Carrier 30RAP010-060 specifications Controls, Control Module Communication

Page 19

CONTROLS

General — The 30RAP air-cooled scroll chillers contain the ComfortLink™ electronic control system that controls and monitors all operations of the chiller.

The control system is composed of several components as listed in the sections below. See Fig. 3-5 for typical control box drawings. See Fig. 6 and 7 for control schematics.

Main Base Board (MBB) — See Fig. 8. The MBB is the heart of the ComfortLink control system. It contains the major portion of operating software and controls the operation of the machine. The MBB continuously monitors input/output channel information received from its inputs and from all other modules. The MBB receives inputs from the discharge and suction pressure transducers and thermistors. See Table 15. The MBB also receives the feedback inputs from each compressor current sensor board and other status switches. See Table 16. The MBB also controls several outputs. Relay outputs con- trolled by the MBB are shown in Table 17. Information is transmitted between modules via a 3-wire communication bus or LEN (Local Equipment Network). The CCN (Carrier Com- fort Network) bus is also supported. Connections to both LEN and CCN buses are made at the LVT (low voltage terminal). See Fig. 8.

Energy Management Module (EMM) — The EMM module is available as a factory-installed option or as a field- installed accessory. The EMM module receives 4 to 20 mA inputs for the leaving fluid temperature reset, cooling set point and demand limit functions. The EMM module also receives the switch inputs for the field-installed2-stage demand limit and ice done functions. The EMM module communicates the status of all inputs with the MBB, and the MBB adjusts the control point, capacity limit, and other functions according to the inputs received.

Current Sensor Board (CSB) — The CSB is used to monitor the status of the compressors by measuring current and providing an analog input to the main base board (MBB) or compressor expansion module (CXB).

AUX Board (AUX) — The AUX is used with the digital scroll option and the low ambient head pressure option. It pro- vides additional inputs and outputs for digital scroll control along with analog outputs to control head pressure control fan speeds.

Expansion Valve Board (EXV) — The EXV board communicates with the MBB and directly controls the expan- sion valves to maintain the correct compressor superheat.

Enable/Off/Remote Contact Switch — The Enable/ Off/Remote Contact switch is a 3-position switch used to control the chiller. When switched to the Enable position the chiller is under its own control. Move the switch to the Off position to shut the chiller down. Move the switch to the Remote Contact position and a field-installed dry contact can be used to start the chiller. The contacts must be capable of handling a 24 vac, 50-mA load. In the Enable and Remote Contact (dry contacts closed) positions, the chiller is allowed to operate and respond to the scheduling configuration, CCN configuration and set point data. See Fig. 9.

Emergency On/Off Switch — The Emergency On/Off switch should only be used when it is required to shut the chiller off immediately. Power to the MBB, EMM, and marquee display is interrupted when this switch is off and all outputs from these modules will be turned off.

Board Addresses — The main base board (MBB) has a 3-position instance jumper that must be set to ‘1.’ The elec- tronic expansion valve board (EXV) and energy management board (EMM) have 4-position DIP switches. All switches are

set to ‘On’ for these boards. The auxiliary board (AUX) has an 8-position DIP switch. Switches 2, 5, and 7 are set to ‘On.’

Control Module Communication

RED LED — Proper operation of the control boards can be visually checked by looking at the red status LEDs (light-emitting diodes). When operating correctly, the red status LEDs should be blinking in unison at a rate of once every 2 seconds. If the red LEDs are not blinking in unison, verify that correct power is being supplied to all modules. Be sure that the main base board (MBB) is supplied with the current soft- ware. If necessary, reload current software. If the problem still persists, replace the MBB. A red LED that is lit continuously or blinking at a rate of once per second or faster indicates that the board should be replaced.

GREEN LED — The MBB has one green LED. The Local Equipment Network (LEN) LED should always be blinking whenever power is on. All other boards have a LEN LED which should be blinking whenever power is on. Check LEN connections for potential communication errors at the board J3 and/or J4 connectors. Communication between modules is accomplished by a 3-wire sensor bus. These 3 wires run in parallel from module to module. The J4 connector on the MBB provides both power and communication directly to the marquee display only.

YELLOW LED — The MBB has one yellow LED. The Carrier Comfort Network (CCN) LED will blink during times of network communication.

Carrier Comfort Network® (CCN) Interface —

The 30RAP chiller units can be connected to the CCN if desired. The communication bus wiring is a shielded, 3-conductor cable with drain wire and is supplied and installed in the field. See Table 18. The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system elements on either side of it. This is also required for the negative and signal ground pins of each system element. Wiring connections for CCN should be made at LVT. Consult the CCN Contrac- tor’s Manual for further information.

NOTE: Conductors and drain wire must be 20 AWG (Ameri- can Wire Gage) minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20 C to 60 C is required. Wire manufactured by Alpha (2413 or 5463), American (A22503), Belden (8772), or Columbia (02525) meets the above mentioned requirements.

It is important when connecting to a CCN communication bus that a color coding scheme be used for the entire network to simplify the installation. It is recommended that red be used for the signal positive, black for the signal negative, and white for the signal ground. Use a similar scheme for cables contain- ing different colored wires.

At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the commu- nication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only). To connect the unit to the network:

1.Turn off power to the control box.

2.Cut the CCN wire and strip the ends of the red (+), white (ground), and black (–) conductors. (Substitute appropri- ate colors for different colored cables.)

19

Image 19
Contents Contents Controls, Start-Up, Operation, Service, and TroubleshootingSafety Considerations ContentsUnit Nominal Capacity Tons GeneralBasic Controls Usage Unit SizesAccessory Navigator Display Module Test Mode RUN Service TemperaturesSET Inputs Outputs Configuration Time Operating Alarms Scrolling Marquee Display Menu StructureStrt Run Status Mode and Sub-Mode DirectoryVers SUB-MODE Keypad Display SUB-ITEM Comment Entry ExpansionCmpa Service Test Mode and Sub-Mode DirectorySUB-MODE Keypad Display Comment Entry Expansion Test OutsPressure Mode and Sub-Mode Directory Temperature Mode and Sub-Mode DirectorySet Points Mode and Sub-Mode Directory Outputs Mode and Sub-Mode Directory Inputs Mode and Sub-Mode DirectorySUB-MODE Keypad Display Comment Entry Expansion EXV Configuration Mode and Sub-Mode DirectorySUB-MODE Keypad Display Comment Entry Expansion Unit OPT1OPT2 SUB-MODE Keypad Display CommentXXX XXX.X ΔF Date Time Clock Mode and Sub-Mode DirectoryDST Alarms Mode and Sub-Mode Directory Operating Mode and Sub-Mode DirectoryOperating Modes Mode Item Expansion DescriptionControl Module Communication ControlsCarrier Comfort Network CCN Interface Output Relays CCN Communication Bus WiringThermistor Designations Status InputsCHC AlmrAUX CCBA30-4963 A30-4962Typical Control Box for 30RAP035-060 A30-4964Typical Wiring Schematic, 30RAP018-030 Units Power Wiring A30-4966 Typical Wiring Schematic, 30RAP018-030 Units Control Wiring5283 Typical Wiring Schematic, 30RAP035-060 Units Power WiringA30-5284 Typical Wiring Schematic, 30RAP035-060 Units Control WiringA30-4968 A30-4967Page CEPL130351 30RAP Unit Size Control Capacity Steps Capacity % Deadband MultiplierOperating Envelope for R-410A Compressor A30-4969A30-4970 Cooling Set Point Select30RAP Unit Size FAN Stages CCN Optional Factory-Installed Hydronic PackControl Methods and Cooling Set Points Control Occupancy Cooling SET Point Select Clsp Type State→PM1E = YES Configuring and Operating Dual Chiller Con Rset Dual Chiller Configuration Master Chiller ExampleNumber PartSUB-MODE Keypad Entry Display Item Expansion Comments Rset Slave Complete Dual Chiller Configuration Slave Chiller ExampleMenu Configuration of 4 to 20 mA Cooling Set Point Control To 20 mA ResetRED LED Entry Mode Configuring Outdoor Air and Space Temperature ResetConfiguring Return Temperature Reset Mode Keypad SUB DisplayOutdoor-Air Temperature Reset To 20-mA Demand Limiting System Check Configuring Demand LimitItem Expansion Comment Entry Configuration PRE-START-UPA30-4978 START-UP and Operation30RAP Minimum Cooler Flow Maximum Cooler Flow Size Unit Size 30RA Temperature Limits for Standard 30RAP UnitsOperating Limitations Operation SequenceUnit Size 30RAP EXV Steps ServiceElectronic Components EXV StepsElectronic Expansion Valve Details A30-4971A30-4972 Compressor Replacement Refer to FigUnit Torque Specification CoolerCheck Refrigerant Feed Components Oil ChargeA30-4974 A30-4973LWT Check Unit Safeties Factory Settings, High-Pressure Switch FixedUnit Cutout CUT-IN Thermistor Well Temp Voltage Resistance Drop 100,260 143 Drop 86K Thermistor vs Resistance DTTAccsy A30-4975A30-499 A30-4976P50 Fault History Last 8 faults P51 Software version TB13A-TB2 Mode Nominal Voltage Control Input Start JumperA30-4977 TB1-TB2Fault Codes Motormaster V Program Parameters for Operating Modes Parameters Description ModePID Replacement Modules MaintenanceReplacement Replacement Part Module Troubleshooting 30RAP Unit Cutout CUT-IN Size Advanced Scroll Temperature Protection LabelSymptoms Cause Remedy TroubleshootingT051 Alarm and Alert CodesT110 T153 T197 EMM Alert GENERATED?CCN CSBCompressor Stuck on Failure Alarms Page RUN Appendix a Display TablesSUB-MODE Display Item Description Comment ViewStrt Appendix a Display TablesVers Pressures Mode and Sub-Mode Directory FRZ SUB-MODE Display Item Description Range CommentCool HeadGEN.O SUB-MODE Display Item Description Comment HP.B HP.AEXV.B EXV.ARset Bcst HOL.L SUB-MODE Display Item Description Comment TimeDate DSTHD.19 HD.30 PER.2 SUB-MODE Display Item Description Comment SCH.NSCH.L PER.1PER.7 PER.6PER.8 Rcrn CrntHist Description Value Units Point Name Forcible Appendix B CCN TablesCCN Display Tables Aunit General Unit Parameters CCN Display Tables Circaan Circuit a Analog ParametersCCN Display Tables Circban Circuit B Analog Parameters Appendix B CCN TablesCCN Display Tables Options Unit Parameters CCN Configuration Tables Unit Unit ConfigurationCCN Configuration Tables OPTIONS1 Options 1 Configuration Description Value Default Units Point NameCCN Configuration Tables Schedovr Timed Override Setup CCN Configuration Tables OPTIONS2 Options 2 ConfigurationCCN Configuration Tables Mmconf Motormaster Configuration CCN Configuration Tables Display Marquee Display SetupCCN Service Tables Service Description Value Point Name Description Value Units Point NameDescription Version Value CCN Maintenance Tables AlarmsCCN Maintenance Tables PM-PUMP CCN Maintenance Tables Runtest CCN Maintenance Tables Dualchil Setting Appendix C Factory Settings for Pump and Manual StartersOptional BACnet Communications Wiring Appendix D Optional Bacnet Communications WiringDS8 DS7 DS6 DS5 DS4 DS3 Appendix D Optional Bacnet Communications WiringTable a SW3 Protocol Switch Settings For MS/TP Table B Baud Selection TableCL2P Table C MS/TP Wiring RecommendationsSpecification Recommmendation AWGRmcorp Wiring Specifications Recommended Vendors and Part NumbersCMP RUN LED Error LED Status Table E LED Status IndicatorsLED Status Table G Network Points List Control Mode108 109 Quarterly Appendix E Maintenance Summary and LOG Sheets30RAP Maintenance Interval Requirements Weekly30RAP Weekly Maintenance Log Appendix E Maintenance Summary and LOG SheetsUnit Section Action Entry 30RAP Monthly Maintenance LogPSI 113 30RAP Seasonal Shutdown LogCopyright 2010 Carrier Corporation Design Information START-UP Checklist for 30RAP Liquid ChillerRemove and use for Job File Project Information II. Preliminary Equipment CheckStart and Operate Machine. Complete the Following III. Unit Start-UpDual Chiller Control Only Record Software Versions Mode RUN StatusOPT1 Unit Configuration SettingsOPTIONS1 Options Configuration Submode Item Expansion Display EntryHP.B Head Pressure Cmp. Delta Configuration OPTIONS2 Options ConfigurationCCN CCN Network Configuration HP.A Head Pressure Cmp. Delta ConfigurationEXV.B EXV.A Circuit a EXV ConfigurationEXV.B Circuit B EXV Configuration MM Motormaster Configuration SettingsSlct Setpoint and Ramp Load Configuration Rset Reset Configuration SettingsSetpoint Entry Expansion SUB-MODE Keypad Display Comment
Related manuals
Manual 40 pages 58.51 Kb

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.