Carrier 30RAP010-060 specifications →PM1E = YES

Page 35

Cooler Pump Sequence of Operation — At any- time the unit is in an ON status, as defined by the one of the following conditions, the cooler pump relay will be enabled.

1.The Enable-Off-Remote Switch in ENABLE, (CTRL=0).

2.Enable-Off-Remote Switch in REMOTE with a Start-Stop remote contact closure (CTRL=0).

3.An Occupied Time Period from an Occupancy Schedule in combination with items 1 or 2 (CTRL=2).

4.A CCN Start-Stop Command to Start in combination with items 1 or 2 (CTRL=3).

As stated before, there are certain alarm conditions and Operating Modes that will turn the cooler pump relay ON. This sequence will describe the normal operation of the pump control algorithm.

When the unit cycles from an “On” state to an “Off” state, the cooler pump output will remain energized for the Cooler Pump Shutdown Delay (ConfigurationOPT1PM.DY). This is configurable from 0 to 10 minutes. The factory default is 1 minute.

NO INTEGRAL PUMP — SINGLE EXTERNAL PUMP CONTROL — With a single external pump, the following options must be configured:

Cooler Pump Control (ConfigurationOPT1CPC) = OFF.

Cooler Pump 1 Enable (ConfigurationOPT1

PM1E) = NO.

Cooler Pump 2 Enable (ConfigurationOPT1

PM2E) = NO.

The maximum load allowed for the Chilled Water Pump Starter is 5 VA sealed, 10 VA inrush at 24 volts. The starter coil is powered from the chiller control system. The starter should be wired between LVT-25 and LVT-21. If equipped, the field- installed chilled water pump starter auxiliary contacts should be connected in series with the chilled water flow switch.

The Cooler Pump Relay will be energized when the machine is “On.” The chilled water pump interlock circuit consists of a chilled water flow switch and a field-installed chilled water pump interlock. If the chilled water pump inter- lock circuit does not close within five (5) minutes of starting, an A200 — Cooler Flow/Interlock Failed to Close at Start-Up Alarm will be generated and chiller will not be allowed to start.

If the chilled water pump interlock or chilled water flow switch opens for at least three (3) seconds after initially being closed, an A201 — Cooler Flow/Interlock Contacts Opened During Normal Operation Alarm will be generated and the ma- chine will stop.

NO INTEGRAL PUMP — DUAL EXTERNAL PUMP CONTROL — With two external pumps, the following options must be configured:

Cooler Pump Control (ConfigurationOPT1CPC) = ON.

Cooler Pump 1 Enable (ConfigurationOPT1

PM1E) = YES.

Cooler Pump 2 Enable (ConfigurationOPT1

PM2E) = YES.

The maximum load allowed for the Chilled Water Pump Starters is 5 VA sealed, 10 VA inrush at 24 volts. The starter coil is powered from the chiller control system. The starter for Chilled Water Pump 1 should be wired between LVT-25 and LVT-21. The starter for Chilled Water Pump 2 should be wired between LVT-24 and LVT-21. A field-installed chilled water pump interlock for each pump must be connected to each pump’s interlock points on the main base board. The chilled water pump 1 interlock, CWP1, must be connected to MBB- J7-1 and –2. The chilled water pump 2 interlock, CWP2, must be connected to MBB-J7-3 and –4. The chilled water pump

interlock contacts should be rated for dry circuit application capable of handling 5 vdc at 2 mA.

SINGLE INTEGRAL PUMP CONTROL — With a single pump, the following options must be configured:

Cooler Pump Control (ConfigurationOPT1CPC) = ON.

Cooler Pump 1 Enable (ConfigurationOPT1

PM1E) = YES.

Cooler Pump 2 Enable (ConfigurationOPT1

PM2E) = NO.

With a single integral pump, the Cooler Pump Starter will be energized when the machine is occupied. As part of the factory-installed package, an auxiliary set of contacts is wired to the MBB to serve as Chilled Water Pump Interlock. When the mechanical cooling is called for, the pump interlock and flow switch is checked. If the circuits are closed, the machine starts its capacity routine. If the auxiliary contact interlock does not close within 25 seconds of the ON command, a T190 — Cooler Pump 1 Aux Contacts Failed to Close at Start-Up Alert will be generated and the pump shut down. The unit will not be allowed to start. If the chilled water flow switch does not close within one (1) minute, two alarms will be generated. A T192 — Cooler Pump 1 Failed to Provide Flow at Start-Up Alert and an A200 — Cooler Flow/Interlock Failed to Close at Start-Up Alarm will be generated and chiller will not be al- lowed to start.

If the chilled water flow switch opens for at least 3 seconds after initially being closed, a T196 — Flow Lost While Pump 1 Running Alert and an A201 — Cooler Flow/Interlock Contacts Opened During Normal Operation Alarm will be generated and the machine will stop.

If the control detects the chilled water pump interlock open for 25 seconds after initially being closed, a T194 — Cooler Pump 1 Contacts Opened During Normal Operation Alert is generated and the unit is shut down.

If the control detects the chilled water flow switch circuit closed for at least 5 minutes with the pump output OFF, an A202 — Cooler Pump Interlock Closed When Pump is Off Alarm will be generated and the unit will not be allowed to start.

If the control detects that the chilled water pump auxiliary contacts are closed for at least 25 seconds while the pump is OFF, a T198 — Cooler Pump 1 Aux Contacts Closed While Pump Off Alert is generated. The chiller will not be allowed to start.

If the control starts a pump and the wrong interlock circuit closes for at least 20 seconds, an A189 — Cooler Pump and Aux Contact Input Miswire Alarm will be generated. The unit will be prevented from starting.

As part of a pump maintenance routine, the pump can be started to maintain lubrication of the pump seal. To utilize this function, Cooler Pmp Periodic Start (ConfigurationOPT1 PM.P.S) must be set to YES. This option is set to NO as the factory default. With this feature enabled, if the pump is not op- erating, it will be started and operated for 2 seconds starting at 14:00 hours. If the pump is operating, this routine is skipped. If the pump has failed and an Alarm/Alert condition is active, the pump will not start that day.

DUAL INTEGRAL PUMP CONTROL — With a dual inte- gral pump package, the following options must be configured:

Cooler Pump Control (ConfigurationOPT1CPC) = ON.

Cooler Pump 1 Enable (ConfigurationOPT1

PM1E) = YES.

Cooler Pump 2 Enable (ConfigurationOPT1

PM2E) = YES.

Pump Start Selection is a field-configurable choice. Cooler Pump Select (ConfigurationOPT1PM.SL) is factory defaulted to 0 (Automatic). This value can be changed to 1

35

Image 35
Contents Contents Controls, Start-Up, Operation, Service, and TroubleshootingSafety Considerations ContentsUnit Nominal Capacity Tons GeneralBasic Controls Usage Unit SizesAccessory Navigator Display Module Test Mode RUN Service TemperaturesSET Inputs Outputs Configuration Time Operating Alarms Scrolling Marquee Display Menu StructureStrt Run Status Mode and Sub-Mode DirectoryVers SUB-MODE Keypad Display SUB-ITEM Comment Entry ExpansionCmpa Service Test Mode and Sub-Mode DirectorySUB-MODE Keypad Display Comment Entry Expansion Test OutsSet Points Mode and Sub-Mode Directory Temperature Mode and Sub-Mode DirectoryPressure Mode and Sub-Mode Directory Outputs Mode and Sub-Mode Directory Inputs Mode and Sub-Mode DirectorySUB-MODE Keypad Display Comment Entry Expansion EXV Configuration Mode and Sub-Mode DirectorySUB-MODE Keypad Display Comment Entry Expansion Unit OPT1OPT2 SUB-MODE Keypad Display CommentXXX XXX.X ΔF DST Time Clock Mode and Sub-Mode DirectoryDate Alarms Mode and Sub-Mode Directory Operating Mode and Sub-Mode DirectoryOperating Modes Mode Item Expansion DescriptionCarrier Comfort Network CCN Interface ControlsControl Module Communication Output Relays CCN Communication Bus WiringThermistor Designations Status InputsCHC AlmrAUX CCBA30-4963 A30-4962Typical Control Box for 30RAP035-060 A30-4964Typical Wiring Schematic, 30RAP018-030 Units Power Wiring A30-4966 Typical Wiring Schematic, 30RAP018-030 Units Control Wiring5283 Typical Wiring Schematic, 30RAP035-060 Units Power WiringA30-5284 Typical Wiring Schematic, 30RAP035-060 Units Control WiringA30-4968 A30-4967Page CEPL130351 30RAP Unit Size Control Capacity Steps Capacity % Deadband MultiplierOperating Envelope for R-410A Compressor A30-496930RAP Unit Size FAN Stages Cooling Set Point SelectA30-4970 CCN Optional Factory-Installed Hydronic PackControl Methods and Cooling Set Points Control Occupancy Cooling SET Point Select Clsp Type State→PM1E = YES Configuring and Operating Dual Chiller Con Rset Dual Chiller Configuration Master Chiller ExampleSUB-MODE Keypad Entry Display Item Expansion Comments PartNumber Rset Slave Complete Dual Chiller Configuration Slave Chiller ExampleMenu Configuration of 4 to 20 mA Cooling Set Point Control To 20 mA ResetRED LED Entry Mode Configuring Outdoor Air and Space Temperature ResetConfiguring Return Temperature Reset Mode Keypad SUB DisplayOutdoor-Air Temperature Reset To 20-mA Demand Limiting System Check Configuring Demand LimitItem Expansion Comment Entry Configuration PRE-START-UP30RAP Minimum Cooler Flow Maximum Cooler Flow Size START-UP and OperationA30-4978 Unit Size 30RA Temperature Limits for Standard 30RAP UnitsOperating Limitations Operation SequenceUnit Size 30RAP EXV Steps ServiceElectronic Components EXV StepsElectronic Expansion Valve Details A30-4971A30-4972 Compressor Replacement Refer to FigUnit Torque Specification CoolerCheck Refrigerant Feed Components Oil ChargeLWT A30-4973A30-4974 Unit Cutout CUT-IN Factory Settings, High-Pressure Switch FixedCheck Unit Safeties Thermistor Well Temp Voltage Resistance Drop 100,260 143 Drop 86K Thermistor vs Resistance DTTAccsy A30-4975A30-499 A30-4976P50 Fault History Last 8 faults P51 Software version TB13A-TB2 Mode Nominal Voltage Control Input Start JumperA30-4977 TB1-TB2Fault Codes PID Parameters Description ModeMotormaster V Program Parameters for Operating Modes Replacement Replacement Part Module MaintenanceReplacement Modules Troubleshooting 30RAP Unit Cutout CUT-IN Size Advanced Scroll Temperature Protection LabelSymptoms Cause Remedy TroubleshootingT051 Alarm and Alert CodesT110 T153 T197 EMM Alert GENERATED?CCN CSBCompressor Stuck on Failure Alarms Page RUN Appendix a Display TablesSUB-MODE Display Item Description Comment ViewVers Appendix a Display TablesStrt Pressures Mode and Sub-Mode Directory FRZ SUB-MODE Display Item Description Range CommentCool HeadGEN.O SUB-MODE Display Item Description Comment HP.B HP.AEXV.B EXV.ARset Bcst HOL.L SUB-MODE Display Item Description Comment TimeDate DSTHD.19 HD.30 PER.2 SUB-MODE Display Item Description Comment SCH.NSCH.L PER.1PER.8 PER.6PER.7 Hist CrntRcrn Description Value Units Point Name Forcible Appendix B CCN TablesCCN Display Tables Aunit General Unit Parameters CCN Display Tables Circaan Circuit a Analog ParametersCCN Display Tables Circban Circuit B Analog Parameters Appendix B CCN TablesCCN Display Tables Options Unit Parameters CCN Configuration Tables Unit Unit ConfigurationCCN Configuration Tables OPTIONS1 Options 1 Configuration Description Value Default Units Point NameCCN Configuration Tables Schedovr Timed Override Setup CCN Configuration Tables OPTIONS2 Options 2 ConfigurationCCN Configuration Tables Mmconf Motormaster Configuration CCN Configuration Tables Display Marquee Display SetupCCN Service Tables Service Description Value Point Name Description Value Units Point NameDescription Version Value CCN Maintenance Tables AlarmsCCN Maintenance Tables PM-PUMP CCN Maintenance Tables Runtest CCN Maintenance Tables Dualchil Setting Appendix C Factory Settings for Pump and Manual StartersOptional BACnet Communications Wiring Appendix D Optional Bacnet Communications WiringDS8 DS7 DS6 DS5 DS4 DS3 Appendix D Optional Bacnet Communications WiringTable a SW3 Protocol Switch Settings For MS/TP Table B Baud Selection TableCL2P Table C MS/TP Wiring RecommendationsSpecification Recommmendation AWGCMP Wiring Specifications Recommended Vendors and Part NumbersRmcorp LED Status Table E LED Status IndicatorsRUN LED Error LED Status Table G Network Points List Control Mode108 109 Quarterly Appendix E Maintenance Summary and LOG Sheets30RAP Maintenance Interval Requirements Weekly30RAP Weekly Maintenance Log Appendix E Maintenance Summary and LOG SheetsPSI 30RAP Monthly Maintenance LogUnit Section Action Entry 113 30RAP Seasonal Shutdown LogCopyright 2010 Carrier Corporation Design Information START-UP Checklist for 30RAP Liquid ChillerRemove and use for Job File Project Information II. Preliminary Equipment CheckStart and Operate Machine. Complete the Following III. Unit Start-UpDual Chiller Control Only Record Software Versions Mode RUN StatusOPT1 Unit Configuration SettingsOPTIONS1 Options Configuration Submode Item Expansion Display EntryHP.B Head Pressure Cmp. Delta Configuration OPTIONS2 Options ConfigurationCCN CCN Network Configuration HP.A Head Pressure Cmp. Delta ConfigurationEXV.B EXV.A Circuit a EXV ConfigurationEXV.B Circuit B EXV Configuration MM Motormaster Configuration SettingsSlct Setpoint and Ramp Load Configuration Rset Reset Configuration SettingsSetpoint Entry Expansion SUB-MODE Keypad Display Comment
Related manuals
Manual 40 pages 58.51 Kb

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.