

 

 

AV:34

oat_1

Override Modes in Effect

MODE

R

 

 

 

BV:5

mode_1

Percent Available Cap.

CAP_A

R

%

 

 

AV:12

capa_a_1

Percent Available Cap.

CAPB_A

R

%

 

 

AV:22

capb_a_1

LEGEND

RRead

W — Write

108

Image 108
Contents Controls, Start-Up, Operation, Service, and Troubleshooting ContentsContents Safety ConsiderationsGeneral Basic Controls UsageUnit Sizes Unit Nominal Capacity TonsAccessory Navigator Display Module Mode RUN Service Temperatures SET Inputs Outputs Configuration Time Operating AlarmsScrolling Marquee Display Menu Structure TestRun Status Mode and Sub-Mode Directory StrtSUB-MODE Keypad Display SUB-ITEM Comment Entry Expansion VersService Test Mode and Sub-Mode Directory SUB-MODE Keypad Display Comment Entry Expansion TestOuts CmpaTemperature Mode and Sub-Mode Directory Pressure Mode and Sub-Mode DirectorySet Points Mode and Sub-Mode Directory Inputs Mode and Sub-Mode Directory Outputs Mode and Sub-Mode DirectoryConfiguration Mode and Sub-Mode Directory SUB-MODE Keypad Display Comment Entry Expansion EXVOPT1 SUB-MODE Keypad Display Comment Entry Expansion UnitSUB-MODE Keypad Display Comment OPT2XXX XXX.X ΔF Time Clock Mode and Sub-Mode Directory DateDST Operating Mode and Sub-Mode Directory Alarms Mode and Sub-Mode DirectoryMode Item Expansion Description Operating ModesControls Control Module CommunicationCarrier Comfort Network CCN Interface CCN Communication Bus Wiring Thermistor DesignationsStatus Inputs Output RelaysAlmr AUXCCB CHCA30-4962 A30-4963A30-4964 Typical Control Box for 30RAP035-060Typical Wiring Schematic, 30RAP018-030 Units Power Wiring Typical Wiring Schematic, 30RAP018-030 Units Control Wiring A30-4966Typical Wiring Schematic, 30RAP035-060 Units Power Wiring 5283Typical Wiring Schematic, 30RAP035-060 Units Control Wiring A30-5284A30-4967 A30-4968Page CEPL130351 Deadband Multiplier 30RAP Unit Size Control Capacity Steps Capacity %A30-4969 Operating Envelope for R-410A CompressorCooling Set Point Select A30-497030RAP Unit Size FAN Stages Optional Factory-Installed Hydronic Pack Control Methods and Cooling Set PointsControl Occupancy Cooling SET Point Select Clsp Type State CCN→PM1E = YES Configuring and Operating Dual Chiller Con Dual Chiller Configuration Master Chiller Example RsetPart NumberSUB-MODE Keypad Entry Display Item Expansion Comments Dual Chiller Configuration Slave Chiller Example Rset Slave CompleteTo 20 mA Reset Menu Configuration of 4 to 20 mA Cooling Set Point ControlConfiguring Outdoor Air and Space Temperature Reset Configuring Return Temperature ResetMode Keypad SUB Display RED LED Entry ModeOutdoor-Air Temperature Reset To 20-mA Demand Limiting Configuring Demand Limit Item Expansion Comment Entry ConfigurationPRE-START-UP System CheckSTART-UP and Operation A30-497830RAP Minimum Cooler Flow Maximum Cooler Flow Size Temperature Limits for Standard 30RAP Units Operating LimitationsOperation Sequence Unit Size 30RAService Electronic ComponentsEXV Steps Unit Size 30RAP EXV StepsA30-4971 Electronic Expansion Valve DetailsCompressor Replacement Refer to Fig Unit Torque SpecificationCooler A30-4972Oil Charge Check Refrigerant Feed ComponentsA30-4973 A30-4974LWT Factory Settings, High-Pressure Switch Fixed Check Unit SafetiesUnit Cutout CUT-IN Thermistor Well Temp Voltage Resistance Drop 100,260 143 86K Thermistor vs Resistance DTT DropA30-4975 A30-499A30-4976 AccsyP50 Fault History Last 8 faults P51 Software version Mode Nominal Voltage Control Input Start Jumper A30-4977TB1-TB2 TB13A-TB2Fault Codes Parameters Description Mode Motormaster V Program Parameters for Operating ModesPID Maintenance Replacement ModulesReplacement Replacement Part Module Troubleshooting Advanced Scroll Temperature Protection Label 30RAP Unit Cutout CUT-IN SizeTroubleshooting Symptoms Cause RemedyAlarm and Alert Codes T051T110 T153 T197 Alert GENERATED? CCNCSB EMMCompressor Stuck on Failure Alarms Page Appendix a Display Tables SUB-MODE Display Item Description CommentView RUNAppendix a Display Tables StrtVers Pressures Mode and Sub-Mode Directory SUB-MODE Display Item Description Range Comment CoolHead FRZGEN.O SUB-MODE Display Item Description Comment HP.A HP.BEXV.A EXV.BRset Bcst SUB-MODE Display Item Description Comment Time DateDST HOL.LHD.19 HD.30 SUB-MODE Display Item Description Comment SCH.N SCH.LPER.1 PER.2PER.6 PER.7PER.8 Crnt RcrnHist Appendix B CCN Tables CCN Display Tables Aunit General Unit ParametersCCN Display Tables Circaan Circuit a Analog Parameters Description Value Units Point Name ForcibleAppendix B CCN Tables CCN Display Tables Circban Circuit B Analog ParametersCCN Configuration Tables Unit Unit Configuration CCN Configuration Tables OPTIONS1 Options 1 ConfigurationDescription Value Default Units Point Name CCN Display Tables Options Unit ParametersCCN Configuration Tables OPTIONS2 Options 2 Configuration CCN Configuration Tables Schedovr Timed Override SetupCCN Configuration Tables Display Marquee Display Setup CCN Configuration Tables Mmconf Motormaster ConfigurationCCN Service Tables Service Description Value Units Point Name Description Value Point NameCCN Maintenance Tables Alarms Description Version ValueCCN Maintenance Tables PM-PUMP CCN Maintenance Tables Runtest CCN Maintenance Tables Dualchil Appendix C Factory Settings for Pump and Manual Starters SettingAppendix D Optional Bacnet Communications Wiring Optional BACnet Communications WiringAppendix D Optional Bacnet Communications Wiring Table a SW3 Protocol Switch Settings For MS/TPTable B Baud Selection Table DS8 DS7 DS6 DS5 DS4 DS3Table C MS/TP Wiring Recommendations Specification RecommmendationAWG CL2PWiring Specifications Recommended Vendors and Part Numbers RmcorpCMP Table E LED Status Indicators RUN LED Error LED StatusLED Status Control Mode Table G Network Points List108 109 Appendix E Maintenance Summary and LOG Sheets 30RAP Maintenance Interval RequirementsWeekly QuarterlyAppendix E Maintenance Summary and LOG Sheets 30RAP Weekly Maintenance Log30RAP Monthly Maintenance Log Unit Section Action EntryPSI 30RAP Seasonal Shutdown Log 113Copyright 2010 Carrier Corporation START-UP Checklist for 30RAP Liquid Chiller Remove and use for Job File Project InformationII. Preliminary Equipment Check Design InformationIII. Unit Start-Up Start and Operate Machine. Complete the FollowingDual Chiller Control Only Mode RUN Status Record Software VersionsUnit Configuration Settings OPTIONS1 Options ConfigurationSubmode Item Expansion Display Entry OPT1OPTIONS2 Options Configuration CCN CCN Network ConfigurationHP.A Head Pressure Cmp. Delta Configuration HP.B Head Pressure Cmp. Delta ConfigurationEXV.A Circuit a EXV Configuration EXV.B Circuit B EXV ConfigurationMM Motormaster Configuration Settings EXV.BRset Reset Configuration Settings Slct Setpoint and Ramp Load ConfigurationSetpoint SUB-MODE Keypad Display Comment Entry Expansion
Related manuals
Manual 40 pages 58.51 Kb

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.