Carrier 30RAP010-060 specifications SUB-MODE Keypad Display Comment, Entry Expansion

Page 124

III.Unit Start-Up (cont)

COMPONENT TEST

USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY ‘DISP’. PRESS ENTER AGAIN TO DISPLAY ‘TEST’ FOLLOWED BY ‘OFF’. PRESS ENTER TO STOP DISPLAY AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ DISPLAY FLASHES. ‘PASS’ AND ‘WORD’ WILL FLASH IF PASSWORD NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD. AT FLASHING ‘OFF’ DISPLAY, PRESS THE UP ARROW KEY TO DISPLAY ‘ON’ AND PRESS ENTER. ALL LED SEGMENTS AND MODE LEDS WILL LIGHT UP. PRESS ESCAPE TO STOP THE TEST. PRESS ESCAPE TO RETURN TO THE ‘DISP’ DISPLAY. PRESS THE ESCAPE KEY AGAIN AND USE THE ARROW KEYS TO ILLU- MINATE THE SERVICE TEST LED. PRESS ENTER TO DISPLAY ‘TEST’. PRESS ENTER TO STOP DISPLAY AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ FLASHES. PRESS THE UP ARROW KEY AND ENTER TO ENABLE THE MANUAL MODE. PRESS ESCAPE AND DISPLAY NOW SAYS ‘TEST’ ‘ON’. REFER TO THE TABLE BELOW.

Service Test Mode and Sub-Mode Directory

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

COMMENT

Completed

ENTRY

EXPANSION

(Yes/No)

 

 

 

 

 

 

 

 

 

ON/OFF

SERVICE TEST MODE

To Enable Service Test Mode,

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

move Enable/Off/Remote

 

TEST

 

 

 

 

 

 

 

 

 

 

 

 

 

Contact switch to OFF. Change

 

 

 

 

 

 

 

 

TEST to ON. Move switch to

 

 

 

 

 

 

 

 

ENABLE.

 

 

 

 

 

 

 

OUTPUTS AND PUMPS

 

 

 

 

 

FAN1

ON/OFF

FAN 1 RELAY

Condenser fan contactor 1

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN2

ON/OFF

FAN 2 RELAY

Condenser fan contactor 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN3

ON/OFF

FAN 3 RELAY

Condenser fan contactor 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN4

ON/OFF

FAN 4 RELAY

Condenser fan contactor 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN5

ON/OFF

FAN 5 RELAY

Condenser fan contactor 5

 

OUTS

 

 

 

 

 

 

 

 

 

 

 

FAN6

ON/OFF

FAN 6 RELAY

Condenser fan contactor 6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V.HPA

XXX%

VAR HEAD PRESS %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V.HPB

XXX%

VAR HEAD PRESS %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CLP.1

ON/OFF

COOLER PUMP 1 RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CLP.2

ON/OFF

COOLER PUMP 2 RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CL.HT

ON/OFF

COOLER/PUMP HEATER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RMT.A

ON/OFF

REMOTE ALARM RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCUIT A COMPRESSOR TEST

 

 

 

 

ENTER

 

CC.A1

ON/OFF

COMPRESSOR A1 RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UL.TM

0 to 15

COMP A1 UnLOAD TIME

 

 

 

 

 

 

 

 

 

 

 

CMPA

 

 

 

CC.A2

ON/OFF

COMPRESSOR A2 RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC.A3

ON/OFF

COMPRESSOR A3 RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC.A4

ON/OFF

COMPRESSOR A4 RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MLV

ON/OFF

MINIMUM LOAD VALVE RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCUIT B COMPRESSOR TEST

 

 

 

 

ENTER

 

CC.B1

ON/OFF

COMPRESSOR B1 RELAY

See Note

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CMPB

 

 

 

CC.B2

ON/OFF

COMPRESSOR B2 RELAY

See Note

 

 

 

 

 

 

 

 

 

 

 

 

 

CC.B3

ON/OFF

COMPRESSOR B3 RELAY

See Note

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC.B4

ON/OFF

COMPRESSOR B4 RELAY

See Note

 

 

 

 

 

 

 

 

 

 

NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.

Copyright 2010 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53300067-01

Printed in U.S.A.

Form 30RAP-2T

Pg CL-10

12-10

Replaces: 30RAP-1T

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINECUT ALONG DOTTED LINE

Image 124
Contents Controls, Start-Up, Operation, Service, and Troubleshooting ContentsContents Safety ConsiderationsGeneral Basic Controls UsageUnit Sizes Unit Nominal Capacity TonsAccessory Navigator Display Module Mode RUN Service Temperatures SET Inputs Outputs Configuration Time Operating AlarmsScrolling Marquee Display Menu Structure TestRun Status Mode and Sub-Mode Directory StrtSUB-MODE Keypad Display SUB-ITEM Comment Entry Expansion VersService Test Mode and Sub-Mode Directory SUB-MODE Keypad Display Comment Entry Expansion TestOuts CmpaPressure Mode and Sub-Mode Directory Temperature Mode and Sub-Mode DirectorySet Points Mode and Sub-Mode Directory Inputs Mode and Sub-Mode Directory Outputs Mode and Sub-Mode DirectoryConfiguration Mode and Sub-Mode Directory SUB-MODE Keypad Display Comment Entry Expansion EXVOPT1 SUB-MODE Keypad Display Comment Entry Expansion UnitSUB-MODE Keypad Display Comment OPT2XXX XXX.X ΔF Date Time Clock Mode and Sub-Mode DirectoryDST Operating Mode and Sub-Mode Directory Alarms Mode and Sub-Mode DirectoryMode Item Expansion Description Operating ModesControl Module Communication ControlsCarrier Comfort Network CCN Interface CCN Communication Bus Wiring Thermistor DesignationsStatus Inputs Output RelaysAlmr AUXCCB CHCA30-4962 A30-4963A30-4964 Typical Control Box for 30RAP035-060Typical Wiring Schematic, 30RAP018-030 Units Power Wiring Typical Wiring Schematic, 30RAP018-030 Units Control Wiring A30-4966Typical Wiring Schematic, 30RAP035-060 Units Power Wiring 5283Typical Wiring Schematic, 30RAP035-060 Units Control Wiring A30-5284A30-4967 A30-4968Page CEPL130351 Deadband Multiplier 30RAP Unit Size Control Capacity Steps Capacity %A30-4969 Operating Envelope for R-410A CompressorA30-4970 Cooling Set Point Select30RAP Unit Size FAN Stages Optional Factory-Installed Hydronic Pack Control Methods and Cooling Set PointsControl Occupancy Cooling SET Point Select Clsp Type State CCN→PM1E = YES Configuring and Operating Dual Chiller Con Dual Chiller Configuration Master Chiller Example RsetNumber PartSUB-MODE Keypad Entry Display Item Expansion Comments Dual Chiller Configuration Slave Chiller Example Rset Slave CompleteTo 20 mA Reset Menu Configuration of 4 to 20 mA Cooling Set Point ControlConfiguring Outdoor Air and Space Temperature Reset Configuring Return Temperature ResetMode Keypad SUB Display RED LED Entry ModeOutdoor-Air Temperature Reset To 20-mA Demand Limiting Configuring Demand Limit Item Expansion Comment Entry ConfigurationPRE-START-UP System CheckA30-4978 START-UP and Operation30RAP Minimum Cooler Flow Maximum Cooler Flow Size Temperature Limits for Standard 30RAP Units Operating LimitationsOperation Sequence Unit Size 30RAService Electronic ComponentsEXV Steps Unit Size 30RAP EXV StepsA30-4971 Electronic Expansion Valve DetailsCompressor Replacement Refer to Fig Unit Torque SpecificationCooler A30-4972Oil Charge Check Refrigerant Feed ComponentsA30-4974 A30-4973LWT Check Unit Safeties Factory Settings, High-Pressure Switch FixedUnit Cutout CUT-IN Thermistor Well Temp Voltage Resistance Drop 100,260 143 86K Thermistor vs Resistance DTT DropA30-4975 A30-499A30-4976 AccsyP50 Fault History Last 8 faults P51 Software version Mode Nominal Voltage Control Input Start Jumper A30-4977TB1-TB2 TB13A-TB2Fault Codes Motormaster V Program Parameters for Operating Modes Parameters Description ModePID Replacement Modules MaintenanceReplacement Replacement Part Module Troubleshooting Advanced Scroll Temperature Protection Label 30RAP Unit Cutout CUT-IN SizeTroubleshooting Symptoms Cause RemedyAlarm and Alert Codes T051T110 T153 T197 Alert GENERATED? CCNCSB EMMCompressor Stuck on Failure Alarms Page Appendix a Display Tables SUB-MODE Display Item Description CommentView RUNStrt Appendix a Display TablesVers Pressures Mode and Sub-Mode Directory SUB-MODE Display Item Description Range Comment CoolHead FRZGEN.O SUB-MODE Display Item Description Comment HP.A HP.BEXV.A EXV.BRset Bcst SUB-MODE Display Item Description Comment Time DateDST HOL.LHD.19 HD.30 SUB-MODE Display Item Description Comment SCH.N SCH.LPER.1 PER.2PER.7 PER.6PER.8 Rcrn CrntHist Appendix B CCN Tables CCN Display Tables Aunit General Unit ParametersCCN Display Tables Circaan Circuit a Analog Parameters Description Value Units Point Name ForcibleAppendix B CCN Tables CCN Display Tables Circban Circuit B Analog ParametersCCN Configuration Tables Unit Unit Configuration CCN Configuration Tables OPTIONS1 Options 1 ConfigurationDescription Value Default Units Point Name CCN Display Tables Options Unit ParametersCCN Configuration Tables OPTIONS2 Options 2 Configuration CCN Configuration Tables Schedovr Timed Override SetupCCN Configuration Tables Display Marquee Display Setup CCN Configuration Tables Mmconf Motormaster ConfigurationCCN Service Tables Service Description Value Units Point Name Description Value Point NameCCN Maintenance Tables Alarms Description Version ValueCCN Maintenance Tables PM-PUMP CCN Maintenance Tables Runtest CCN Maintenance Tables Dualchil Appendix C Factory Settings for Pump and Manual Starters SettingAppendix D Optional Bacnet Communications Wiring Optional BACnet Communications WiringAppendix D Optional Bacnet Communications Wiring Table a SW3 Protocol Switch Settings For MS/TPTable B Baud Selection Table DS8 DS7 DS6 DS5 DS4 DS3Table C MS/TP Wiring Recommendations Specification RecommmendationAWG CL2PRmcorp Wiring Specifications Recommended Vendors and Part NumbersCMP RUN LED Error LED Status Table E LED Status IndicatorsLED Status Control Mode Table G Network Points List108 109 Appendix E Maintenance Summary and LOG Sheets 30RAP Maintenance Interval RequirementsWeekly QuarterlyAppendix E Maintenance Summary and LOG Sheets 30RAP Weekly Maintenance LogUnit Section Action Entry 30RAP Monthly Maintenance LogPSI 30RAP Seasonal Shutdown Log 113Copyright 2010 Carrier Corporation START-UP Checklist for 30RAP Liquid Chiller Remove and use for Job File Project InformationII. Preliminary Equipment Check Design InformationIII. Unit Start-Up Start and Operate Machine. Complete the FollowingDual Chiller Control Only Mode RUN Status Record Software VersionsUnit Configuration Settings OPTIONS1 Options ConfigurationSubmode Item Expansion Display Entry OPT1OPTIONS2 Options Configuration CCN CCN Network ConfigurationHP.A Head Pressure Cmp. Delta Configuration HP.B Head Pressure Cmp. Delta ConfigurationEXV.A Circuit a EXV Configuration EXV.B Circuit B EXV ConfigurationMM Motormaster Configuration Settings EXV.BRset Reset Configuration Settings Slct Setpoint and Ramp Load ConfigurationSetpoint SUB-MODE Keypad Display Comment Entry Expansion
Related manuals
Manual 40 pages 58.51 Kb

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.