e.Select I/O Modules.
f.In the right pane,
g.Click the Alerts tab.
h.
NOTE: The alerts may not appear immediately. If the alerts do not appear, wait 10 seconds and then click Refresh.
Next steps
1.Use SupportAssist to send diagnostic data to Dell Technical Support Services.
Replace Both Storage Controllers in Succession
Use this procedure to replace both storage controllers, one at a time.
Prerequisites
1.Use SupportAssist to send diagnostic data to Dell Technical Support Services.
2.Shut down the left storage controller.
About this task
This procedure is useful if you are swapping out degraded, but operational storage controllers. Steps
1.Make sure all of the cables are labeled.
2.Disconnect all of the cables from the left storage controller
3.Remove the battery from the left storage controller.
4.Squeeze the release tab on the storage controller release lever.
5.Pull the release lever away from the chassis.
6.Grasp the release lever and pull the storage controller away from the chassis.
Replacing SCv2000/SCv2020 Components | 33 |