Carrier 30RAP010-060 specifications Thermistor Well

Page 53

disconnected from J8. Compare the values determined with the value read by the control in the Temperatures mode using the scrolling marquee display.

Pressure Transducers — The suction and discharge transducers are different part numbers and can be distinguished by the color of the transducer body, suction (yellow) and dis- charge (red). No pressure transducer calibration is required. The transducers operate on a 5 vdc supply, which is generated by the main base board (MBB). See Fig. 29 for transducer con- nections to the J8 connector on the MBB.

TROUBLESHOOTING — If a transducer is suspected of be- ing faulty, first check supply voltage to the transducer. Supply voltage should be 5 vdc ± 0.2 v. If supply voltage is correct, compare pressure reading displayed on the scrolling marquee display module against pressure shown on a calibrated pressure gauge. Pressure readings should be within ± 15 psig. If the two readings are not reasonably close, replace the pressure transducer.

Chilled Water Flow Switch — A factory-installed flow switch is installed in the leaving fluid piping for all units without the factory-installed hydronic package. See Fig. 30. Units with the optional hydronic package have the flow switch installed in the entering fluid piping. This is a thermal-disper- sion flow switch with no field adjustments. The switch is set for approximately 0.5 ft/sec of flow. The sensor tip houses two thermistors and a heater element. One thermistor is located in the sensor tip, closest to the flowing fluid. This thermistor is used to detect changes in the flow velocity of the liquid. The second thermistor is bonded to the cylindrical wall and is af- fected only by changes in the temperature of the liquid. The thermistors are positioned to be in close contact with the wall of the sensor probe and, at the same time, to be kept separated from each other within the confines of the probe.

In order to sense flow, it is necessary to heat one of the thermistors in the probe. When power is applied, the tip of the probe is heated. As the fluid starts to flow, heat will be carried away from the sensor tip. Cooling of the first thermistor is a function of how fast heat is conducted away by the flowing liquid.

The difference in temperature between the two thermistors provides a measurement of fluid velocity past the sensor probe. When fluid velocity is high, more heat will be carried away from the heated thermistor and the temperature differential will be small. As fluid velocity decreases, less heat will be taken from the heated thermistor and there will be an increase in tem- perature differential.

When unit flow rate is above the minimum flow rate, then the output is switched on, sending 24 vac to the MBB to prove flow has been established.

For recommended maintenance, check the sensor tip for build-up every 6 months. Clean the tip with a soft cloth. If

necessary, build-up (e.g., lime) can be removed with a common vinegar cleansing agent.

The flow sensor cable is provided with (3) LEDs that indi- cate if 24 vac power is present and also status of the switch contacts. The LEDs are as follows:

Green LED ON – 24 vac present

One Yellow LED ON – Flow sensor switch OPEN

Two Yellow LED ON – Flow sensor switch CLOSED

If nuisance trips of the sensor are occurring, follow the steps below to correct the situation:

1.Check to confirm that the factory installed strainer is clean. Use the blow-down valve provided or remove the screen and clean it. For the case of VFD controlled pumps, ensure that the minimum speed setting has not been changed.

2.Measure the pressure drop across the cooler or cooler/ pump system and compare this to the system requirements.

3.Verify that cable connections at the switch and at the ter- minal block are secure.

4.For factory-installed hydronic systems, verify that:

All air has been purged from the system.

Circuit setter balance valve has been correctly set.

5.Pump impeller has been improperly trimmed and is not providing sufficient flow.

6.Wrong pump motor rotation. Pump must rotate clockwise when viewed from motor end of pump.

Strainer — Periodic factory-installed strainer cleaning is required. Pressure drop across strainer in excess of 3 psi (21 kPa) indicates the need for cleaning. Normal (clean) pres- sure drop is approximately 1 psi (6.9 kPa). Open the factory- installed blowdown valve to clean the strainer. If required, shut the chiller down and remove the strainer screen to clean. When strainer has been cleaned, enter ‘YES’ for Strainer Mainte- nance Done (Run StatusPMS.T.MN).

Condenser Fans — Each fan is supported by a formed wire mount bolted to a fan deck and covered with a wire guard.

METAL FANS — The exposed end of fan motor shaft is pro- tected from weather by grease and a rubber boot. If fan motor must be removed for service or replacement, be sure to re- grease fan shaft and reinstall fan guard. For proper perfor- mance with the value sound fan option, fan web should be

0.32in. (8 mm) below top of orifice on the fan deck to top of the fan hub. (See Fig. 31.) Tighten set screws to 15 ± 1 ft-lb (20 ± 1.3 N-m).

IMPORTANT: Check for proper fan rotation (clockwise when viewed from above). If necessary, switch any 2 power leads to reverse fan rotation.

5/8 in. HEX

1/4-18 NPT

 

6" MINIMUM

CLEARANCE FOR

THERMISTOR

REMOVAL

Fig. 28 — Thermistor Well

53

Image 53
Contents Contents Controls, Start-Up, Operation, Service, and TroubleshootingSafety Considerations ContentsBasic Controls Usage GeneralUnit Sizes Unit Nominal Capacity TonsAccessory Navigator Display Module SET Inputs Outputs Configuration Time Operating Alarms Mode RUN Service TemperaturesScrolling Marquee Display Menu Structure TestStrt Run Status Mode and Sub-Mode DirectoryVers SUB-MODE Keypad Display SUB-ITEM Comment Entry ExpansionSUB-MODE Keypad Display Comment Entry Expansion Test Service Test Mode and Sub-Mode DirectoryOuts CmpaSet Points Mode and Sub-Mode Directory Temperature Mode and Sub-Mode DirectoryPressure Mode and Sub-Mode Directory Outputs Mode and Sub-Mode Directory Inputs Mode and Sub-Mode DirectorySUB-MODE Keypad Display Comment Entry Expansion EXV Configuration Mode and Sub-Mode DirectorySUB-MODE Keypad Display Comment Entry Expansion Unit OPT1OPT2 SUB-MODE Keypad Display CommentXXX XXX.X ΔF DST Time Clock Mode and Sub-Mode DirectoryDate Alarms Mode and Sub-Mode Directory Operating Mode and Sub-Mode DirectoryOperating Modes Mode Item Expansion DescriptionCarrier Comfort Network CCN Interface ControlsControl Module Communication Thermistor Designations CCN Communication Bus WiringStatus Inputs Output RelaysAUX AlmrCCB CHCA30-4963 A30-4962Typical Control Box for 30RAP035-060 A30-4964Typical Wiring Schematic, 30RAP018-030 Units Power Wiring A30-4966 Typical Wiring Schematic, 30RAP018-030 Units Control Wiring5283 Typical Wiring Schematic, 30RAP035-060 Units Power WiringA30-5284 Typical Wiring Schematic, 30RAP035-060 Units Control WiringA30-4968 A30-4967Page CEPL130351 30RAP Unit Size Control Capacity Steps Capacity % Deadband MultiplierOperating Envelope for R-410A Compressor A30-496930RAP Unit Size FAN Stages Cooling Set Point SelectA30-4970 Control Methods and Cooling Set Points Optional Factory-Installed Hydronic PackControl Occupancy Cooling SET Point Select Clsp Type State CCN→PM1E = YES Configuring and Operating Dual Chiller Con Rset Dual Chiller Configuration Master Chiller ExampleSUB-MODE Keypad Entry Display Item Expansion Comments PartNumber Rset Slave Complete Dual Chiller Configuration Slave Chiller ExampleMenu Configuration of 4 to 20 mA Cooling Set Point Control To 20 mA ResetConfiguring Return Temperature Reset Configuring Outdoor Air and Space Temperature ResetMode Keypad SUB Display RED LED Entry ModeOutdoor-Air Temperature Reset To 20-mA Demand Limiting Item Expansion Comment Entry Configuration Configuring Demand LimitPRE-START-UP System Check30RAP Minimum Cooler Flow Maximum Cooler Flow Size START-UP and OperationA30-4978 Operating Limitations Temperature Limits for Standard 30RAP UnitsOperation Sequence Unit Size 30RAElectronic Components ServiceEXV Steps Unit Size 30RAP EXV StepsElectronic Expansion Valve Details A30-4971Unit Torque Specification Compressor Replacement Refer to FigCooler A30-4972Check Refrigerant Feed Components Oil ChargeLWT A30-4973A30-4974 Unit Cutout CUT-IN Factory Settings, High-Pressure Switch FixedCheck Unit Safeties Thermistor Well Temp Voltage Resistance Drop 100,260 143 Drop 86K Thermistor vs Resistance DTTA30-499 A30-4975A30-4976 AccsyP50 Fault History Last 8 faults P51 Software version A30-4977 Mode Nominal Voltage Control Input Start JumperTB1-TB2 TB13A-TB2Fault Codes PID Parameters Description ModeMotormaster V Program Parameters for Operating Modes Replacement Replacement Part Module MaintenanceReplacement Modules Troubleshooting 30RAP Unit Cutout CUT-IN Size Advanced Scroll Temperature Protection LabelSymptoms Cause Remedy TroubleshootingT051 Alarm and Alert CodesT110 T153 T197 CCN Alert GENERATED?CSB EMMCompressor Stuck on Failure Alarms Page SUB-MODE Display Item Description Comment Appendix a Display TablesView RUNVers Appendix a Display TablesStrt Pressures Mode and Sub-Mode Directory Cool SUB-MODE Display Item Description Range CommentHead FRZGEN.O SUB-MODE Display Item Description Comment HP.B HP.AEXV.B EXV.ARset Bcst Date SUB-MODE Display Item Description Comment TimeDST HOL.LHD.19 HD.30 SCH.L SUB-MODE Display Item Description Comment SCH.NPER.1 PER.2PER.8 PER.6PER.7 Hist CrntRcrn CCN Display Tables Aunit General Unit Parameters Appendix B CCN TablesCCN Display Tables Circaan Circuit a Analog Parameters Description Value Units Point Name ForcibleCCN Display Tables Circban Circuit B Analog Parameters Appendix B CCN TablesCCN Configuration Tables OPTIONS1 Options 1 Configuration CCN Configuration Tables Unit Unit ConfigurationDescription Value Default Units Point Name CCN Display Tables Options Unit ParametersCCN Configuration Tables Schedovr Timed Override Setup CCN Configuration Tables OPTIONS2 Options 2 ConfigurationCCN Configuration Tables Mmconf Motormaster Configuration CCN Configuration Tables Display Marquee Display SetupCCN Service Tables Service Description Value Point Name Description Value Units Point NameDescription Version Value CCN Maintenance Tables AlarmsCCN Maintenance Tables PM-PUMP CCN Maintenance Tables Runtest CCN Maintenance Tables Dualchil Setting Appendix C Factory Settings for Pump and Manual StartersOptional BACnet Communications Wiring Appendix D Optional Bacnet Communications WiringTable a SW3 Protocol Switch Settings For MS/TP Appendix D Optional Bacnet Communications WiringTable B Baud Selection Table DS8 DS7 DS6 DS5 DS4 DS3Specification Recommmendation Table C MS/TP Wiring RecommendationsAWG CL2PCMP Wiring Specifications Recommended Vendors and Part NumbersRmcorp LED Status Table E LED Status IndicatorsRUN LED Error LED Status Table G Network Points List Control Mode108 109 30RAP Maintenance Interval Requirements Appendix E Maintenance Summary and LOG SheetsWeekly Quarterly30RAP Weekly Maintenance Log Appendix E Maintenance Summary and LOG SheetsPSI 30RAP Monthly Maintenance LogUnit Section Action Entry 113 30RAP Seasonal Shutdown LogCopyright 2010 Carrier Corporation Remove and use for Job File Project Information START-UP Checklist for 30RAP Liquid ChillerII. Preliminary Equipment Check Design InformationStart and Operate Machine. Complete the Following III. Unit Start-UpDual Chiller Control Only Record Software Versions Mode RUN StatusOPTIONS1 Options Configuration Unit Configuration SettingsSubmode Item Expansion Display Entry OPT1CCN CCN Network Configuration OPTIONS2 Options ConfigurationHP.A Head Pressure Cmp. Delta Configuration HP.B Head Pressure Cmp. Delta ConfigurationEXV.B Circuit B EXV Configuration EXV.A Circuit a EXV ConfigurationMM Motormaster Configuration Settings EXV.BSlct Setpoint and Ramp Load Configuration Rset Reset Configuration SettingsSetpoint Entry Expansion SUB-MODE Keypad Display Comment
Related manuals
Manual 40 pages 58.51 Kb

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.