Carrier 30RAP010-060 specifications Optional Factory-Installed Hydronic Pack, Ccn

Page 34

Table 21 — Control Methods and Cooling Set Points

 

CONTROL

OCCUPANCY

 

COOLING SET POINT SELECT (CLSP)

 

 

TYPE

STATE

0

1

2

3

 

(CTRL)

(single)

(dual, switch)

(dual, occ)

(4 to 20 mA)

 

 

0

(switch)

Occupied

ON,CSP1

ON*

ON,CSP1

ON†

Unoccupied

ON,CSP1

ON*

ON,CSP2

ON

 

 

2

(Occupancy)

Occupied

ON,CSP1

ON*

Illegal

ON†

Unoccupied

OFF

OFF

Illegal

OFF

 

 

3

(CCN)

Occupied

ON,CSP1

ON*

ON,CSP1

ON†

Unoccupied

ON,CSP1

ON*

ON,CSP2

ON†

 

 

*Dual set point switch input used. CSP1 used when switch input is open. CSP2 used when switch input is closed. †Cooling set point determined from 4 to 20 mA input to energy management module (EMM) to terminals TB6-3,5.

4 TO 20 mA INPUT — Unit operation is based on an external 4 to 20 mA signal input to the Energy Management Module (EMM).

Low Sound Mode Operation — All models are fac- tory configured with the Low Sound Mode disabled. In the Configuration mode under sub-mode OPT2, items for Low Sound Mode Select (ConfigurationOPT2LS.MD), Low Sound Start Time (ConfigurationOPT2LS.ST), Low Sound End Time (ConfigurationOPT2LS.ND) and Low Sound Capacity Limit (ConfigurationOPT2LS.LT) are factory configured so that the chiller always runs as quietly as possible. This results in operation at increased saturated con- densing temperature. As a result, some models may not be able to achieve rated efficiency. For chiller operation at rated effi- ciency, disable the low sound mode or adjust the low sound mode start and stop times accordingly or set both times to 00:00 for rated efficiency operation 24 hours per day. In addi- tion, the low sound capacity limit can be used to reduce overall chiller capacity, if required, by limiting the maximum to a user- configured percentage.

Heating Operation — The chiller can be used for pump outputs or optional factory-installed hydronic system operation can be utilized for heating applications. The heating mode is activated when the control sees a field-supplied closed switch input to terminal block LVT-19,20. The control locks out cool- ing when the heat relay input is seen. A field-supplied boiler re- lay connection is made using heat relay and alarm relay con- tacts. Factory-installed ‘BOILER’ connections exist in the con- trol panel near LVT for these applications. Alarms and alerts A189 through A202 are active during heating operation.

Service Test (See Table 4) — Both main power and control circuit power must be on.

The Service Test function should be used to verify proper operation of condenser fan(s), compressors, minimum load valve solenoid (if installed), cooler pump(s), EXVs, and re- mote alarm relay. To use the Service Test mode, the Enable/ Off/Remote Contact switch must be in the OFF position. Use the display keys and Table 4 to enter the mode and display TEST. Press ENTER twice so that OFF flashes. Enter the password if required. Use either arrow key to change the TEST value to the ON position and press ENTER . Press ESCAPE and the button to enter the OUTS or COMP sub-mode.

Test the condenser fans, cooler pump(s) and alarm relay by changing the item values from OFF to ON. These discrete outputs are then turned off if there is no keypad activity for 10 minutes. Use the arrow keys to select the desired percentage when testing expansion valves and Motormaster® V controller. When testing compressors, lead compressor must be started first. All compressor outputs can be turned on, but the control will limit the rate by staging one compressor per minute. Com- pressor unloaders and hot gas bypass relays/solenoids (if in- stalled) can be tested with the compressors on or off. The relays

under the COMP mode will stay on for 10 minutes if there is no keypad activity. Compressors will stay on until they are turned off by the operator. The Service Test mode will remain enabled for as long as there is one or more compressors run- ning. All safeties are monitored during this test and will turn a compressor, circuit or the machine off if required. Any other mode or sub-mode can be accessed, viewed, or changed during the TEST mode. The MODE item (Run StatusVIEW) will display “0” as long as the Service mode is enabled. The TEST sub-mode value must be changed back to OFF before the chill- er can be switched to Enable or Remote contact for normal operation.

Optional Factory-Installed Hydronic Pack-

age — If the chiller has factory-installed chilled fluid pumps, specific steps should be followed for proper operation.

The pump(s) in the hydronic package come factory pre-wired into the main unit power supply/starter. In order to check proper pump rotation, use the Service Test function to test the condenser fans and observe them for proper rotation. If fans turn correctly, the pumps will rotate correctly. Clockwise rotation of the pump motor cooling fans can also be used to de- termine that pumps are rotating correctly.

CAUTION

Operation of pump in wrong direction, even for a few seconds, can cause irreversible damage to pump impeller and housing. Always verify correct wiring/pump rotation before operation.

Use Service Test function to test operation of pumps. Verify that the flow switch input is made when the pump is running. For dual pump hydronic systems, the control only uses one pump at a time. Consult the Installation Instructions supplied with this chiller and use the circuit setter balancing valve installed in hydronic package to adjust fluid flow rate.

Cooler Pump Control — The AquaSnap® 30RAP ma- chines equipped with a factory-installed pump package are configured with the Cooler Pump Control (Configura- tionOPT1CPC) = ON.

Machines not equipped with a pump package are config- ured with the cooler pump control OFF. It is recommended that the machine control the chilled water pump. If not, a 5-minute time delay is required after the command to shut the machine down is sent before the chilled water pump is turned off. This is required to maintain water flow during the shutdown period of the machine.

With or without this option enabled, the cooler pump relay will be energized when the machine enters an ON status (i.e., On Local, On CCN, On Time). An A207 - Cooler Freeze Protection Alarm, will energize the cooler pump relay also, as an override. The cooler pump relay will remain energized if the machine is in MODE 10 – Minimum Off Time.

34

Image 34
Contents Controls, Start-Up, Operation, Service, and Troubleshooting ContentsContents Safety ConsiderationsUnit Sizes GeneralBasic Controls Usage Unit Nominal Capacity TonsAccessory Navigator Display Module Scrolling Marquee Display Menu Structure Mode RUN Service TemperaturesSET Inputs Outputs Configuration Time Operating Alarms TestRun Status Mode and Sub-Mode Directory StrtSUB-MODE Keypad Display SUB-ITEM Comment Entry Expansion VersOuts Service Test Mode and Sub-Mode DirectorySUB-MODE Keypad Display Comment Entry Expansion Test CmpaPressure Mode and Sub-Mode Directory Temperature Mode and Sub-Mode DirectorySet Points Mode and Sub-Mode Directory Inputs Mode and Sub-Mode Directory Outputs Mode and Sub-Mode DirectoryConfiguration Mode and Sub-Mode Directory SUB-MODE Keypad Display Comment Entry Expansion EXVOPT1 SUB-MODE Keypad Display Comment Entry Expansion UnitSUB-MODE Keypad Display Comment OPT2XXX XXX.X ΔF Date Time Clock Mode and Sub-Mode DirectoryDST Operating Mode and Sub-Mode Directory Alarms Mode and Sub-Mode DirectoryMode Item Expansion Description Operating ModesControl Module Communication ControlsCarrier Comfort Network CCN Interface Status Inputs CCN Communication Bus WiringThermistor Designations Output RelaysCCB AlmrAUX CHCA30-4962 A30-4963A30-4964 Typical Control Box for 30RAP035-060Typical Wiring Schematic, 30RAP018-030 Units Power Wiring Typical Wiring Schematic, 30RAP018-030 Units Control Wiring A30-4966Typical Wiring Schematic, 30RAP035-060 Units Power Wiring 5283Typical Wiring Schematic, 30RAP035-060 Units Control Wiring A30-5284A30-4967 A30-4968Page CEPL130351 Deadband Multiplier 30RAP Unit Size Control Capacity Steps Capacity %A30-4969 Operating Envelope for R-410A CompressorA30-4970 Cooling Set Point Select30RAP Unit Size FAN Stages Control Occupancy Cooling SET Point Select Clsp Type State Optional Factory-Installed Hydronic PackControl Methods and Cooling Set Points CCN→PM1E = YES Configuring and Operating Dual Chiller Con Dual Chiller Configuration Master Chiller Example RsetNumber PartSUB-MODE Keypad Entry Display Item Expansion Comments Dual Chiller Configuration Slave Chiller Example Rset Slave CompleteTo 20 mA Reset Menu Configuration of 4 to 20 mA Cooling Set Point ControlMode Keypad SUB Display Configuring Outdoor Air and Space Temperature ResetConfiguring Return Temperature Reset RED LED Entry ModeOutdoor-Air Temperature Reset To 20-mA Demand Limiting PRE-START-UP Configuring Demand LimitItem Expansion Comment Entry Configuration System CheckA30-4978 START-UP and Operation30RAP Minimum Cooler Flow Maximum Cooler Flow Size Operation Sequence Temperature Limits for Standard 30RAP UnitsOperating Limitations Unit Size 30RAEXV Steps ServiceElectronic Components Unit Size 30RAP EXV StepsA30-4971 Electronic Expansion Valve DetailsCooler Compressor Replacement Refer to FigUnit Torque Specification A30-4972Oil Charge Check Refrigerant Feed ComponentsA30-4974 A30-4973LWT Check Unit Safeties Factory Settings, High-Pressure Switch FixedUnit Cutout CUT-IN Thermistor Well Temp Voltage Resistance Drop 100,260 143 86K Thermistor vs Resistance DTT DropA30-4976 A30-4975A30-499 AccsyP50 Fault History Last 8 faults P51 Software version TB1-TB2 Mode Nominal Voltage Control Input Start JumperA30-4977 TB13A-TB2Fault Codes Motormaster V Program Parameters for Operating Modes Parameters Description ModePID Replacement Modules MaintenanceReplacement Replacement Part Module Troubleshooting Advanced Scroll Temperature Protection Label 30RAP Unit Cutout CUT-IN SizeTroubleshooting Symptoms Cause RemedyAlarm and Alert Codes T051T110 T153 T197 CSB Alert GENERATED?CCN EMMCompressor Stuck on Failure Alarms Page View Appendix a Display TablesSUB-MODE Display Item Description Comment RUNStrt Appendix a Display TablesVers Pressures Mode and Sub-Mode Directory Head SUB-MODE Display Item Description Range CommentCool FRZGEN.O SUB-MODE Display Item Description Comment HP.A HP.BEXV.A EXV.BRset Bcst DST SUB-MODE Display Item Description Comment TimeDate HOL.LHD.19 HD.30 PER.1 SUB-MODE Display Item Description Comment SCH.NSCH.L PER.2PER.7 PER.6PER.8 Rcrn CrntHist CCN Display Tables Circaan Circuit a Analog Parameters Appendix B CCN TablesCCN Display Tables Aunit General Unit Parameters Description Value Units Point Name ForcibleAppendix B CCN Tables CCN Display Tables Circban Circuit B Analog ParametersDescription Value Default Units Point Name CCN Configuration Tables Unit Unit ConfigurationCCN Configuration Tables OPTIONS1 Options 1 Configuration CCN Display Tables Options Unit ParametersCCN Configuration Tables OPTIONS2 Options 2 Configuration CCN Configuration Tables Schedovr Timed Override SetupCCN Configuration Tables Display Marquee Display Setup CCN Configuration Tables Mmconf Motormaster ConfigurationCCN Service Tables Service Description Value Units Point Name Description Value Point NameCCN Maintenance Tables Alarms Description Version ValueCCN Maintenance Tables PM-PUMP CCN Maintenance Tables Runtest CCN Maintenance Tables Dualchil Appendix C Factory Settings for Pump and Manual Starters SettingAppendix D Optional Bacnet Communications Wiring Optional BACnet Communications WiringTable B Baud Selection Table Appendix D Optional Bacnet Communications WiringTable a SW3 Protocol Switch Settings For MS/TP DS8 DS7 DS6 DS5 DS4 DS3AWG Table C MS/TP Wiring RecommendationsSpecification Recommmendation CL2PRmcorp Wiring Specifications Recommended Vendors and Part NumbersCMP RUN LED Error LED Status Table E LED Status IndicatorsLED Status Control Mode Table G Network Points List108 109 Weekly Appendix E Maintenance Summary and LOG Sheets30RAP Maintenance Interval Requirements QuarterlyAppendix E Maintenance Summary and LOG Sheets 30RAP Weekly Maintenance LogUnit Section Action Entry 30RAP Monthly Maintenance LogPSI 30RAP Seasonal Shutdown Log 113Copyright 2010 Carrier Corporation II. Preliminary Equipment Check START-UP Checklist for 30RAP Liquid ChillerRemove and use for Job File Project Information Design InformationIII. Unit Start-Up Start and Operate Machine. Complete the FollowingDual Chiller Control Only Mode RUN Status Record Software VersionsSubmode Item Expansion Display Entry Unit Configuration SettingsOPTIONS1 Options Configuration OPT1HP.A Head Pressure Cmp. Delta Configuration OPTIONS2 Options ConfigurationCCN CCN Network Configuration HP.B Head Pressure Cmp. Delta ConfigurationMM Motormaster Configuration Settings EXV.A Circuit a EXV ConfigurationEXV.B Circuit B EXV Configuration EXV.BRset Reset Configuration Settings Slct Setpoint and Ramp Load ConfigurationSetpoint SUB-MODE Keypad Display Comment Entry Expansion
Related manuals
Manual 40 pages 58.51 Kb

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.