Table 35 — 10K Thermistor Temperature (°F) vs. Resistance/Voltage Drop

(For SPT)

TEMP

VOLTAGE

RESISTANCE

 

TEMP

VOLTAGE

RESISTANCE

 

TEMP

VOLTAGE

RESISTANCE

DROP

 

DROP

 

DROP

(F)

(Ohms)

 

(F)

(Ohms)

 

(F)

(Ohms)

(V)

 

(V)

 

(V)

 

 

 

 

 

 

 

 

–25

4.758

196,453

 

61

2.994

14,925

 

147

0.890

2,166

–24

4.750

189,692

62

2.963

14,549

148

0.876

2,124

–23

4.741

183,300

63

2.932

14,180

149

0.862

2,083

–22

4.733

177,000

64

2.901

13,824

150

0.848

2,043

–21

4.724

171,079

65

2.870

13,478

151

0.835

2,003

–20

4.715

165,238

66

2.839

13,139

152

0.821

1,966

–19

4.705

159,717

67

2.808

12,814

153

0.808

1,928

–18

4.696

154,344

68

2.777

12,493

154

0.795

1,891

–17

4.686

149,194

69

2.746

12,187

155

0.782

1,855

–16

4.676

144,250

70

2.715

11,884

156

0.770

1,820

–15

4.665

139,443

71

2.684

11,593

157

0.758

1,786

–14

4.655

134,891

72

2.653

11,308

158

0.745

1,752

–13

4.644

130,402

73

2.622

11,031

159

0.733

1,719

–12

4.633

126,183

74

2.592

10,764

160

0.722

1,687

–11

4.621

122,018

75

2.561

10,501

161

0.710

1,656

–10

4.609

118,076

76

2.530

10,249

162

0.699

1,625

–9

4.597

114,236

77

2.500

10,000

163

0.687

1,594

–8

4.585

110,549

78

2.470

9,762

164

0.676

1,565

–7

4.572

107,006

79

2.439

9,526

165

0.666

1,536

–6

4.560

103,558

80

2.409

9,300

166

0.655

1,508

–5

4.546

100,287

81

2.379

9,078

167

0.645

1,480

–4

4.533

97,060

82

2.349

8,862

168

0.634

1,453

–3

4.519

94,020

83

2.319

8,653

169

0.624

1,426

–2

4.505

91,019

84

2.290

8,448

170

0.614

1,400

–1

4.490

88,171

85

2.260

8,251

171

0.604

1,375

0

4.476

85,396

86

2.231

8,056

172

0.595

1,350

1

4.461

82,729

87

2.202

7,869

173

0.585

1,326

2

4.445

80,162

88

2.173

7,685

174

0.576

1,302

3

4.429

77,662

89

2.144

7,507

175

0.567

1,278

4

4.413

75,286

90

2.115

7,333

176

0.558

1,255

5

4.397

72,940

91

2.087

7,165

177

0.549

1,233

6

4.380

70,727

92

2.059

6,999

178

0.540

1,211

7

4.363

68,542

93

2.030

6,838

179

0.532

1,190

8

4.346

66,465

94

2.003

6,683

180

0.523

1,169

9

4.328

64,439

95

1.975

6,530

181

0.515

1,148

10

4.310

62,491

96

1.948

6,383

182

0.507

1,128

11

4.292

60,612

97

1.921

6,238

183

0.499

1,108

12

4.273

58,781

98

1.894

6,098

184

0.491

1,089

13

4.254

57,039

99

1.867

5,961

185

0.483

1,070

14

4.235

55,319

100

1.841

5,827

186

0.476

1,052

15

4.215

53,693

101

1.815

5,698

187

0.468

1,033

16

4.195

52,086

102

1.789

5,571

188

0.461

1,016

17

4.174

50,557

103

1.763

5,449

189

0.454

998

18

4.153

49,065

104

1.738

5,327

190

0.447

981

19

4.132

47,627

105

1.713

5,210

191

0.440

964

20

4.111

46,240

106

1.688

5,095

192

0.433

947

21

4.089

44,888

107

1.663

4,984

193

0.426

931

22

4.067

43,598

108

1.639

4,876

194

0.419

915

23

4.044

42,324

109

1.615

4,769

195

0.413

900

24

4.021

41,118

110

1.591

4,666

196

0.407

885

25

3.998

39,926

111

1.567

4,564

197

0.400

870

26

3.975

38,790

112

1.544

4,467

198

0.394

855

27

3.951

37,681

113

1.521

4,370

199

0.388

841

28

3.927

36,610

114

1.498

4,277

200

0.382

827

29

3.903

35,577

115

1.475

4,185

201

0.376

814

30

3.878

34,569

116

1.453

4,096

202

0.370

800

31

3.853

33,606

117

1.431

4,008

203

0.365

787

32

3.828

32,654

118

1.409

3,923

204

0.359

774

33

3.802

31,752

119

1.387

3,840

205

0.354

762

34

3.776

30,860

120

1.366

3,759

206

0.349

749

35

3.750

30,009

121

1.345

3,681

207

0.343

737

36

3.723

29,177

122

1.324

3,603

208

0.338

725

37

3.697

28,373

123

1.304

3,529

209

0.333

714

38

3.670

27,597

124

1.284

3,455

210

0.328

702

39

3.654

26,838

125

1.264

3,383

211

0.323

691

40

3.615

26,113

126

1.244

3,313

212

0.318

680

41

3.587

25,396

127

1.225

3,244

213

0.314

670

42

3.559

24,715

128

1.206

3,178

214

0.309

659

43

3.531

24,042

129

1.187

3,112

215

0.305

649

44

3.503

23,399

130

1.168

3,049

216

0.300

639

45

3.474

22,770

131

1.150

2,986

217

0.296

629

46

3.445

22,161

132

1.132

2,926

218

0.292

620

47

3.416

21,573

133

1.114

2,866

219

0.288

610

48

3.387

20,998

134

1.096

2,809

220

0.284

601

49

3.357

20,447

135

1.079

2,752

221

0.279

592

50

3.328

19,903

136

1.062

2,697

222

0.275

583

51

3.298

19,386

137

1.045

2,643

223

0.272

574

52

3.268

18,874

138

1.028

2,590

224

0.268

566

53

3.238

18,384

139

1.012

2,539

225

0.264

557

54

3.208

17,904

140

0.996

2,488

 

 

 

 

55

3.178

17,441

141

0.980

2,439

 

 

 

 

56

3.147

16,991

142

0.965

2,391

 

 

 

 

57

3.117

16,552

143

0.949

2,343

 

 

 

 

58

3.086

16,131

144

0.934

2,297

 

 

 

 

59

3.056

15,714

145

0.919

2,253

 

 

 

 

60

3.025

15,317

 

146

0.905

2,209

 

 

 

 

56

Image 56
Contents Controls, Start-Up, Operation, Service, and Troubleshooting ContentsContents Safety ConsiderationsGeneral Basic Controls UsageUnit Sizes Unit Nominal Capacity TonsAccessory Navigator Display Module Mode RUN Service Temperatures SET Inputs Outputs Configuration Time Operating AlarmsScrolling Marquee Display Menu Structure TestRun Status Mode and Sub-Mode Directory StrtSUB-MODE Keypad Display SUB-ITEM Comment Entry Expansion VersService Test Mode and Sub-Mode Directory SUB-MODE Keypad Display Comment Entry Expansion TestOuts CmpaSet Points Mode and Sub-Mode Directory Temperature Mode and Sub-Mode DirectoryPressure Mode and Sub-Mode Directory Inputs Mode and Sub-Mode Directory Outputs Mode and Sub-Mode DirectoryConfiguration Mode and Sub-Mode Directory SUB-MODE Keypad Display Comment Entry Expansion EXVOPT1 SUB-MODE Keypad Display Comment Entry Expansion UnitSUB-MODE Keypad Display Comment OPT2XXX XXX.X ΔF DST Time Clock Mode and Sub-Mode DirectoryDate Operating Mode and Sub-Mode Directory Alarms Mode and Sub-Mode DirectoryMode Item Expansion Description Operating ModesCarrier Comfort Network CCN Interface ControlsControl Module Communication CCN Communication Bus Wiring Thermistor DesignationsStatus Inputs Output RelaysAlmr AUXCCB CHCA30-4962 A30-4963A30-4964 Typical Control Box for 30RAP035-060Typical Wiring Schematic, 30RAP018-030 Units Power Wiring Typical Wiring Schematic, 30RAP018-030 Units Control Wiring A30-4966Typical Wiring Schematic, 30RAP035-060 Units Power Wiring 5283Typical Wiring Schematic, 30RAP035-060 Units Control Wiring A30-5284A30-4967 A30-4968Page CEPL130351 Deadband Multiplier 30RAP Unit Size Control Capacity Steps Capacity %A30-4969 Operating Envelope for R-410A Compressor30RAP Unit Size FAN Stages Cooling Set Point SelectA30-4970 Optional Factory-Installed Hydronic Pack Control Methods and Cooling Set PointsControl Occupancy Cooling SET Point Select Clsp Type State CCN→PM1E = YES Configuring and Operating Dual Chiller Con Dual Chiller Configuration Master Chiller Example RsetSUB-MODE Keypad Entry Display Item Expansion Comments PartNumber Dual Chiller Configuration Slave Chiller Example Rset Slave CompleteTo 20 mA Reset Menu Configuration of 4 to 20 mA Cooling Set Point ControlConfiguring Outdoor Air and Space Temperature Reset Configuring Return Temperature ResetMode Keypad SUB Display RED LED Entry ModeOutdoor-Air Temperature Reset To 20-mA Demand Limiting Configuring Demand Limit Item Expansion Comment Entry ConfigurationPRE-START-UP System Check30RAP Minimum Cooler Flow Maximum Cooler Flow Size START-UP and OperationA30-4978 Temperature Limits for Standard 30RAP Units Operating LimitationsOperation Sequence Unit Size 30RAService Electronic ComponentsEXV Steps Unit Size 30RAP EXV StepsA30-4971 Electronic Expansion Valve DetailsCompressor Replacement Refer to Fig Unit Torque SpecificationCooler A30-4972Oil Charge Check Refrigerant Feed ComponentsLWT A30-4973A30-4974 Unit Cutout CUT-IN Factory Settings, High-Pressure Switch FixedCheck Unit Safeties Thermistor Well Temp Voltage Resistance Drop 100,260 143 86K Thermistor vs Resistance DTT DropA30-4975 A30-499A30-4976 AccsyP50 Fault History Last 8 faults P51 Software version Mode Nominal Voltage Control Input Start Jumper A30-4977TB1-TB2 TB13A-TB2Fault Codes PID Parameters Description ModeMotormaster V Program Parameters for Operating Modes Replacement Replacement Part Module MaintenanceReplacement Modules Troubleshooting Advanced Scroll Temperature Protection Label 30RAP Unit Cutout CUT-IN SizeTroubleshooting Symptoms Cause RemedyAlarm and Alert Codes T051T110 T153 T197 Alert GENERATED? CCNCSB EMMCompressor Stuck on Failure Alarms Page Appendix a Display Tables SUB-MODE Display Item Description CommentView RUNVers Appendix a Display TablesStrt Pressures Mode and Sub-Mode Directory SUB-MODE Display Item Description Range Comment CoolHead FRZGEN.O SUB-MODE Display Item Description Comment HP.A HP.BEXV.A EXV.BRset Bcst SUB-MODE Display Item Description Comment Time DateDST HOL.LHD.19 HD.30 SUB-MODE Display Item Description Comment SCH.N SCH.LPER.1 PER.2PER.8 PER.6PER.7 Hist CrntRcrn Appendix B CCN Tables CCN Display Tables Aunit General Unit ParametersCCN Display Tables Circaan Circuit a Analog Parameters Description Value Units Point Name ForcibleAppendix B CCN Tables CCN Display Tables Circban Circuit B Analog ParametersCCN Configuration Tables Unit Unit Configuration CCN Configuration Tables OPTIONS1 Options 1 ConfigurationDescription Value Default Units Point Name CCN Display Tables Options Unit ParametersCCN Configuration Tables OPTIONS2 Options 2 Configuration CCN Configuration Tables Schedovr Timed Override SetupCCN Configuration Tables Display Marquee Display Setup CCN Configuration Tables Mmconf Motormaster ConfigurationCCN Service Tables Service Description Value Units Point Name Description Value Point NameCCN Maintenance Tables Alarms Description Version ValueCCN Maintenance Tables PM-PUMP CCN Maintenance Tables Runtest CCN Maintenance Tables Dualchil Appendix C Factory Settings for Pump and Manual Starters SettingAppendix D Optional Bacnet Communications Wiring Optional BACnet Communications WiringAppendix D Optional Bacnet Communications Wiring Table a SW3 Protocol Switch Settings For MS/TPTable B Baud Selection Table DS8 DS7 DS6 DS5 DS4 DS3Table C MS/TP Wiring Recommendations Specification RecommmendationAWG CL2PCMP Wiring Specifications Recommended Vendors and Part NumbersRmcorp LED Status Table E LED Status IndicatorsRUN LED Error LED Status Control Mode Table G Network Points List108 109 Appendix E Maintenance Summary and LOG Sheets 30RAP Maintenance Interval RequirementsWeekly QuarterlyAppendix E Maintenance Summary and LOG Sheets 30RAP Weekly Maintenance LogPSI 30RAP Monthly Maintenance LogUnit Section Action Entry 30RAP Seasonal Shutdown Log 113Copyright 2010 Carrier Corporation START-UP Checklist for 30RAP Liquid Chiller Remove and use for Job File Project InformationII. Preliminary Equipment Check Design InformationIII. Unit Start-Up Start and Operate Machine. Complete the FollowingDual Chiller Control Only Mode RUN Status Record Software VersionsUnit Configuration Settings OPTIONS1 Options ConfigurationSubmode Item Expansion Display Entry OPT1OPTIONS2 Options Configuration CCN CCN Network ConfigurationHP.A Head Pressure Cmp. Delta Configuration HP.B Head Pressure Cmp. Delta ConfigurationEXV.A Circuit a EXV Configuration EXV.B Circuit B EXV ConfigurationMM Motormaster Configuration Settings EXV.BRset Reset Configuration Settings Slct Setpoint and Ramp Load ConfigurationSetpoint SUB-MODE Keypad Display Comment Entry Expansion
Related manuals
Manual 40 pages 58.51 Kb

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.