Table 34 — 5K Thermistor Temperatures (°C) vs. Resistance/Voltage Drop

(Voltage Drop for EWT, LWT, RGT, and OAT)

TEMP

VOLTAGE

RESISTANCE

DROP

(C)

(Ohms)

(V)

 

 

–32

3.705

100,260

–31

3.687

94,165

–30

3.668

88,480

–29

3.649

83,170

–28

3.629

78,125

–27

3.608

73,580

–26

3.586

69,250

–25

3.563

65,205

–24

3.539

61,420

–23

3.514

57,875

–22

3.489

54,555

–21

3.462

51,450

–20

3.434

48,536

–19

3.406

45,807

–18

3.376

43,247

–17

3.345

40,845

–16

3.313

38,592

–15

3.281

38,476

–14

3.247

34,489

–13

3.212

32,621

–12

3.177

30,866

–11

3.140

29,216

–10

3.103

27,633

–9

3.065

26,202

–8

3.025

24,827

–7

2.985

23,532

–6

2.945

22,313

–5

2.903

21,163

–4

2.860

20,079

–3

2.817

19,058

–2

2.774

18,094

–1

2.730

17,184

0

2.685

16,325

1

2.639

15,515

2

2.593

14,749

3

2.547

14,026

4

2.500

13,342

5

2.454

12,696

6

2.407

12,085

7

2.360

11,506

8

2.312

10,959

9

2.265

10,441

10

2.217

9,949

11

2.170

9,485

12

2.123

9,044

13

2.076

8,627

14

2.029

8,231

TEMP

VOLTAGE

RESISTANCE

DROP

(C)

(Ohms)

(V)

 

 

15

1.982

7,855

16

1.935

7,499

17

1.889

7,161

18

1.844

6,840

19

1.799

6,536

20

1.754

6,246

21

1.710

5,971

22

1.666

5,710

23

1.623

5,461

24

1.580

5,225

25

1.538

5,000

26

1.497

4,786

27

1.457

4,583

28

1.417

4,389

29

1.378

4,204

30

1.340

4,028

31

1.302

3,861

32

1.265

3,701

33

1.229

3,549

34

1.194

3,404

35

1.160

3,266

36

1.126

3,134

37

1.093

3,008

38

1.061

2,888

39

1.030

2,773

40

0.999

2,663

41

0.969

2,559

42

0.940

2,459

43

0.912

2,363

44

0.885

2,272

45

0.858

2,184

46

0.832

2,101

47

0.807

2,021

48

0.782

1,944

49

0.758

1,871

50

0.735

1,801

51

0.713

1,734

52

0.691

1,670

53

0.669

1,609

54

0.649

1,550

55

0.629

1,493

56

0.610

1,439

57

0.591

1,387

58

0.573

1,337

59

0.555

1,290

60

0.538

1,244

61

0.522

1,200

TEMP

VOLTAGE

RESISTANCE

DROP

(C)

(Ohms)

(V)

 

 

62

0.506

1,158

63

0.490

1,118

64

0.475

1,079

65

0.461

1,041

66

0.447

1,006

67

0.433

971

68

0.420

938

69

0.407

906

70

0.395

876

71

0.383

836

72

0.371

805

73

0.360

775

74

0.349

747

75

0.339

719

76

0.329

693

77

0.319

669

78

0.309

645

79

0.300

623

80

0.291

602

81

0.283

583

82

0.274

564

83

0.266

547

84

0.258

531

85

0.251

516

86

0.244

502

87

0.237

489

88

0.230

477

89

0.223

466

90

0.217

456

91

0.211

446

92

0.204

436

93

0.199

427

94

0.193

419

95

0.188

410

96

0.182

402

97

0.177

393

98

0.172

385

99

0.168

376

100

0.163

367

101

0.158

357

102

0.154

346

103

0.150

335

104

0.146

324

105

0.142

312

106

0.138

299

107

0.134

285

55

Image 55
Contents Contents Controls, Start-Up, Operation, Service, and TroubleshootingSafety Considerations ContentsUnit Nominal Capacity Tons GeneralBasic Controls Usage Unit SizesAccessory Navigator Display Module Test Mode RUN Service TemperaturesSET Inputs Outputs Configuration Time Operating Alarms Scrolling Marquee Display Menu StructureStrt Run Status Mode and Sub-Mode DirectoryVers SUB-MODE Keypad Display SUB-ITEM Comment Entry ExpansionCmpa Service Test Mode and Sub-Mode DirectorySUB-MODE Keypad Display Comment Entry Expansion Test OutsPressure Mode and Sub-Mode Directory Temperature Mode and Sub-Mode DirectorySet Points Mode and Sub-Mode Directory Outputs Mode and Sub-Mode Directory Inputs Mode and Sub-Mode DirectorySUB-MODE Keypad Display Comment Entry Expansion EXV Configuration Mode and Sub-Mode DirectorySUB-MODE Keypad Display Comment Entry Expansion Unit OPT1OPT2 SUB-MODE Keypad Display CommentXXX XXX.X ΔF Date Time Clock Mode and Sub-Mode DirectoryDST Alarms Mode and Sub-Mode Directory Operating Mode and Sub-Mode DirectoryOperating Modes Mode Item Expansion DescriptionControl Module Communication ControlsCarrier Comfort Network CCN Interface Output Relays CCN Communication Bus WiringThermistor Designations Status InputsCHC AlmrAUX CCBA30-4963 A30-4962Typical Control Box for 30RAP035-060 A30-4964Typical Wiring Schematic, 30RAP018-030 Units Power Wiring A30-4966 Typical Wiring Schematic, 30RAP018-030 Units Control Wiring5283 Typical Wiring Schematic, 30RAP035-060 Units Power WiringA30-5284 Typical Wiring Schematic, 30RAP035-060 Units Control WiringA30-4968 A30-4967Page CEPL130351 30RAP Unit Size Control Capacity Steps Capacity % Deadband MultiplierOperating Envelope for R-410A Compressor A30-4969A30-4970 Cooling Set Point Select30RAP Unit Size FAN Stages CCN Optional Factory-Installed Hydronic PackControl Methods and Cooling Set Points Control Occupancy Cooling SET Point Select Clsp Type State→PM1E = YES Configuring and Operating Dual Chiller Con Rset Dual Chiller Configuration Master Chiller ExampleNumber PartSUB-MODE Keypad Entry Display Item Expansion Comments Rset Slave Complete Dual Chiller Configuration Slave Chiller ExampleMenu Configuration of 4 to 20 mA Cooling Set Point Control To 20 mA ResetRED LED Entry Mode Configuring Outdoor Air and Space Temperature ResetConfiguring Return Temperature Reset Mode Keypad SUB DisplayOutdoor-Air Temperature Reset To 20-mA Demand Limiting System Check Configuring Demand LimitItem Expansion Comment Entry Configuration PRE-START-UPA30-4978 START-UP and Operation30RAP Minimum Cooler Flow Maximum Cooler Flow Size Unit Size 30RA Temperature Limits for Standard 30RAP UnitsOperating Limitations Operation SequenceUnit Size 30RAP EXV Steps ServiceElectronic Components EXV StepsElectronic Expansion Valve Details A30-4971A30-4972 Compressor Replacement Refer to FigUnit Torque Specification CoolerCheck Refrigerant Feed Components Oil ChargeA30-4974 A30-4973LWT Check Unit Safeties Factory Settings, High-Pressure Switch FixedUnit Cutout CUT-IN Thermistor Well Temp Voltage Resistance Drop 100,260 143 Drop 86K Thermistor vs Resistance DTTAccsy A30-4975A30-499 A30-4976P50 Fault History Last 8 faults P51 Software version TB13A-TB2 Mode Nominal Voltage Control Input Start JumperA30-4977 TB1-TB2Fault Codes Motormaster V Program Parameters for Operating Modes Parameters Description ModePID Replacement Modules MaintenanceReplacement Replacement Part Module Troubleshooting 30RAP Unit Cutout CUT-IN Size Advanced Scroll Temperature Protection LabelSymptoms Cause Remedy TroubleshootingT051 Alarm and Alert CodesT110 T153 T197 EMM Alert GENERATED?CCN CSBCompressor Stuck on Failure Alarms Page RUN Appendix a Display TablesSUB-MODE Display Item Description Comment ViewStrt Appendix a Display TablesVers Pressures Mode and Sub-Mode Directory FRZ SUB-MODE Display Item Description Range CommentCool HeadGEN.O SUB-MODE Display Item Description Comment HP.B HP.AEXV.B EXV.ARset Bcst HOL.L SUB-MODE Display Item Description Comment TimeDate DSTHD.19 HD.30 PER.2 SUB-MODE Display Item Description Comment SCH.NSCH.L PER.1PER.7 PER.6PER.8 Rcrn CrntHist Description Value Units Point Name Forcible Appendix B CCN TablesCCN Display Tables Aunit General Unit Parameters CCN Display Tables Circaan Circuit a Analog ParametersCCN Display Tables Circban Circuit B Analog Parameters Appendix B CCN TablesCCN Display Tables Options Unit Parameters CCN Configuration Tables Unit Unit ConfigurationCCN Configuration Tables OPTIONS1 Options 1 Configuration Description Value Default Units Point NameCCN Configuration Tables Schedovr Timed Override Setup CCN Configuration Tables OPTIONS2 Options 2 ConfigurationCCN Configuration Tables Mmconf Motormaster Configuration CCN Configuration Tables Display Marquee Display SetupCCN Service Tables Service Description Value Point Name Description Value Units Point NameDescription Version Value CCN Maintenance Tables AlarmsCCN Maintenance Tables PM-PUMP CCN Maintenance Tables Runtest CCN Maintenance Tables Dualchil Setting Appendix C Factory Settings for Pump and Manual StartersOptional BACnet Communications Wiring Appendix D Optional Bacnet Communications WiringDS8 DS7 DS6 DS5 DS4 DS3 Appendix D Optional Bacnet Communications WiringTable a SW3 Protocol Switch Settings For MS/TP Table B Baud Selection TableCL2P Table C MS/TP Wiring RecommendationsSpecification Recommmendation AWGRmcorp Wiring Specifications Recommended Vendors and Part NumbersCMP RUN LED Error LED Status Table E LED Status IndicatorsLED Status Table G Network Points List Control Mode108 109 Quarterly Appendix E Maintenance Summary and LOG Sheets30RAP Maintenance Interval Requirements Weekly30RAP Weekly Maintenance Log Appendix E Maintenance Summary and LOG SheetsUnit Section Action Entry 30RAP Monthly Maintenance LogPSI 113 30RAP Seasonal Shutdown LogCopyright 2010 Carrier Corporation Design Information START-UP Checklist for 30RAP Liquid ChillerRemove and use for Job File Project Information II. Preliminary Equipment CheckStart and Operate Machine. Complete the Following III. Unit Start-UpDual Chiller Control Only Record Software Versions Mode RUN StatusOPT1 Unit Configuration SettingsOPTIONS1 Options Configuration Submode Item Expansion Display EntryHP.B Head Pressure Cmp. Delta Configuration OPTIONS2 Options ConfigurationCCN CCN Network Configuration HP.A Head Pressure Cmp. Delta ConfigurationEXV.B EXV.A Circuit a EXV ConfigurationEXV.B Circuit B EXV Configuration MM Motormaster Configuration SettingsSlct Setpoint and Ramp Load Configuration Rset Reset Configuration SettingsSetpoint Entry Expansion SUB-MODE Keypad Display Comment
Related manuals
Manual 40 pages 58.51 Kb

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.